SettingsSettings for this calculationUS
Which of the two NEC methods gives the headline figure — both are computed and both appear in the breakdown.
The standard calculation applies a separate demand factor to each class of load. The optional calculation lumps most of them together and takes the first 10 kVA at 100% and everything above it at 40%. On a typical house the optional method gives the smaller answer, which is why it exists; some inspectors expect one, some the other, and a service sized by the smaller of the two is only defensible if the jurisdiction accepts that method.
The edition your jurisdiction has adopted — adoption lags publication, often by years.
Of the figures this page uses, the one that moves between editions is electric-vehicle supply equipment: 220.57, which sets the EVSE load at the nameplate rating or 7,200 VA whichever is larger, arrived in the 2020 edition. Lighting, range and dryer demands are unchanged across all three. The 2023 edition renumbered much of Article 220 without changing those numbers.
The habitable floor area, measured to the outside of the exterior walls.
NEC 220.12 measures from the outside dimensions of the dwelling and excludes open porches, garages and unfinished or unused spaces unless they are adaptable for future use. An unfinished basement that could be finished counts; an attic with no floor does not.
The number of 20 A small-appliance circuits serving the kitchen, pantry and dining areas.
NEC 210.11(C)(1) requires at least two, which is why the field will not go below two. Larger kitchens and separate island or pantry circuits push the number higher; each one adds 1,500 VA to the calculation whether or not it is heavily loaded.
Whether the dwelling has the dedicated laundry receptacle circuit.
NEC 210.11(C)(2) requires one in a dwelling unit, so the usual answer is yes and it adds 1,500 VA. The exception is a unit with no laundry provision at all — some apartments in buildings with a shared laundry room.
The nameplate kilowatt rating of the electric range. Enter 0 for a gas range.
A single range of 12 kW or less has a demand of 8 kW under Table 220.55 Column C — the table already assumes you will never run every element at once. Above 12 kW the 8 kW figure rises 5% for each additional kilowatt. Separate wall ovens and counter-mounted cooktops on one circuit are treated as a single range of their combined rating.
The dryer's nameplate rating in volt-amperes. Enter 0 for a gas dryer or no dryer.
NEC 220.54 sets a floor of 5,000 VA, so anything you enter below that is raised to it. A typical electric dryer is 5,000 to 5,600 VA. A heat-pump dryer draws far less and still carries the 5,000 VA calculated load, because the rule is a minimum rather than a measurement.
Nameplate total for the water heater, dishwasher, disposal, microwave and similar fixed appliances.
Everything fastened in place except the range, the dryer, space heating and air conditioning, which are counted separately. A 4,500 W water heater, a 1,200 W dishwasher and a 900 W disposal come to 6,600 VA. Do not include portable appliances — they are already covered by the general lighting and receptacle load taken from the floor area.
The count of those appliances — four or more earns a demand factor, three or fewer do not.
NEC 220.53 allows 75% of the total nameplate where four or more fastened-in-place appliances are served, on the reasoning that they do not all run together. With three or fewer the full nameplate total is used, so the count genuinely changes the answer.
The larger of the electric heating load and the air-conditioning load — not both added together.
NEC 220.60 treats heating and cooling as noncoincident, so only the larger is included. For a heat pump, add the compressor to the supplemental resistance heat if they can run together. Enter 0 where heating is gas or oil and there is no air conditioning.
The charger's nameplate rating — 7,680 VA for a 32 A unit at 240 V. Enter 0 if none is planned.
Multiply the continuous amp rating by the voltage: a 32 A charger on 240 V is 7,680 VA, a 48 A one is 11,520 VA. Under the 2020 and 2023 editions the calculated load is that figure or 7,200 VA, whichever is larger, so a small charger does not reduce the calculation below 7,200. Where an energy management system limits the charger, a different and lower figure may be permitted — that is outside this page.
Calculated service load
155 A
A screening calculation, not a load letter. Every figure here comes from the NEC's own demand tables, but a service upgrade is designed by a licensed electrician, permitted by the authority having jurisdiction and coordinated with the utility, whose own sizing rules and available capacity govern what can actually be installed.
- Recommended service rating
- 175 A
- Standard calculation (Part III)
- 154.69 A
- Optional calculation (220.82)
- 116.67 A
- Headline load in volt-amperes
- 37,125 VA
- General lighting at 3 VA per sq ft
- 6,000 VA
- Lighting group after Table 220.42 demand
- 5,625 VA
- Range demand, Table 220.55 Column C
- 8,000 VA
- Dryer, 5,000 VA minimum
- 5,000 VA
- Fixed appliances at 75%
- 4,500 VA
- EV supply equipment at 125%
- 9,000 VA
They open the calculator with your figures already in it
Electrical Panel Load Calculator (NEC Service Sizing): 155 A — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- NEC 220.12 and Table 220.12: dwelling general lighting and general-use receptacle load at 3 VA per square foot of floor area
- NEC 220.52: 1,500 VA for each 2-wire small-appliance branch circuit and 1,500 VA for the laundry branch circuit
- NEC Table 220.42: demand factors for lighting and receptacle loads — first 3,000 VA at 100%, 3,001 to 120,000 VA at 35%, remainder at 25%
- NEC Table 220.55, Column C, Note 1: one household range of 12 kW or less has a demand of 8 kW, increased 5% per additional kW or major fraction above 12 kW
- NEC 220.54: household clothes dryer at 5,000 VA or the nameplate rating, whichever is larger
- NEC 220.53: four or more fastened-in-place appliances (other than ranges, dryers, space heating and air conditioning) may be taken at a 75% demand factor
- NEC 220.60: noncoincident loads — where heating and cooling cannot operate together, only the larger is included
- NEC 220.82: optional calculation for a dwelling on a 100 A or larger 120/240 V service — first 10 kVA of general load at 100%, remainder at 40%, plus the largest of the 220.82(C) heating and cooling figures
- NEC 220.57 (2020 and 2023 editions): electric-vehicle supply equipment at the nameplate rating or 7,200 VA, whichever is larger. Under the 2017 edition the nameplate rating applies, treated as a continuous load under 625.41
- NEC 240.6(A) standard overcurrent device ratings: 100, 125, 150, 175, 200, 225, 250, 300, 350, 400 A
Inputs used
- Headline method
- Standard calculation (Article 220, Part III)
- NEC edition
- NEC 2023
- Dwelling floor area
- 2000 sq ft
- Small-appliance branch circuits
- 2
- Laundry branch circuit
- Yes — dedicated laundry circuit
- Range or cooktop nameplate (kW)
- 12
- Clothes dryer nameplate (VA)
- 5000
- Fastened-in-place appliances, total nameplate (VA)
- 6000
- How many fastened-in-place appliances
- 4
- Heating or cooling, whichever is larger (VA)
- 5000
- EV supply equipment nameplate (VA)
- 7200
Intermediate steps
- Recommended service rating
- 175 A
- Standard calculation (Part III)
- 154.69 A
- Optional calculation (220.82)
- 116.67 A
- Headline load in volt-amperes
- 37,125 VA
- General lighting at 3 VA per sq ft
- 6,000 VA
- Lighting group after Table 220.42 demand
- 5,625 VA
- Range demand, Table 220.55 Column C
- 8,000 VA
- Dryer, 5,000 VA minimum
- 5,000 VA
- Fixed appliances at 75%
- 4,500 VA
- EV supply equipment at 125%
- 9,000 VA
Confidence note: A screening calculation, not a load letter. Every figure here comes from the NEC's own demand tables, but a service upgrade is designed by a licensed electrician, permitted by the authority having jurisdiction and coordinated with the utility, whose own sizing rules and available capacity govern what can actually be installed.
What this calculation does not cover
- This is a screening calculation and not a submitted load letter. A service change needs a licensed electrician, a permit from the authority having jurisdiction, and the utility's agreement — the utility's transformer, service drop and metering all have their own limits, and none of them appears in Article 220.
- The 125% continuous-load multiplier on the EV charger follows 230.42(A) for service conductors. Some authorities read 220.57's 7,200 VA as already being the calculated load and do not apply 125% on top of it, which changes the answer by a quarter of the charger's load — worth establishing locally before sizing anything.
- 220.82(C) is only partly modelled. The optional calculation here takes the heating or cooling figure you entered at 100%, which is correct for air conditioning and for a heat pump with its supplemental heat. The reduced percentages the code allows — 65% for central systems with supplementary heat, 65% for fewer than four separately controlled electric space heating units, 40% for four or more — need a description of the heating system this page does not ask for, and they would lower the result.
- The Canadian Electrical Code is not this calculation. CEC Section 8 sizes a single-dwelling service from a minimum figure per unit of floor area with its own demand factors, and it produces materially different answers from NEC Article 220. Nothing on this page has been checked against the CEC, and it must not be used for Canadian permit work.
- Conductor sizing is a separate step. NEC 310.12 permits the ungrounded service conductors of a 120/240 V single-phase dwelling service to be sized at 83% of the service rating, and conductor ampacity is then subject to temperature and conduit-fill corrections. The recommended rating above is the overcurrent device, not the wire.
- Load management and demand-controlled equipment are outside the model. Where an energy management system limits an EV charger or a heat pump, the code permits a lower calculated load, and a house that would otherwise need a service upgrade may not. That determination belongs with the system's listing and the designer.
Add the equipment this sizes
This result is a specification — 155 A — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
Part of a bigger job
This trade is one line of a job takeoff. Run the whole job and every other trade comes back with it, off the same measurements.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-11 · v1.0.0
Regulatory standards & verification citations10
- NEC 220.12 and Table 220.12: dwelling general lighting and general-use receptacle load at 3 VA per square foot of floor area
- NEC 220.52: 1,500 VA for each 2-wire small-appliance branch circuit and 1,500 VA for the laundry branch circuit
- NEC Table 220.42: demand factors for lighting and receptacle loads — first 3,000 VA at 100%, 3,001 to 120,000 VA at 35%, remainder at 25%
- NEC Table 220.55, Column C, Note 1: one household range of 12 kW or less has a demand of 8 kW, increased 5% per additional kW or major fraction above 12 kW
- NEC 220.54: household clothes dryer at 5,000 VA or the nameplate rating, whichever is larger
- NEC 220.53: four or more fastened-in-place appliances (other than ranges, dryers, space heating and air conditioning) may be taken at a 75% demand factor
- NEC 220.60: noncoincident loads — where heating and cooling cannot operate together, only the larger is included
- NEC 220.82: optional calculation for a dwelling on a 100 A or larger 120/240 V service — first 10 kVA of general load at 100%, remainder at 40%, plus the largest of the 220.82(C) heating and cooling figures
- NEC 220.57 (2020 and 2023 editions): electric-vehicle supply equipment at the nameplate rating or 7,200 VA, whichever is larger. Under the 2017 edition the nameplate rating applies, treated as a continuous load under 625.41
- NEC 240.6(A) standard overcurrent device ratings: 100, 125, 150, 175, 200, 225, 250, 300, 350, 400 A
Which documents these citations point at
- National Electrical Code (NFPA 70) — 220.12, 220.52, Table 220.42, Table 220.55, 220.54, 220.53, 220.60, 220.82, 220.57, 240.6(A) (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.
A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.
Cite this page
Your workspace
Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.