  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "electrical-panel-load-calculator",
  "category": "electrical",
  "title": "Electrical Panel Load Calculator (NEC Service Sizing)",
  "description": "Size a dwelling's electrical service by NEC Article 220's standard and optional methods, with the standard service rating that covers the one you choose.",
  "url": "https://craftquantities.com/calculators/electrical/electrical-panel-load-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/electrical-panel-load-calculator.json",
  "inputCount": 11,
  "testCaseCount": 5,
  "sourceCount": 10,
  "lastVerified": "2026-09-11",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/electrical/electrical-panel-load-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Electrical Panel Load Calculator (NEC Service Sizing)",
    "version": "1.0.0",
    "sourcesChecked": "2026-09-11",
    "url": "https://craftquantities.com/calculators/electrical/electrical-panel-load-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Electrical Panel Load Calculator (NEC Service Sizing). Version 1.0.0. Sources checked 2026-09-11. https://craftquantities.com/calculators/electrical/electrical-panel-load-calculator/",
      "apa": "Craft Quantities. (2026). Electrical Panel Load Calculator (NEC Service Sizing) (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/electrical/electrical-panel-load-calculator/",
      "harvard": "Craft Quantities (2026) Electrical Panel Load Calculator (NEC Service Sizing) (Version 1.0.0). Available at: https://craftquantities.com/calculators/electrical/electrical-panel-load-calculator/",
      "bibtex": "@misc{craftquantities-calculators-electrical-electrical-panel-load-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Electrical Panel Load Calculator (NEC Service Sizing)},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/electrical/electrical-panel-load-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "calcMethod",
      "label": "Headline method",
      "type": "select",
      "defaultValue": "standard",
      "options": [
        {
          "value": "standard",
          "label": "Standard calculation (Article 220, Part III)"
        },
        {
          "value": "optional",
          "label": "Optional calculation for dwellings (220.82)"
        }
      ],
      "help": "Which of the two NEC methods gives the headline figure — both are computed and both appear in the breakdown."
    },
    {
      "id": "codeEdition",
      "label": "NEC edition",
      "type": "select",
      "defaultValue": "2023",
      "options": [
        {
          "value": "2017",
          "label": "NEC 2017"
        },
        {
          "value": "2020",
          "label": "NEC 2020"
        },
        {
          "value": "2023",
          "label": "NEC 2023"
        }
      ],
      "help": "The edition your jurisdiction has adopted — adoption lags publication, often by years."
    },
    {
      "id": "floorArea",
      "label": "Dwelling floor area",
      "type": "number",
      "dimension": "area",
      "defaultValue": 185.80608,
      "min": 20,
      "max": 2000,
      "step": 1,
      "help": "The habitable floor area, measured to the outside of the exterior walls."
    },
    {
      "id": "smallApplianceCircuits",
      "label": "Small-appliance branch circuits",
      "type": "number",
      "defaultValue": 2,
      "min": 2,
      "max": 8,
      "step": 1,
      "help": "The number of 20 A small-appliance circuits serving the kitchen, pantry and dining areas."
    },
    {
      "id": "hasLaundry",
      "label": "Laundry branch circuit",
      "type": "select",
      "defaultValue": "yes",
      "options": [
        {
          "value": "yes",
          "label": "Yes — dedicated laundry circuit"
        },
        {
          "value": "no",
          "label": "No laundry circuit in this dwelling"
        }
      ],
      "help": "Whether the dwelling has the dedicated laundry receptacle circuit."
    },
    {
      "id": "rangeKw",
      "label": "Range or cooktop nameplate (kW)",
      "type": "number",
      "defaultValue": 12,
      "min": 0,
      "max": 27,
      "step": 0.5,
      "help": "The nameplate kilowatt rating of the electric range. Enter 0 for a gas range."
    },
    {
      "id": "dryerVa",
      "label": "Clothes dryer nameplate (VA)",
      "type": "number",
      "defaultValue": 5000,
      "min": 0,
      "max": 12000,
      "step": 100,
      "help": "The dryer's nameplate rating in volt-amperes. Enter 0 for a gas dryer or no dryer."
    },
    {
      "id": "fixedApplianceVa",
      "label": "Fastened-in-place appliances, total nameplate (VA)",
      "type": "number",
      "defaultValue": 6000,
      "min": 0,
      "max": 40000,
      "step": 100,
      "help": "Nameplate total for the water heater, dishwasher, disposal, microwave and similar fixed appliances."
    },
    {
      "id": "fixedApplianceCount",
      "label": "How many fastened-in-place appliances",
      "type": "number",
      "defaultValue": 4,
      "min": 0,
      "max": 20,
      "step": 1,
      "help": "The count of those appliances — four or more earns a demand factor, three or fewer do not."
    },
    {
      "id": "hvacVa",
      "label": "Heating or cooling, whichever is larger (VA)",
      "type": "number",
      "defaultValue": 5000,
      "min": 0,
      "max": 40000,
      "step": 100,
      "help": "The larger of the electric heating load and the air-conditioning load — not both added together."
    },
    {
      "id": "evVa",
      "label": "EV supply equipment nameplate (VA)",
      "type": "number",
      "defaultValue": 7200,
      "min": 0,
      "max": 20000,
      "step": 240,
      "help": "The charger's nameplate rating — 7,680 VA for a 32 A unit at 240 V. Enter 0 if none is planned."
    }
  ],
  "sources": [
    {
      "label": "NEC 220.12 and Table 220.12: dwelling general lighting and general-use receptacle load at 3 VA per square foot of floor area"
    },
    {
      "label": "NEC 220.52: 1,500 VA for each 2-wire small-appliance branch circuit and 1,500 VA for the laundry branch circuit"
    },
    {
      "label": "NEC Table 220.42: demand factors for lighting and receptacle loads — first 3,000 VA at 100%, 3,001 to 120,000 VA at 35%, remainder at 25%"
    },
    {
      "label": "NEC Table 220.55, Column C, Note 1: one household range of 12 kW or less has a demand of 8 kW, increased 5% per additional kW or major fraction above 12 kW"
    },
    {
      "label": "NEC 220.54: household clothes dryer at 5,000 VA or the nameplate rating, whichever is larger"
    },
    {
      "label": "NEC 220.53: four or more fastened-in-place appliances (other than ranges, dryers, space heating and air conditioning) may be taken at a 75% demand factor"
    },
    {
      "label": "NEC 220.60: noncoincident loads — where heating and cooling cannot operate together, only the larger is included"
    },
    {
      "label": "NEC 220.82: optional calculation for a dwelling on a 100 A or larger 120/240 V service — first 10 kVA of general load at 100%, remainder at 40%, plus the largest of the 220.82(C) heating and cooling figures"
    },
    {
      "label": "NEC 220.57 (2020 and 2023 editions): electric-vehicle supply equipment at the nameplate rating or 7,200 VA, whichever is larger. Under the 2017 edition the nameplate rating applies, treated as a continuous load under 625.41"
    },
    {
      "label": "NEC 240.6(A) standard overcurrent device ratings: 100, 125, 150, 175, 200, 225, 250, 300, 350, 400 A"
    }
  ],
  "testCases": [
    {
      "name": "2,000 sq ft house with an EV charger, standard method",
      "inputs": {
        "calcMethod": "standard",
        "codeEdition": "2023",
        "floorArea": 185.80608,
        "smallApplianceCircuits": 2,
        "hasLaundry": "yes",
        "rangeKw": 12,
        "dryerVa": 5000,
        "fixedApplianceVa": 6000,
        "fixedApplianceCount": 4,
        "hvacVa": 5000,
        "evVa": 7200
      },
      "expected": 154.69,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Recommended service rating",
          "value": 175,
          "unit": "A"
        },
        {
          "label": "Standard calculation (Part III)",
          "value": 154.6875,
          "unit": "A"
        },
        {
          "label": "Optional calculation (220.82)",
          "value": 116.66666666666667,
          "unit": "A"
        },
        {
          "label": "Headline load in volt-amperes",
          "value": 37125,
          "unit": "VA"
        },
        {
          "label": "General lighting at 3 VA per sq ft",
          "value": 6000,
          "unit": "VA"
        },
        {
          "label": "Lighting group after Table 220.42 demand",
          "value": 5625,
          "unit": "VA"
        },
        {
          "label": "Range demand, Table 220.55 Column C",
          "value": 8000,
          "unit": "VA"
        },
        {
          "label": "Dryer, 5,000 VA minimum",
          "value": 5000,
          "unit": "VA"
        },
        {
          "label": "Fixed appliances at 75%",
          "value": 4500,
          "unit": "VA"
        },
        {
          "label": "EV supply equipment at 125%",
          "value": 9000,
          "unit": "VA"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "The same house by the optional method lands lower",
      "inputs": {
        "calcMethod": "optional",
        "codeEdition": "2023",
        "floorArea": 185.80608,
        "smallApplianceCircuits": 2,
        "hasLaundry": "yes",
        "rangeKw": 12,
        "dryerVa": 5000,
        "fixedApplianceVa": 6000,
        "fixedApplianceCount": 4,
        "hvacVa": 5000,
        "evVa": 7200
      },
      "expected": 116.67,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Recommended service rating",
          "value": 125,
          "unit": "A"
        },
        {
          "label": "Standard calculation (Part III)",
          "value": 154.6875,
          "unit": "A"
        },
        {
          "label": "Optional calculation (220.82)",
          "value": 116.66666666666667,
          "unit": "A"
        },
        {
          "label": "Headline load in volt-amperes",
          "value": 28000,
          "unit": "VA"
        },
        {
          "label": "General lighting at 3 VA per sq ft",
          "value": 6000,
          "unit": "VA"
        },
        {
          "label": "Lighting group after Table 220.42 demand",
          "value": 5625,
          "unit": "VA"
        },
        {
          "label": "Range demand, Table 220.55 Column C",
          "value": 8000,
          "unit": "VA"
        },
        {
          "label": "Dryer, 5,000 VA minimum",
          "value": 5000,
          "unit": "VA"
        },
        {
          "label": "Fixed appliances at 75%",
          "value": 4500,
          "unit": "VA"
        },
        {
          "label": "EV supply equipment at 125%",
          "value": 9000,
          "unit": "VA"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "Small all-gas dwelling, lighting and receptacles only",
      "inputs": {
        "calcMethod": "standard",
        "codeEdition": "2020",
        "floorArea": 92.90304,
        "smallApplianceCircuits": 2,
        "hasLaundry": "yes",
        "rangeKw": 0,
        "dryerVa": 0,
        "fixedApplianceVa": 0,
        "fixedApplianceCount": 0,
        "hvacVa": 0,
        "evVa": 0
      },
      "expected": 19.06,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Recommended service rating",
          "value": 100,
          "unit": "A"
        },
        {
          "label": "Standard calculation (Part III)",
          "value": 19.0625,
          "unit": "A"
        },
        {
          "label": "Optional calculation (220.82)",
          "value": 31.25,
          "unit": "A"
        },
        {
          "label": "Headline load in volt-amperes",
          "value": 4575,
          "unit": "VA"
        },
        {
          "label": "General lighting at 3 VA per sq ft",
          "value": 3000,
          "unit": "VA"
        },
        {
          "label": "Lighting group after Table 220.42 demand",
          "value": 4575,
          "unit": "VA"
        },
        {
          "label": "Range demand, Table 220.55 Column C",
          "value": 0,
          "unit": "VA"
        },
        {
          "label": "Dryer, 5,000 VA minimum",
          "value": 0,
          "unit": "VA"
        },
        {
          "label": "Fixed appliances at full nameplate",
          "value": 0,
          "unit": "VA"
        },
        {
          "label": "EV supply equipment at 125%",
          "value": 0,
          "unit": "VA"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "A 16 kW range takes the Column C increase of 5% per kW",
      "inputs": {
        "calcMethod": "standard",
        "codeEdition": "2020",
        "floorArea": 92.90304,
        "smallApplianceCircuits": 2,
        "hasLaundry": "yes",
        "rangeKw": 16,
        "dryerVa": 0,
        "fixedApplianceVa": 0,
        "fixedApplianceCount": 0,
        "hvacVa": 0,
        "evVa": 0
      },
      "expected": 59.06,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Recommended service rating",
          "value": 100,
          "unit": "A"
        },
        {
          "label": "Standard calculation (Part III)",
          "value": 59.0625,
          "unit": "A"
        },
        {
          "label": "Optional calculation (220.82)",
          "value": 64.16666666666667,
          "unit": "A"
        },
        {
          "label": "Headline load in volt-amperes",
          "value": 14175,
          "unit": "VA"
        },
        {
          "label": "General lighting at 3 VA per sq ft",
          "value": 3000,
          "unit": "VA"
        },
        {
          "label": "Lighting group after Table 220.42 demand",
          "value": 4575,
          "unit": "VA"
        },
        {
          "label": "Range demand, Table 220.55 Column C",
          "value": 9600,
          "unit": "VA"
        },
        {
          "label": "Dryer, 5,000 VA minimum",
          "value": 0,
          "unit": "VA"
        },
        {
          "label": "Fixed appliances at full nameplate",
          "value": 0,
          "unit": "VA"
        },
        {
          "label": "EV supply equipment at 125%",
          "value": 0,
          "unit": "VA"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "Under the 2017 edition a small charger carries no 7,200 VA floor",
      "inputs": {
        "calcMethod": "standard",
        "codeEdition": "2017",
        "floorArea": 92.90304,
        "smallApplianceCircuits": 2,
        "hasLaundry": "yes",
        "rangeKw": 0,
        "dryerVa": 0,
        "fixedApplianceVa": 0,
        "fixedApplianceCount": 0,
        "hvacVa": 0,
        "evVa": 3840
      },
      "expected": 39.06,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Recommended service rating",
          "value": 100,
          "unit": "A"
        },
        {
          "label": "Standard calculation (Part III)",
          "value": 39.0625,
          "unit": "A"
        },
        {
          "label": "Optional calculation (220.82)",
          "value": 45.5,
          "unit": "A"
        },
        {
          "label": "Headline load in volt-amperes",
          "value": 9375,
          "unit": "VA"
        },
        {
          "label": "General lighting at 3 VA per sq ft",
          "value": 3000,
          "unit": "VA"
        },
        {
          "label": "Lighting group after Table 220.42 demand",
          "value": 4575,
          "unit": "VA"
        },
        {
          "label": "Range demand, Table 220.55 Column C",
          "value": 0,
          "unit": "VA"
        },
        {
          "label": "Dryer, 5,000 VA minimum",
          "value": 0,
          "unit": "VA"
        },
        {
          "label": "Fixed appliances at full nameplate",
          "value": 0,
          "unit": "VA"
        },
        {
          "label": "EV supply equipment at 125%",
          "value": 4800,
          "unit": "VA"
        }
      ],
      "basis": "ambiguous"
    }
  ],
  "usedByAssemblies": [
    {
      "id": "panel-upgrade",
      "name": "Service panel upgrade"
    }
  ]
}