SettingsSettings for this calculationUS
The rating of the fuse or circuit breaker protecting the circuit ahead of the equipment grounding conductor.
The device ahead of the conductor, not the load it serves and not the conductor's own ampacity. Grounding conductors are sized from the protective device because their job is to carry fault current long enough to open it. One consequence gets missed often: where phase conductors are upsized for voltage drop, the grounding conductor has to be upsized in proportion — the fault path has to keep up with the run it protects.
An illustrative scaling constant used only to produce a rough proportional estimate — not a code value.
This is a proportionality knob for a rough figure, and the result it produces is NOT a code-compliant size. Grounding conductors are sized from a published table against the protective device rating, not from a formula, and that table is not linear. Use this to see roughly how the size moves with the device, then take the actual size from the table that applies where the work is.
Approximate grounding conductor sizing factor
2.3 (illustrative scaling units)
This proportional calculation is illustrative ONLY — NEC Table 250.122 defines equipment grounding conductor size using specific breakpoints (e.g. 60A→10AWG copper, 100A→8AWG copper, 200A→6AWG copper, 400A→3AWG copper), NOT a continuous formula. Always look up the required size directly from NEC Table 250.122 (or your local code) for the actual OCPD rating — never use a proportional/interpolated calculation for the real conductor size.
They open the calculator with your figures already in it
Equipment Grounding Conductor Sizing Reference Calculator: 2.25 (illustrative scaling units) — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- NEC Table 250.122 sets equipment grounding conductor size based on the rating of the automatic overcurrent device ahead of the circuit — sizes step up at defined breakpoints rather than scaling continuously. This calculator applies a simplified proportional approximation (OCPD rating × a scaling factor) as a rough estimate only; the actual required size MUST be taken directly from NEC Table 250.122, not calculated proportionally.
Inputs used
- Overcurrent Protective Device Rating (A)
- 100
- Sizing Factor (Illustrative Scaling Constant)
- 0.02
Confidence note: This proportional calculation is illustrative ONLY — NEC Table 250.122 defines equipment grounding conductor size using specific breakpoints (e.g. 60A→10AWG copper, 100A→8AWG copper, 200A→6AWG copper, 400A→3AWG copper), NOT a continuous formula. Always look up the required size directly from NEC Table 250.122 (or your local code) for the actual OCPD rating — never use a proportional/interpolated calculation for the real conductor size.
What this calculation does not cover
- One conductor of several that get confused with it. Table 250.122 sizes the equipment grounding conductor — the one running with the circuit back to the panel. The grounding electrode conductor out to the rod or the concrete-encased electrode comes from 250.66 off the service-entrance conductors, the main and system bonding jumpers from 250.28(D), and a supply-side bonding jumper from 250.102(C). Every one of those keys off conductor size rather than device rating, so entering a breaker rating for any of them returns an answer from the wrong table entirely.
- The overcurrent device rating is the index in the NEC and almost nowhere else. BS 7671 and the IEC-derived codes size the protective conductor from the LINE conductor — a table keyed to the phase cross-section, or the adiabatic equation run against the prospective fault current and the device's let-through energy — so the same circuit is sized on a different quantity in most of the world. A reader outside the United States will not find the breaker rating in the method at all.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-06 · in the site-wide review of 2026-09-06 · v1.0.1
Regulatory standards & verification citations1
- NEC Table 250.122 sets equipment grounding conductor size based on the rating of the automatic overcurrent device ahead of the circuit — sizes step up at defined breakpoints rather than scaling continuously. This calculator applies a simplified proportional approximation (OCPD rating × a scaling factor) as a rough estimate only; the actual required size MUST be taken directly from NEC Table 250.122, not calculated proportionally.
Which documents these citations point at
- National Electrical Code (NFPA 70) — Table 250.122 (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.
A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.
Cite this page
Your workspace
Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.