SettingsSettings for this calculationUS
Whether the appliance's rating plate gives you power or current.
If the plate gives amps, use amps — it is the figure the manufacturer measured and it already accounts for power factor and efficiency. Converting from watts assumes a power factor of one, which is right for a resistive load such as a heater or a hob and optimistic for anything with a motor or a switching supply in it.
The nameplate power rating of the equipment on this circuit.
Where several pieces of equipment share the circuit, add their ratings. Use the nameplate figure rather than a measured one — a breaker is sized for what the equipment may draw, not for what it happened to draw when you looked.
The nominal voltage of the circuit the equipment is connected to.
For a three-phase circuit this is the line-to-line voltage — 208 or 480 in North America, 400 in Europe. Using a line-to-neutral figure with the three-phase setting is the commonest error here and it overstates the current by about three quarters.
Whether the circuit is single or three phase.
A three-phase load of the same power draws about 58% of the single-phase current, because the power is shared across three conductors and the line-to-line voltage does the work of the square root of three. This assumes the load is balanced across the phases.
Whether the load runs for three hours or more at maximum current.
Three hours is the NEC's own threshold. Electric heating, EV charging, commercial lighting and most fixed process equipment are continuous; a kettle, a hob and a power tool are not. Where you are unsure, treating a load as continuous is the conservative answer — it raises the calculated minimum by a quarter.
Minimum breaker size
25 A
The arithmetic is the code's and it is exact. What makes this a screening figure rather than a design is everything it cannot see: the conductor's insulation rating, the ambient temperature, how many conductors share the raceway, the length of the run, and what the terminals at each end are listed for. Any of those can move the required conductor — and therefore the acceptable device — by a size or more.
- Load current
- 20 A
- Required minimum at 125% (continuous)
- 25 A
- Minimum conductor ampacity after corrections
- 25 A
- Headroom to the next trip point
- 0 %
- Load as a share of the breaker
- 80 %
They open the calculator with your figures already in it
Breaker Size Calculator: 25 A — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- NEC 240.6(A): standard ampere ratings for inverse-time circuit breakers and fuses — 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A
- NEC 210.20(A) and 215.3: the overcurrent device rating shall be not less than 100% of the noncontinuous load plus 125% of the continuous load
- NEC 210.19(A)(1): branch-circuit conductors shall have an ampacity not less than the same figure, before any temperature or conduit-fill correction
- NEC 240.4: conductors shall be protected at their ampacity — the device rating follows the conductor, not the load it happens to serve
- NEC Article 430 governs motor branch circuits: short-circuit and ground-fault protection is sized from Table 430.52 and may substantially exceed the motor's full-load current, so this page does not apply to motors
Inputs used
- I know the load as
- Watts (or VA) from the nameplate
- Load (W or VA)
- 4800
- Load current (A)
- 20
- Circuit voltage
- 240 V (North American large appliance)
- Phase
- Single phase
- Continuous load
- Yes — runs three hours or more at a time
Intermediate steps
- Load current
- 20 A
- Required minimum at 125% (continuous)
- 25 A
- Minimum conductor ampacity after corrections
- 25 A
- Headroom to the next trip point
- 0 %
- Load as a share of the breaker
- 80 %
Confidence note: The arithmetic is the code's and it is exact. What makes this a screening figure rather than a design is everything it cannot see: the conductor's insulation rating, the ambient temperature, how many conductors share the raceway, the length of the run, and what the terminals at each end are listed for. Any of those can move the required conductor — and therefore the acceptable device — by a size or more.
What this calculation does not cover
- A breaker protects the conductor, not the appliance. The rating above is the minimum the LOAD demands; it is only the right breaker if the conductor behind it is rated to carry it after every applicable correction. Fitting a larger breaker to stop a circuit tripping, without changing the wire, removes the protection the wire depends on and is the most common serious mistake made in a domestic panel.
- Motors are not sized this way. NEC Article 430 sizes motor branch-circuit short-circuit and ground-fault protection from Table 430.52, and an inverse-time breaker on a motor is routinely rated well above the motor's full-load current so that starting inrush does not trip it — while the overload protection is a separate device sized much closer to the running current. Putting a motor's nameplate current into this page gives a breaker that will trip on starting.
- Converting watts to amps assumes a power factor of one. That is correct for resistive loads — heaters, hobs, water heaters, incandescent lighting — and optimistic for motors, welders, electronic supplies and anything with a substantial inductive component, where the real current is higher than the power rating alone suggests. Where the plate gives amps, use amps.
- Conductor ampacity has not been calculated here, only stated as a minimum. The actual conductor is chosen from the ampacity tables at the insulation's temperature rating, then corrected for ambient temperature and for the number of current-carrying conductors bundled together, and finally limited by the temperature rating of the terminations at both ends — which on most equipment is 75 °C regardless of what the cable itself can take.
- Voltage drop is a separate constraint and often the binding one. On a long run the conductor that satisfies ampacity may still deliver too little voltage at the load, and the fix is a larger conductor — which does not change the breaker, because the breaker still has to match the load it protects.
- This is NEC arithmetic. Circuit protection outside North America follows BS 7671, the relevant IEC standards or the local equivalent, which use different device characteristics, different standard ratings and a different treatment of continuous duty. The voltages offered here include European and Australian values because the load arithmetic is universal; the 125% rule and the standard rating list are not.
Add the equipment this sizes
This result is a specification — 25 A — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
Part of a bigger job
This trade is one line of a job takeoff. Run the whole job and every other trade comes back with it, off the same measurements.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-11 · v1.0.0
Regulatory standards & verification citations5
- NEC 240.6(A): standard ampere ratings for inverse-time circuit breakers and fuses — 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A
- NEC 210.20(A) and 215.3: the overcurrent device rating shall be not less than 100% of the noncontinuous load plus 125% of the continuous load
- NEC 210.19(A)(1): branch-circuit conductors shall have an ampacity not less than the same figure, before any temperature or conduit-fill correction
- NEC 240.4: conductors shall be protected at their ampacity — the device rating follows the conductor, not the load it happens to serve
- NEC Article 430 governs motor branch circuits: short-circuit and ground-fault protection is sized from Table 430.52 and may substantially exceed the motor's full-load current, so this page does not apply to motors
Which documents these citations point at
- National Electrical Code (NFPA 70) — 240.6(A), 210.20(A), 210.19(A)(1), 240.4, Article 430 (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.
A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.
Cite this page
Your workspace
Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.
Protection this work requires
- Stop and check first. Textured ceiling coatings, board behind panels, floor tiles and bitumen adhesive in older buildings — built before asbestos was banned or phased out where you are — can contain asbestos, and drilling or sanding them releases fibres. Do not disturb it — have it sampled first. This is not a job for better PPE.
Tools and safety for this job
To first-fix electrical. Generic types, no brands, no prices.
- Assume every cable is live until proved dead at the point you will touch, with a two-pole tester you have just proved on a known source.
First-fix electrical: This site does not publish a tool list for electrical installation work. In every market it serves, fixed wiring is either reserved to a registered electrician or notifiable to a building authority, and the failure mode is a fire or an electrocution months later rather than a visibly bad job on the day. The calculator gives you the quantities to discuss and to buy against. The installation is a job for a qualified electrician, and the certificate they issue is the point of them.