Cross-market term

Consumer unit / breaker panel

The enclosure where a building's incoming supply is divided into final circuits, each with its own overcurrent protection, and where the earthing and any residual-current protection are arranged.
  • 4Markets
  • NoSame thing everywhere
  • 6Calculators

What it is called, by market

One concept, four markets. Where a name means something else locally, the card says so rather than leaving you to find out on site.

  • United Kingdom

    Close, not identical

    consumer unit

    also CU, fuse board, distribution board

    "Consumer unit" is the domestic enclosure specifically; "distribution board" is the broader term used for commercial and industrial installations.

  • United Statesyours

    Close, not identical

    panelboard

    also breaker panel, load center, service panel

    "Load center" is the residential product and "panelboard" the commercial one, so the two American words split the same way the British pair does.

  • Canada

    Close, not identical

    panelboard

    also breaker panel, load centre

    As the United States for the product names, though the governing code and the earthing arrangements are Canadian and differ in detail.

  • Australia

    Close, not identical

    switchboard

    also distribution board, DB

    "Switchboard" covers the enclosure and its devices, and is used for domestic and commercial alike rather than splitting the way the British and American terms do.

The governing standard, by market

  • United Kingdom

    BS 7671

    Requirements for electrical installations — the IET Wiring Regulations.

  • United States

    NFPA 70 (NEC)

    National Electrical Code — panelboard and overcurrent requirements.

  • Australia

    AS/NZS 3000

    Electrical installations — the Wiring Rules.

Calculators for this

Each works in either measurement system, and the terminology on the page follows whichever market you have selected.

Frequently asked questions

Is an RCD the same as a GFCI?
Close in purpose and different in threshold and in where it sits. Both detect an imbalance between the current flowing out and the current returning — the signature of current leaking to earth, possibly through a person — and disconnect. British and Australian practice calls the device an RCD, commonly fits it at the consumer unit to protect groups of circuits or, increasingly, per circuit as an RCBO combining it with overcurrent protection. American practice calls it a GFCI, most familiarly built into a socket outlet in a wet location or into a breaker, and the trip threshold for personal protection differs from the RCD's typical figure. So the words map, the function maps, and the ratings and the installation conventions do not — which is why a device cannot simply be substituted across a specification.
What is an AFCI, and does Britain have one?
An arc-fault circuit interrupter detects the electrical signature of an arcing fault — a loose connection, a damaged cable, a pierced conductor — which can generate enough heat to start a fire while drawing too little current to trip an overcurrent device and causing no earth leakage for a residual-current device to see. It is a distinct protection from both, required in American practice for many circuit types. The British and European equivalent is the arc fault detection device, recognised in the wiring regulations and recommended rather than universally mandated. So the concept exists in both, under different names, with different scope — and a specification calling for AFCI protection is calling for a device that is not the default in a British consumer unit.
Why do the earthing arrangements differ so much?
Because the supply systems differ, and the protective arrangement follows from how the supply is earthed rather than from a preference. British practice classifies installations by earthing system — whether the earth comes with the supply cable, is combined with the neutral, or is provided by an electrode at the property — and the choice of protective device, the bonding of services and the acceptable earth loop impedance all follow from that classification. American and Canadian practice arranges the service grounding and bonding differently again, and Australian practice differently once more. The practical consequence is that the earthing section of a foreign specification cannot be read across even when every device name translates, because it is describing a different supply.