Calculators

Electrical

Wire sizing, circuit load, breaker, and outlet-count calculators.

  • 40Calculators
  • 3Families
  • 10Method papers cited

Electrical calculators are only as useful as their scope is honest. Conductor sizing, voltage drop and load calculation are arithmetic with well-defined inputs, and they are done here to the standard's own method. What no calculator can do is inspect an installation, judge a termination, or know what else is already on the circuit — and those are the parts that decide whether work is safe.

Every page states which code or standard its method comes from and when that was last checked, because ampacity tables, correction factors and derating rules differ between jurisdictions and change between editions. Where a figure depends on a table, the table is named. Where a rule varies by market, the page says so instead of quietly picking one.

AWG to mm² Wire Size Calculator

Convert American Wire Gauge to a metric conductor cross-section and back, with the nearest standard size in the other system.

Metric

Breaker Size Calculator

Find the smallest standard breaker rating for a load in watts or amps, with the continuous-load rule applied and the conductor ampacity it then demands.

Conduit Fill Calculator

Find the maximum number of THHN conductors that fit in a conduit, per the NEC's 40% fill rule.

Imperial / Metric

Extension Cord Gauge Calculator

Find the thinnest extension cord gauge rated for your tool's amp draw that also keeps voltage drop under 3% over the cord length.

Imperial / Metric

kVA to kW Calculator

Convert apparent power in kVA into real power in kW at the power factor you enter: 0.8 for a three-phase generator's badge, 1 for a single-phase one's.

kW to kVA Calculator

Convert real power in kW into the apparent power in kVA a generator, transformer or supply has to carry, at the load's power factor.

Ohm's Law Calculator

Enter voltage and resistance to get the current and power that follow from Ohm's Law.

Outlet Spacing Calculator

The minimum number of wall outlets one continuous wall space needs under the NEC 12-foot (3.7 m) rule. For a room, add up each wall space's count.

Imperial / Metric

Wire Gauge to Amperage Calculator

Look up the NEC allowable ampacity of a copper conductor from its AWG size, at the 60, 75 and 90 °C (140, 167 and 194 °F) insulation ratings.