Measure the free wall before you open a catalogue
Go down to the room with a tape and put it on the wall under the window, not on the floor. In a basement being finished that stretch is shorter than anyone remembers: the stair carriage eats one end of it, a service chase for the boiler flue or the waste stack eats the other, the window well drops the sill lower than the drawing suggested, and somewhere along it a sump lid has to stay liftable. What is left — five feet, six feet, sometimes less — is the number the whole job turns on, because electric baseboard is the one heat emitter whose capacity is measured in feet of wall rather than in cubic inches of cabinet.
That is also the reason the system gets chosen. There is no duct to extend through a finished ceiling, no refrigerant line, no condensate to fall, no flue and nothing outdoors: a chassis screws to the studs, a two-pole circuit lands in its wiring compartment, and the room has heat that zones itself without a damper anywhere. For a basement bedroom or a two-hundred-square-foot addition that is a genuinely good trade, and it stays good right up to the point where the required wattage needs eleven feet of wall in a room that has six.
So the order of work is not the order of the conversation. The owner wants to talk about which heater to buy. The job actually runs: settle the wall build, then the watts the finished room will lose, then the enclosure length those watts need, then whether that length fits where it has to go, and only then the circuit. Move any of those and everything downstream of it changes.
Sizing the room you are going to end up with, not the one you are standing in
A whole-house heat loss figure is no help here. Electric baseboard is bought and controlled one room at a time, so the number that matters is the loss of this room, at the outdoor design condition, in the state it will be in when the drywall is up and the window is trimmed. A bare basement with a concrete wall and a joist bay open to the rim is not that room, and measuring the space you are standing in will size a heater for a building that stops existing the week the insulation goes in.
The starting rule of thumb across most of the North American trade is ten watts per square foot of floor, and its assumptions are worth stating out loud: roughly eight foot ceilings, an average insulated envelope, a room doing nothing unusual. Below grade a basement can beat that comfortably. Soil is a milder neighbour than winter air and changes temperature slowly, so an insulated below-grade wall loses less and loses it more steadily than an above-grade wall of the same area — which is why the ASHRAE Handbook — Fundamentals gives below-grade transmission its own method rather than folding it into the same arithmetic.
The addition goes the other way. Three exposed walls, a floor over a vented crawl or a cantilever, a disproportionate area of glass because that was the point of building it, and often a ceiling higher than eight feet. Ten watts per square foot on a sunroom is how a room ends up with a heater that runs continuously in January and still reads three degrees short.
The defensible version of this number is a room-by-room calculation to ANSI/ACCA Manual J, which counts each wall by its own area, orientation and construction, counts the glazing and the infiltration separately, and hands back a heating load for that room alone. It costs an afternoon or a fee, and it is worth one or the other whenever the room is unusual, the climate is severe, or the answer sits near a boundary between two heater sizes.
There is a legal floor underneath all of it. The International Residential Code's required-heating provision obliges a dwelling to have heating capable of holding 68 degrees Fahrenheit, twenty degrees Celsius, measured a stated distance above the floor and in from the exterior walls — a detail that catches out basement conversions done without a permit and then discovered at sale. Size to hold that at the local design temperature, not at the coldest hour ever recorded, and not at whatever the owner keeps the rest of the house at.
Put the finished room's floor area in and read the watts as an opening position — it converts to BTU per hour alongside, which is the unit every other heating appliance on the job will be quoted in.
The floor area of the room to heat.
Recommended heater size
2,200 W
This is a general rule of thumb for average-insulated rooms with standard 8 ft (2.5 m) ceilings. Poorly insulated rooms, high ceilings, large uncovered windows, or very cold climates need more capacity — a full room-by-room heat loss calculation gives a more precise number.
- Equivalent heat output
- 7,506.71 BTU/hr
They open the calculator with your figures already in it
Electric Baseboard Heater Sizing Calculator: 2,200 W — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 2,200 W — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- The 10 watts per square foot figure is a flat rule of thumb, not a heat loss calculation. Insulation level, air tightness, window area and orientation, how many walls face outside, and the local design temperature are not inputs, so a corner room with large glazing in a cold climate and an interior room in a well-insulated house of the same floor area return the same number.
- Floor area is the only input, so the assumed standard ceiling height is baked in. Vaulted or double-height rooms, and rooms sitting over an unheated crawl space, garage or open porch, are not accounted for.
- This is a heat output figure, not an electrical calculation. It does not size a branch circuit, check conductor ampacity or breaker rating, distinguish 120 V from 240 V units, or consider how many heaters share a circuit. Electric space heating is a continuous load and the circuit has to be designed and permitted separately.
- The answer is a continuous wattage, not a product. Baseboard heaters are sold in fixed wattages at a fixed watts-per-foot density, so the required output translates into a specific physical length that has to fit on clear wall — usually under a window, away from furniture, curtains and receptacles.
- Use a room-by-room heat loss calculation anywhere a design figure has to stand up: whole-house sizing, permit or rebate submissions, or high-performance builds, where this rule of thumb consistently oversizes because it was calibrated on ordinary older construction.
The wattage is a property of the wall, not of the room
Two rooms with identical dimensions and different wall builds are different loads, and on a basement the difference is not marginal. Bare concrete against soil, a stud wall with batt in it and nothing else, and continuous rigid foam against the concrete behind an insulated stud bay are three separate heaters. The wall build is therefore a heating decision that happens to be made by whoever is framing, which is why it belongs in this conversation and not in a different one held three weeks later.
Foam directly against the concrete does two jobs at once. It adds resistance, and it puts the cold face of the assembly out of reach of room air, so the concrete stops being a condensing surface for humidity arriving from inside — the failure that turns an insulated basement wall into a mould complaint. Whichever board is specified, expanded or extruded polystyrene to ASTM C578 or faced polyisocyanurate to ASTM C1289, it has to be covered on the room side: the IRC's foam plastic provisions require an approved thermal barrier over it, which in practice is the gypsum board the heater is about to be screwed through. The rim joist above deserves the same attention, since a cold band of joist ends around the perimeter undoes a good wall quietly.
What the heater is screwed to
- Heater enclosure and element — occupies only part of the wall, and its length is set by the watts the finished assembly behind it still loses Baseboard Heater Length Calculator
- Skirting either side — the trim run stops dead at each end cap, so the heater is a deduction on the moulding order the way a doorway is Baseboard & Trim Calculator
- Gypsum board — the room face the chassis fixes through, and the thermal barrier the code wants over any foam plastic behind it Drywall Calculator
- Insulated stud bay — needs blocking added at the heater's fixing centres, since a chassis held by board alone pulls out when knocked Insulation Batt Calculator
- Continuous rigid foam — held tight to the concrete so the cold face stops being a surface room humidity can condense on Foam Board Insulation Calculator
- Foundation wall — loses heat to soil rather than to outdoor air, which is why a basement room can undercut the floor-area rule of thumb
Take the below-grade wall area you are about to cover and turn it into boards before the heater is sized, because every sheet on that wall comes back off the wattage the room ends up needing.
SettingsSettings for this calculation
The standard allowance most suppliers and estimating guides assume for ordinary work.
The total wall, foundation, or roof deck area to cover.
Offcuts from fitting boards between framing, around openings and at corners.
Foam board sheets needed
15 sheets (4x8 ft)
- Area to cover (with waste)
- 473 sq ft
They open the calculator with your figures already in it
Foam Board Insulation Calculator: 15 sheets (4x8 ft) — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- This counts sheets to cover an area. It does not choose a thickness or R-value, check your climate zone's requirement for continuous insulation, or confirm the board's compressive strength grade suits a load-bearing position under a slab or screed.
- The count is for a single layer. A staggered two- or three-layer build-up is a separate full-area order for each layer, so run the area through once per layer rather than entering the combined thickness.
- The waste allowance is a flat uplift on area, not a cutting layout. Rafter bays, hips, curved walls and dense penetrations throw off more offcuts than that, and offcuts from one bay are often unusable in the next. A wall whose window and door openings you did not deduct is over-ordered by roughly their area.
- It assumes every board is the market's standard full sheet. It does not cover the 2 ft wide XPS or 1200 x 600 mm half boards some ranges are sold in, and it does not deduct the overlap on tongue-and-groove or shiplap edges, which cover less than the board's nominal face area.
- Nothing beyond the boards is counted: seam tape, adhesive or foam, fixings and washers sized to the board thickness, furring, and any separate vapour or air control layer. Rigid foam is also combustible, and building codes generally require a thermal or ignition barrier between it and an occupied space. This calculator neither sizes nor includes that.
Watts become inches of enclosure
Inside the cabinet is a resistance element in a finned sheath, and the cabinet is essentially a housing sized to hold a length of it. The specification that converts a load into a physical dimension is watts per linear foot. Ordinary residential units in North America run around 250 watts per foot at 240 volts — call it 820 watts per metre — and most of the market is built around that density. Lower-density models at roughly 175 to 190 watts per foot are not a worse product: a cooler sheath scorches less household dust and gives a gentler surface in a nursery or anywhere furniture ends up close. They simply cost wall, and here wall is the currency.
Stock lengths are short and few — two, three, four, five, six and eight feet cover most catalogues — so the arithmetic almost never lands on a product and you round up. Rounding up is safe here in a way it is not on other equipment: a thermostatically controlled resistance heater with no compressor, no ignition sequence and no minimum run time simply reaches setpoint sooner and switches off, with no short-cycling penalty to pay and no latent load left undone. Rounding down is the real risk, because an undersized element has no reserve on the two or three coldest nights of the year.
Once the requirement passes what one unit can supply, you are fitting two, and that is a design event rather than a purchase detail. Two units can share one circuit where the circuit's capacity allows and be driven by one thermostat, which keeps the control simple. But they need two runs of clear wall, and the second run is usually on a wall the furniture had plans for. Finding that out at the sizing stage costs a conversation; finding it out when the chassis are on site costs a wall.
One trap is worth naming before it is met. A heater rated at 240 volts fed from a 208 volt supply does not deliver 87 percent of its rating — output on a fixed resistance follows the square of the applied voltage, so it delivers about 75 percent, and a nominal 1,500 watt unit becomes about 1,125 watts. In apartment blocks and light commercial buildings where 208 volts is what the panel offers, manufacturers publish separate 208 volt ratings for the same physical unit. Read the nameplate voltage before the nameplate wattage.
| Target wattage | Length at 250 W/ft | Length at 175 W/ft | Nearest stock unit at 250 W/ft |
|---|---|---|---|
| 750 W | 3.0 ft | 4.3 ft | 3 ft |
| 1,000 W | 4.0 ft | 5.7 ft | 4 ft |
| 1,250 W | 5.0 ft | 7.1 ft | 5 ft |
| 1,500 W | 6.0 ft | 8.6 ft | 6 ft |
| 2,000 W | 8.0 ft | 11.4 ft | 8 ft |
| 2,500 W | 10.0 ft | 14.3 ft | two units, 8 ft plus 2 ft |
Feed it the watts you settled on and the density printed on the model you are actually pricing, and it rounds to a length somebody sells — then measure that length against the wall you taped at the start.
The recommended heater wattage for the room, e.g. from the Baseboard Heater Sizing Calculator.
Check the specific heater product's rated watts per linear foot.
Recommended heater length
8 ft
- Minimum length needed
- 8 ft
They open the calculator with your figures already in it
Baseboard Heater Length Calculator: 8 ft — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- This sizes the heater, not the circuit that feeds it. It does not check breaker or conductor size, the continuous-load allowance electrical codes apply to fixed electric space heating, or whether an existing circuit has capacity left for the load. That is a separate branch-circuit calculation, and in most jurisdictions permitted and inspected work.
- The watts-per-foot figure is tied to the heater's nameplate voltage. Output on a fixed resistance element follows the square of the applied voltage, so a 240 V-rated unit on a 208 V supply gives roughly three-quarters of its rating and on 120 V about a quarter — read the nameplate voltage before the nameplate wattage. The model also assumes an electric resistance element; hydronic baseboard is rated in BTU/hr per foot at a stated supply water temperature and is not what this calculates.
- The target wattage is taken as given and never checked. Insulation, glazing area, ceiling height, air leakage, exposure and climate do not enter the arithmetic, so a wattage that came from a floor-area rule of thumb produces a length that is only as good as that rule of thumb.
- It returns one unit from the common short stock lengths and does not split a load across two or more heaters, balance them between walls, or look for the longer cabinets some manufacturer lines carry. Once the requirement passes what a single stock unit supplies, the layout becomes a design decision this does not make.
- It says nothing about whether the length fits. Door swings, stair carriages, window returns, mechanical chases and furniture all shorten the usable run, and the manufacturer's clearances to finished floor level, carpet, drapes and receptacles govern where the cabinet may go — a convector that cannot draw air across its fins does not deliver its rating regardless of length.
Under the glass, and clear of everything else
Baseboard goes under the window for a reason that survives inspection. Glass is the coldest surface in the room; air touching it cools, gets denser and falls, and that sheet of cold air then runs across the floor. A convector under the window puts a rising column straight up into it, the two cancel, and the occupant stops feeling a draught from a window that is not leaking. ANSI/ASHRAE Standard 55 describes both mechanisms this placement answers — draught, and radiant asymmetry off a cold surface.
Height above the floor is set by the listing, and the floor in question is the finished one. A heater set off the slab and then buried behind carpet and underlay has lost the clearance its approval assumed. Establish finished floor level on a story pole before anything is fixed, and set the chassis off that mark rather than off whatever surface happens to be there on the day.
A convector that cannot draw air does nothing, and the room will be full of ways to stop it: curtains hanging into the intake, a sofa back against the front face, a bookcase built over the top. Each turns a correctly sized heater into an underperforming one and puts heat into the wrong surface doing it. The manual states the clearances; the furniture layout has to honour them, which means asking where the sofa goes while the wall is still a pencil line.
Receptacles have their own quarrel with this. Manufacturers prohibit fitting a heater directly beneath a receptacle outlet, because a lamp flex draped over a hot element is exactly the hazard it looks like. NFPA 70's receptacle-spacing rules recognise the conflict from the other side, treating wall space occupied by a permanently installed baseboard heater differently from ordinary wall space, and some listed heaters carry a factory-fitted receptacle section so the wall can still be served. What matters on site is that the outlet layout and the heater run get agreed as one drawing.
Then the rest of the obstacle course: door swings, the stair carriage, the beam pocket, the mechanical chase, the window well returns. Basements concentrate all of it on the same exterior wall the heater wants, which is why the free run is so often shorter than the wall.
Last, the enclosure has to be allowed to move. A resistance element grows measurably when it is hot and shrinks back when it is not, and a chassis screwed hard through every fixing hole converts that movement into a tick the occupant will hear through a quiet ceiling and blame on the plumbing. The slotted fixings in the chassis are slotted deliberately. Leave them that way.
- Mark finished floor level on a story pole and set every heater height from that mark, not from the slab or the subfloor.
- Chalk the heater runs on the wall before the electrician marks outlet centres, so the two layouts get agreed once instead of argued twice.
- Add blocking in the stud bays at the chassis fixing centres while the wall is still open.
- Bring the cable in at the end of the chassis the manual nominates; the opposite end is usually blanked and cannot be used.
- Screw through the slotted fixings without pinching them, leaving the element free to grow along the enclosure.
- Hold the floor covering's expansion gap open behind the heater rather than trapping the floor under the chassis.
- Energise it once before the covers and trim go on, and confirm it warms along its whole length rather than at one end.
Where the skirting stops
The heater interrupts the trim run, and whoever orders moulding needs to know that before the delivery arrives. A baseboard heater is a deduction from the room perimeter the same way a doorway is: the skirting dies into an end cap at each side of the unit and picks up beyond it. Order the perimeter, subtract the doorways, subtract every heater run, then apply waste to what is left — applying waste to a perimeter that still contains the heater lengths is how a small room ends up with two spare sticks.
Heights have to be settled at the same time. Most baseboard cabinets are taller than a standard skirting profile, so the trim either dies into the end cap at a mismatch or the skirting is chosen to suit. Neither is wrong, but it is a decision, and it is far cheaper to make it while the moulding is still on a supplier's shelf than after it is coped and nailed.
Underneath, a floating floor still needs its perimeter gap where it runs behind the chassis, and a chassis screwed down through the floor covering removes that gap in the one place nobody thinks to check. Run the floor to the wall with its gap intact, fix the heater to the wall and not to the floor, and let the two stay independent.
Enter the room and its doorways, then take the heater lengths off the result before you buy sticks — the heater is a hole in the skirting run, and it is the deduction most orders forget.
SettingsSettings for this calculation
The standard allowance most suppliers and estimating guides assume for ordinary work.
The length of the room.
The width of the room.
Doorway openings don't need baseboard.
The length trim is sold in at your supplier.
Extra trim for mitres, coped joints and the odd bad cut.
Estimated baseboard & trim needed
50.65 linear ft
- Room perimeter (minus doorways)
- 46.05 linear ft
- Sticks needed
- 7 x 8 ft sticks
They open the calculator with your figures already in it
Baseboard & Trim Calculator: 50.65 linear ft — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
Schematic layout — positions are illustrative, quantities are exact. This calculator is told how many doors and windows there are, never where they sit or how big each one is, so they are drawn evenly spaced at the standard allowance it deducts. Moving one would change nothing in the numbers above.
What this calculation does not cover
- The run is 2 x (length + width), so the room is taken as a plain rectangle with four square corners; an alcove, a chimney breast, a bay, an L-shaped plan or a return wall all change the length of skirting and none of them can be typed in, so a room that is not four straight walls has to be measured wall by wall and added up by hand.
- Every doorway is deducted at a flat 0.9 m (3 ft) no matter what it measures, so a double door, a wide cased opening or a patio slider is under-deducted while a 760 mm (30 in) single door is over-deducted, and the architrave is not in the deduction at all — skirting dies into the casing, so the real gap at each opening is the opening plus the width of two casings.
- Waste is taken as a percentage of the whole run rather than against the number of cuts, so at the same setting a small room with eight mitred or coped corners loses proportionally more off the ends than one long wall does; the sources quote 10-15%, and a room like that belongs at the top of the band.
- The stick figure is one division — run with waste over a single stock length, rounded up — which is a quantity rather than a cut list: it assumes any wall longer than a stick will be scarf-jointed and that an offcut left on one wall can be carried to the next. Count wall by wall instead if you want the joint-free runs the stock-length note argues for, since a 4.6 m wall swallows two 2.4 m lengths and leaves 200 mm that fits nowhere.
- Nothing about the profile reaches the numbers — height, thickness, material and whether the base is a single section or a base with a separate shoe or cap moulding are all outside it, and a two-piece base means ordering this same perimeter twice in two sections. Fasteners, adhesive, filler, caulk and paint are not counted either, no price is attached to either figure, and each side is capped at 30 m, so a whole-floor take-off has to be broken into rooms.
One dedicated two-pole circuit, sized at 125 percent
Fixed electric space heating is treated as a continuous load, which means the branch-circuit conductors and the overcurrent device are both sized at 125 percent of the connected heating load rather than at the load itself. NFPA 70's Article 424, Fixed Electric Space-Heating Equipment, is where that requirement lives, working alongside the branch-circuit rules of Article 210; the same arithmetic is often quoted the other way round as never loading a standard breaker beyond 80 percent of its rating.
Work it once and it stops being abstract. A 1,500 watt heater at 240 volts draws 6.25 amps; at 125 percent that is 7.8 amps of design current. Two of them on one circuit is 3,000 watts, 12.5 amps, 15.6 amps design — comfortably inside a 20 amp two-pole circuit and comfortably outside a 15 amp one. Add a third and the circuit is finished. Do this arithmetic before you decide how many heaters share a run, because the answer sometimes says two circuits where the plan assumed one.
The circuit is dedicated and the pole count is two. Nothing else belongs on it — no receptacles, no lighting, no smoke alarm — and the disconnecting means Article 424 requires has to be present and identifiable, which is really a question about what the thermostat opens. A single-pole line-voltage thermostat interrupts one leg and leaves the other energised inside the heater with the control reading off; a double-pole opens both, and on an owner-occupied basement it is the one to specify. Whether the circuit also needs arc-fault or ground-fault protection depends on the room and on the code edition adopted locally, so ask rather than assume. Canadian work answers to CSA C22.1, and equipment sold into Europe is built to the room-heater requirements of IEC 60335-2-30.
Nameplate voltage governs everything downstream of it. The compact 120 volt units that look convenient for a small room draw twice the current for the same heat, so above about 1,000 watts 240 volts is what the trade fits, and it is what the rest of this page assumes.
Set the circuit voltage to 240, enter the connected watts of every heater you intend to put on that breaker, and see how much of its continuous capacity is genuinely left before a third unit joins them.
The amp rating printed on the breaker in your panel.
Most household outlets in North America are 120V; large appliances (dryers, ranges, EV chargers) are often 240V.
The sum of the wattage of everything plugged into this circuit at once.
Current draw
10 A
- Total connected load
- 1,200 W
- Safe continuous limit (80% rule)
- 16 A
- Safe continuous limit
- 1,920 W
- % of safe continuous capacity used
- 62.5 %
They open the calculator with your figures already in it
Electrical Circuit Load Calculator: 10 A — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 10 A — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- ONE circuit, not the panel. Whether the service and the panel can carry everything together is a separate calculation under the code's demand-factor rules, and a house full of individually compliant circuits can still overload its supply.
- Says nothing about the WIRE. Conductor ampacity is set by the conductor, its insulation, the ambient temperature and how many current-carrying conductors share a raceway — a breaker rating does not guarantee the cable behind it, and a correctly sized breaker on undersized cable is the dangerous combination.
- Voltage drop over the run is not checked here. A circuit inside its current limit can still deliver too little voltage at the far end, which is a separate calculation.
- Motor and compressor loads draw several times their running current at start-up. Nameplate watts describe the running condition and understate what the breaker sees on a cold morning.
- The 80% figure applies to CONTINUOUS loads — three hours or more at full draw. A load that is genuinely intermittent may use more of the breaker's rating, and which of the two a given appliance is can be a judgement.
Code thresholds this tool can check
Code thresholds this tool can check
Checked for United States. Each check below names the body that published the limit it uses. Switching market re-runs them. This is not a code review and has no official standing.
These checks cover only the specific numeric limits listed below. They are not a complete code review: fire separation, egress, structural capacity and accessibility provisions are outside their scope, and only the handful of local amendments offered in the selector are modelled — your municipality may have others. Passing every check here does not make a design compliant. Final approval rests with your local building authority.
Volts lost on the way are watts lost at the wall
A resistance heater is not a constant-power device. Its element is a fixed resistance, so output follows the square of the voltage actually appearing across it — which means a run that sags five percent under load delivers about 90 percent of nameplate, turning a 1,500 watt heater into roughly 1,354 watts. It does that silently, all winter, on a system with no gauge, no fault code and nothing to indicate that anything is wrong other than a room that never quite arrives at setpoint. NFPA 70 treats its familiar three percent branch-circuit figure as informative guidance rather than a hard requirement, while BS 7671 imposes limits that have to be met; the element is indifferent to which regime it is under.
Additions are where this bites, because the panel is in the old house and the heater is on the far wall of the new room. Measure the conductor path rather than the plan dimension — a run that scales at forty feet becomes seventy once it climbs out of the basement, crosses the joists the wrong way and turns three corners at the panel. If the calculation says upsize, upsize before the wall closes, and check the larger conductor still lands in the heater's own terminal block, which on this equipment is small.
Run it at 240 volts with the current the heaters actually draw — connected watts over 240, not the 125 percent figure the breaker was chosen on — and with the route length you walked. The output penalty is the square of whatever percentage it hands back.
Copper, or aluminum — the metal printed on the jacket (CU or AL).
The size printed on the jacket: an AWG number up to 4/0, then kcmil.
Single phase — including a 240 V circuit and DC — or a balanced three-phase circuit.
The distance from the panel to the load, one direction only.
The expected current draw of the load in amps.
The nominal circuit voltage — line to line for three phase.
Voltage drop
1.936 V
- Voltage drop
- 1.61 %
- Voltage at the load
- 118.06 V
- K constant, Ω·cmil per ft
- 12.9
- Conductor area, circular mils
- 6,530
They open the calculator with your figures already in it
Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil): 1.94 V — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 1.936 V — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- VOLTAGE DROP IS NOT AMPACITY, and the two are different questions with different answers. A conductor can stay inside the 3% suggestion and still be too small to carry the current without overheating, and it can be thermally adequate and still drop too much over a long run. Both checks have to be made, and only one of them is made here.
- The K constants are DC resistance at 75 °C (167 °F) for uncoated copper and for aluminum, the basis of NEC Chapter 9 Table 8. The table's size-by-size resistances differ from the single constant by a percent or so either way, and the table is not reproduced here. A conductor running cooler drops a little less and one at a 90 °C (194 °F) rating a little more; tinned (coated) copper has its own, slightly higher resistance.
- Treats the circuit as resistive, which is close for lighting, heating and most branch circuits. On a large AC feeder, and above all one in steel conduit feeding an inductive load, the conductor's reactance adds to the drop and the power factor matters; Table 9 of the same chapter carries the AC figures and is not reproduced here.
- Three phase assumes a balanced load and gives the drop between lines. A single-phase load taken from one line to neutral of a three-phase supply is a single-phase circuit: choose single phase and the line-to-neutral voltage.
- Aluminum conductors need terminations and devices listed for them; the code does not let dissimilar metals be joined except in a device listed for the purpose. Nothing here checks a termination, a lug or a splice.
- The 3% and 5% figures are suggestions in the code's informational notes rather than requirements, though a local amendment, an equipment maker's instructions or a specification can make a tighter figure binding.
Control is what decides whether anyone likes the result
The best thing about this system is one thermostat per room, and it is worth selling properly. There is no balancing, no dampers, no trunk pressure to argue about and no compromise between a bedroom and a hallway: each room holds its own setpoint and the unused ones cost nothing. A ducted system spends real money trying to approximate that, and rarely gets as close.
Where the thermostat lives decides whether any of it works. An integral thermostat on the heater's end cap sits directly in the unit's own rising air, so it reaches setpoint while the far side of the room is still cold, switches off, and leaves the occupant turning the dial up until the near end of the room is uncomfortable. A wall thermostat mounted on an interior wall, out of the heater's plume, away from a lamp and away from the sun off the window, reads what the room is actually doing. On anything larger than a small bathroom, fit the wall stat.
Line voltage is the other half of the specification. These thermostats switch the full heating current themselves, so they carry a resistive rating in amps or watts that has to exceed everything connected to it — a stat rated for one heater and asked to run three is a failure with a scorch mark. Electronic line-voltage stats hold a much tighter deadband than the old bimetal ones, which swing wide enough that the room noticeably rises and falls — and that swing is most of what people mean when they say electric heat feels different. A low-voltage or smart thermostat needs a relay rated for the load between it and the heaters, sited somewhere accessible at first fix, because retrofitting an enclosure for one into a finished basement means opening a ceiling.
Finally, be plain about what this equipment does not do. It does not filter, it does not ventilate, it does not cool, and it does not dehumidify. A basement with a damp problem gets a drier basement from drainage and air sealing, not from a heater, and an owner told otherwise in August will be back in July.
The question the owner asks in February
Every watt you install is a watt somebody pays for at the full electricity tariff, and this site publishes no tariffs because local ones vary too much for any figure to be honest everywhere. The arithmetic the owner can do for themselves is short: watts times hours of operation, divided by a thousand, gives kilowatt-hours, and their own bill supplies the rest. Do it with them once, at the sizing stage, with the real wattage on the table.
The efficiency claim needs care. Essentially all the electrical energy delivered to the element ends up as heat in the room, which is true and is genuinely 100 percent at the appliance. A heat pump moves several times its electrical input as heat, so per unit of heat delivered it costs a fraction as much to run. Baseboard wins on capital cost, on installation disruption and on true per-room zoning; it loses on running cost, and it loses by a wide margin in a cold climate with expensive electricity.
That comparison should decide the specification rather than surface afterwards. A guest room used six weekends a year, a workshop, a room too small for the smallest available heat pump head, or backup heat for a room that already has some — those are good baseboard rooms, and the running cost is close to irrelevant because the running hours are low. A basement that will be somebody's living room every winter evening is the case where the extra work of a heat pump usually repays itself, and saying so is part of doing the job properly.
What the electrician needs before booking the visit
All of the above collapses onto one sheet of paper, and that sheet is what turns a two-visit job into a one-visit job. An electrician arriving without heater lengths cannot chalk the wall, and cannot chalk the wall means cannot rough in — so the visit becomes a survey.
Have it ready before the call. Nothing on the list needs an electrician to produce it: every item is a tape measure, a nameplate, or a decision the owner has already made and not yet written down.
- Floor area and ceiling height for each heated room, with the finished wall build named rather than described.
- Total watts per room and the nameplate voltage of the units being bought.
- Heater lengths, the number of units per room, and their chalked positions on the wall.
- Thermostat type and location for each room, and whether it is single-pole or double-pole.
- The measured conductor route from the panel to the furthest heater, with the climbs and drops included.
- A photograph of the panel directory and the main breaker rating, taken with the cover on.
- Finished floor level for each room, since the heater's clearance is measured from it and not from the subfloor.
Six numbers, fixed in this order
Each of these is wrong if the one above it moves, which is why the heater catalogue is the last thing anyone should open. Most of them are settled with a tape measure and a pencil.
- Floor area and ceiling height of each heated room — Room by room, in its finished dimensions; the floor-area rule of thumb assumes roughly eight foot ceilings and stops being useful above that.
- The wall build that will be behind the heater run — Continuous foam against the concrete, the stud bay, and the gypsum board over it — all three come off the wattage the room ends up needing.
- Watts per room, then the enclosure length that delivers them — Divide by the density printed on the model actually being priced, not by a generic 250 W/ft, and round up to a stock length.
- Clear wall available, measured after the joinery is agreed — Stair carriage, chase, window well, door swing and the sofa; the run that survives all of them is what the heater has to fit into.
- Circuit current at 125 percent, and the two-pole spaces to land it — Fixed space heating is a continuous load, so the design current is the connected current times 1.25 before a breaker is chosen.
- Conductor route length from the panel to the furthest heater — Walked, not scaled. Output falls with the square of the voltage the element actually sees, so drop costs heat every hour of the winter.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.
