Plumbing & HVAC

Heat Pump Sizing Calculator

Size a heat pump to a known heat loss, and find the balance point where supplementary heat starts to be needed.

  • Answers as you type
  • Every formula cited
  • Calculated in your browser
SettingsSettings for this calculationUS
Market
Imperial · sales tax
Whole-house heat loss at the design outdoor temperature.

From a room-by-room heat loss calculation, or as a screening figure from the load calculator. Sizing a heat pump to the old boiler's output is the most common and most expensive error — boilers were routinely oversized by a factor of two.

The external design condition for your location.

A temperature the outdoor air stays above for all but a small share of the year's hours — not the coldest night on record. A US design commonly takes the 99% heating figure; a UK heat pump design under MCS takes the colder 99.6% figure from MIS 3005-D Table 2, which is London's −3.0 °C (26.6 °F), or the 99% one. Sizing to a record low guarantees an oversized, short-cycling machine for the rest of the winter.

The heat pump's nameplate output at the standard rating point.

Nameplate capacity is quoted at a mild outdoor temperature — 7 °C in Europe, 47 °F in North America. Real output at the design condition is materially lower, which is the whole point of this calculation.

How fast output falls as it gets colder, per °C.

Around 2% per °C is typical for an air-source machine, though it varies by refrigerant and compressor. Use the manufacturer's capacity table where you have it — this default is a planning figure, not a specification. This field wants the PER °C figure even when the design temperature above is showing Fahrenheit: a rate read per °F is 5/9 of it, so 2% per °C is 1.11% per °F, and typing 1.11 here would be accepted without complaint and would under-derate the machine by 44%. Multiply a per-°F rate by 1.8 before entering it.

Capacity required at design temperature

8 kW at design

Medium confidence

The derate is a linear planning approximation. Use the manufacturer's published capacity table for the actual machine before committing.

Nameplate capacity at 7 °C
8 kW
Capacity at the design temperature
6.4 kW
Shortfall needing supplementary heat
1.6 kW
Balance point
32 °F
Capacity retained at design
80 %
Then change the inputs to see how far the answer moves.

Show calculation logic

How this was calculated

Formula source(s)

  • Heat pump capacity falls with outdoor temperature; manufacturers publish capacity tables at 47/17/5 °F (8/−8/−15 °C)
  • ACCA Manual S — equipment selection against the calculated load, including balance-point analysis for heat pumps
  • MCS 3005 (UK) requires sizing to the calculated design heat loss rather than to the existing boiler output

Inputs used

Design heat loss
27297.13 BTU/hr
Design outdoor temperature
26.6 °F
Rated capacity at 7 °C
27297.13 BTU/hr
Capacity loss per °C below rating point (%)
2

Intermediate steps

Nameplate capacity at 7 °C
8 kW
Capacity at the design temperature
6.4 kW
Shortfall needing supplementary heat
1.6 kW
Balance point
32 °F
Capacity retained at design
80 %
Final result8 kW at design

Confidence note: The derate is a linear planning approximation. Use the manufacturer's published capacity table for the actual machine before committing.

What this calculation does not cover

  • Capacity derate is linear here; real machines follow a curve that varies with refrigerant, compressor type and defrost behaviour.
  • Defrost cycles reduce delivered output in damp near-freezing conditions and are not modelled.
  • Says nothing about whether the emitters — radiators or underfloor — can deliver the heat at the lower flow temperature a heat pump uses. That is usually the harder problem in a retrofit.

Add the equipment this sizes

This result is a specification — 8 kW at design — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.

Sources checked 2026-09-03 · in the site-wide review of 2026-09-06 · v1.1.1

Regulatory standards & verification citations3
  1. Heat pump capacity falls with outdoor temperature; manufacturers publish capacity tables at 47/17/5 °F (8/−8/−15 °C)
  2. ACCA Manual S — equipment selection against the calculated load, including balance-point analysis for heat pumps
  3. MCS 3005 (UK) requires sizing to the calculated design heat loss rather than to the existing boiler output

Which documents these citations point at

Standards referenced: ACCA Manual S (Air Conditioning Contractors of America, United States).

Cite this page

Your workspace

Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.

Now that you have the number

These guides cover the work this quantity is for — the first ones run this calculator inside the section that raises the question.

Still deciding? Heat Pump vs Air Conditioner · Heat Pump vs Furnace — the factors that actually differ, with no invented prices.

How to calculate heat pump sizing in 5 steps

  1. Design heat lossWhole-house heat loss at the design outdoor temperature.
  2. Design outdoor temperatureThe external design condition for your location.
  3. Rated capacity at 7 °CThe heat pump's nameplate output at the standard rating point.
  4. Capacity loss per °C below rating point (%)How fast output falls as it gets colder, per °C.
  5. Capacity required at design temperatureThe tool computes the capacity required at design temperature from those figures and shows the formula, its sources, and a confidence rating alongside it.

Capacity required at design temperature by design heat loss

Page defaults, not your figures above.

Design heat lossCapacity required at design temperature (kW at design)
20,000 BTU/hr5.86
30,000 BTU/hr8.79
40,000 BTU/hr11.7
50,000 BTU/hr14.7

Frequently asked questions

Why can I not size a heat pump like a boiler?
Because a boiler's output does not change with the weather and a heat pump's does. A 24 kW boiler delivers 24 kW at −10 °C; an 8 kW heat pump delivers perhaps 5.5 kW there. Sizing from the old boiler also inherits its oversizing — boilers were routinely fitted at two or three times the actual heat loss, and copying that produces a heat pump that costs far more than it needs to and cycles badly.
What is the balance point?
The outdoor temperature at which the heat pump's falling capacity exactly meets the building's rising demand. Above it the heat pump covers everything; below it something else has to make up the difference. A balance point near the design temperature means very little supplementary running; one well above it means the immersion or backup heater carries a large share of the season.
Is supplementary heat a failure?
No, it is a design choice. Sizing for the coldest hour of the year leaves a machine badly oversized for the other 99%, cycling and running inefficiently. Accepting a few dozen hours of backup is usually cheaper both to install and to run. What matters is knowing how many hours, which is what the balance point tells you.
Will my existing radiators work?
Often not without change, and this calculator does not answer it. A heat pump runs at 35-50 °C flow against a boiler's 70-80 °C, and a radiator's output falls sharply at lower flow temperature — frequently to half. Emitter sizing is usually the binding constraint in a retrofit, and it is a room-by-room question.
Preliminary estimate, not certified engineering. This tool produces an indicative quantity calculation for planning purposes only — it is not a certified structural analysis, a guaranteed material takeoff, or a substitute for building department approval. Always verify measurements on-site and have a licensed contractor or structural engineer review any load-bearing, code-sensitive, or safety-critical work before purchasing materials or starting construction. Spotted an arithmetic or standards error? Report it to contact@craftquantities.com with your inputs — a confirmed fix gets a permanent check of its own, so the same mistake cannot come back.