  "slug": "breaker-size-calculator",
  "category": "electrical",
  "title": "Breaker Size Calculator",
  "description": "Find the smallest standard breaker rating for a load in watts or amps, with the continuous-load rule applied and the conductor ampacity it then demands.",
  "url": "https://craftquantities.com/calculators/electrical/breaker-size-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/breaker-size-calculator.json",
  "inputCount": 6,
  "testCaseCount": 5,
  "sourceCount": 5,
  "lastVerified": "2026-09-11",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/electrical/breaker-size-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Breaker Size Calculator",
    "version": "1.0.0",
    "sourcesChecked": "2026-09-11",
    "url": "https://craftquantities.com/calculators/electrical/breaker-size-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Breaker Size Calculator. Version 1.0.0. Sources checked 2026-09-11. https://craftquantities.com/calculators/electrical/breaker-size-calculator/",
      "apa": "Craft Quantities. (2026). Breaker Size Calculator (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/electrical/breaker-size-calculator/",
      "harvard": "Craft Quantities (2026) Breaker Size Calculator (Version 1.0.0). Available at: https://craftquantities.com/calculators/electrical/breaker-size-calculator/",
      "bibtex": "@misc{craftquantities-calculators-electrical-breaker-size-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Breaker Size Calculator},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/electrical/breaker-size-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "loadMode",
      "label": "I know the load as",
      "type": "select",
      "defaultValue": "watts",
      "options": [
        {
          "value": "watts",
          "label": "Watts (or VA) from the nameplate"
        },
        {
          "value": "amps",
          "label": "Amps from the nameplate"
        }
      ],
      "help": "Whether the appliance's rating plate gives you power or current."
    },
    {
      "id": "loadWatts",
      "label": "Load (W or VA)",
      "type": "number",
      "defaultValue": 4800,
      "min": 1,
      "max": 200000,
      "step": 10,
      "help": "The nameplate power rating of the equipment on this circuit."
    },
    {
      "id": "loadAmps",
      "label": "Load current (A)",
      "type": "number",
      "defaultValue": 20,
      "min": 0.1,
      "max": 800,
      "step": 0.1,
      "help": "The nameplate current draw of the equipment on this circuit."
    },
    {
      "id": "voltage",
      "label": "Circuit voltage",
      "type": "select",
      "defaultValue": "240",
      "options": [
        {
          "value": "120",
          "label": "120 V (North American general purpose)"
        },
        {
          "value": "208",
          "label": "208 V (commercial three-phase wye)"
        },
        {
          "value": "230",
          "label": "230 V (UK, EU, AU single phase)"
        },
        {
          "value": "240",
          "label": "240 V (North American large appliance)"
        },
        {
          "value": "277",
          "label": "277 V (commercial lighting)"
        },
        {
          "value": "400",
          "label": "400 V (European three-phase)"
        },
        {
          "value": "480",
          "label": "480 V (North American three-phase)"
        }
      ],
      "help": "The nominal voltage of the circuit the equipment is connected to."
    },
    {
      "id": "phase",
      "label": "Phase",
      "type": "select",
      "defaultValue": "single",
      "options": [
        {
          "value": "single",
          "label": "Single phase"
        },
        {
          "value": "three",
          "label": "Three phase (balanced)"
        }
      ],
      "help": "Whether the circuit is single or three phase."
    },
    {
      "id": "continuous",
      "label": "Continuous load",
      "type": "select",
      "defaultValue": "yes",
      "options": [
        {
          "value": "yes",
          "label": "Yes — runs three hours or more at a time"
        },
        {
          "value": "no",
          "label": "No — intermittent use"
        }
      ],
      "help": "Whether the load runs for three hours or more at maximum current."
    }
  ],
  "sources": [
    {
      "label": "NEC 240.6(A): standard ampere ratings for inverse-time circuit breakers and fuses — 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A"
    },
    {
      "label": "NEC 210.20(A) and 215.3: the overcurrent device rating shall be not less than 100% of the noncontinuous load plus 125% of the continuous load"
    },
    {
      "label": "NEC 210.19(A)(1): branch-circuit conductors shall have an ampacity not less than the same figure, before any temperature or conduit-fill correction"
    },
    {
      "label": "NEC 240.4: conductors shall be protected at their ampacity — the device rating follows the conductor, not the load it happens to serve"
    },
    {
      "label": "NEC Article 430 governs motor branch circuits: short-circuit and ground-fault protection is sized from Table 430.52 and may substantially exceed the motor's full-load current, so this page does not apply to motors"
    }
  ],
  "testCases": [
    {
      "name": "A 4.8 kW continuous load at 240 V needs 25 A",
      "inputs": {
        "loadMode": "watts",
        "loadWatts": 4800,
        "loadAmps": 20,
        "voltage": "240",
        "phase": "single",
        "continuous": "yes"
      },
      "expected": 25,
      "toleranceDecimalPlaces": 6,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Load current",
          "value": 20,
          "unit": "A"
        },
        {
          "label": "Required minimum at 125% (continuous)",
          "value": 25,
          "unit": "A"
        },
        {
          "label": "Minimum conductor ampacity after corrections",
          "value": 25,
          "unit": "A"
        },
        {
          "label": "Headroom to the next trip point",
          "value": 0,
          "unit": "%"
        },
        {
          "label": "Load as a share of the breaker",
          "value": 80,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "The same load intermittently needs only 20 A",
      "inputs": {
        "loadMode": "watts",
        "loadWatts": 4800,
        "loadAmps": 20,
        "voltage": "240",
        "phase": "single",
        "continuous": "no"
      },
      "expected": 20,
      "toleranceDecimalPlaces": 6,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Load current",
          "value": 20,
          "unit": "A"
        },
        {
          "label": "Required minimum (noncontinuous)",
          "value": 20,
          "unit": "A"
        },
        {
          "label": "Minimum conductor ampacity after corrections",
          "value": 20,
          "unit": "A"
        },
        {
          "label": "Headroom to the next trip point",
          "value": 0,
          "unit": "%"
        },
        {
          "label": "Load as a share of the breaker",
          "value": 100,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "A 1.5 kW continuous load at 120 V steps past 15 A to 20 A",
      "inputs": {
        "loadMode": "watts",
        "loadWatts": 1500,
        "loadAmps": 20,
        "voltage": "120",
        "phase": "single",
        "continuous": "yes"
      },
      "expected": 20,
      "toleranceDecimalPlaces": 6,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Load current",
          "value": 12.5,
          "unit": "A"
        },
        {
          "label": "Required minimum at 125% (continuous)",
          "value": 15.625,
          "unit": "A"
        },
        {
          "label": "Minimum conductor ampacity after corrections",
          "value": 20,
          "unit": "A"
        },
        {
          "label": "Headroom to the next trip point",
          "value": 28.000000000000004,
          "unit": "%"
        },
        {
          "label": "Load as a share of the breaker",
          "value": 62.5,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "A 20 kW three-phase load at 208 V needs 60 A",
      "inputs": {
        "loadMode": "watts",
        "loadWatts": 20000,
        "loadAmps": 20,
        "voltage": "208",
        "phase": "three",
        "continuous": "no"
      },
      "expected": 60,
      "toleranceDecimalPlaces": 6,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Load current",
          "value": 55.514448960540946,
          "unit": "A"
        },
        {
          "label": "Required minimum (noncontinuous)",
          "value": 55.514448960540946,
          "unit": "A"
        },
        {
          "label": "Minimum conductor ampacity after corrections",
          "value": 60,
          "unit": "A"
        },
        {
          "label": "Headroom to the next trip point",
          "value": 8.079970392297929,
          "unit": "%"
        },
        {
          "label": "Load as a share of the breaker",
          "value": 92.52408160090158,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "A 30 A continuous nameplate needs 40 A",
      "inputs": {
        "loadMode": "amps",
        "loadWatts": 4800,
        "loadAmps": 30,
        "voltage": "480",
        "phase": "three",
        "continuous": "yes"
      },
      "expected": 40,
      "toleranceDecimalPlaces": 6,
      "unit": "A",
      "confidence": "medium",
      "steps": [
        {
          "label": "Load current",
          "value": 30,
          "unit": "A"
        },
        {
          "label": "Required minimum at 125% (continuous)",
          "value": 37.5,
          "unit": "A"
        },
        {
          "label": "Minimum conductor ampacity after corrections",
          "value": 40,
          "unit": "A"
        },
        {
          "label": "Headroom to the next trip point",
          "value": 6.666666666666667,
          "unit": "%"
        },
        {
          "label": "Load as a share of the breaker",
          "value": 75,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    }
  ],
  "usedByAssemblies": [
    {
      "id": "panel-upgrade",
      "name": "Service panel upgrade"
    }
  ]
}