Fire Detector Spacing and Count Calculator (BS 5839-1 and NFPA 72)

How many point smoke or heat detectors a flat ceiling needs so no point is farther from one than BS 5839-1 or NFPA 72 allows, with their spacing.

  • Answers as you type
  • Every formula cited
  • Calculated in your browser
SettingsSettings for this calculationUS
Market
Imperial · sales tax
Sets the coverage: BS 5839-1 gives a radius per detector type; NFPA 72 works from the detector's listed spacing.

BS 5839-1 keeps every point within 7.5 m (24 ft 7 in) of a smoke detector and 5.3 m (17 ft 5 in) of a heat detector. NFPA 72 lays detectors out at their listed spacing and keeps every point within 0.7 times it.

The spacing the detector is listed for — a nominal 30 ft (9.1 m) for smoke detectors on a smooth ceiling.

Heat detectors are listed at their own spacing, commonly 15 to 50 ft; the listing, not the catalogue, is the figure to use.

The room's longer dimension, wall to wall.

Each room or space is laid out on its own; a wall or a deep beam starts a new layout.

The shorter dimension, wall to wall.

A corridor narrower than 2 m (6 ft 7 in) is treated as a corridor under BS 5839-1.

Detectors needed

12 detectors

High confidence

The fewest detectors in rows that keep a cell's farthest corner within the coverage radius for NFPA 72 spot detectors at their listed spacing.

Coverage radius
21 ft
Detectors along the length
4
Detectors across the width
3
Spacing along the length
24.5 ft
Spacing across the width
26.33 ft
Farthest point from a detector (a cell's corner)
17.98 ft
Floor area each detector covers on this grid
645.17 ft²
Then change the inputs to see how far the answer moves.

Show calculation logic

How this was calculated

Formula source(s)

  • BS 5839-1:2025, clause 21: on a flat ceiling no point more than 7.5 m horizontally from the nearest point smoke detector or 5.3 m from the nearest point heat detector; in corridors under 2 m wide the coverage need not overlap
  • NFPA 72, National Fire Alarm and Signaling Code, Chapter 17: spot detectors at their listed spacing (a nominal 30 ft, 9.1 m, for smoke on a smooth ceiling), with every point within 0.7 times the spacing of a detector
  • Grid geometry: a rectangular cell's farthest point is its corner, at √((sx ÷ 2)² + (sy ÷ 2)²) from the detector

Inputs used

Standard and Detector Type
NFPA 72 — spot detectors at their listed spacing
Listed Spacing of the Detector
30 ft
Room Length
98 ft
Room Width
79 ft

Intermediate steps

Coverage radius
21 ft
Detectors along the length
4
Detectors across the width
3
Spacing along the length
24.5 ft
Spacing across the width
26.33 ft
Farthest point from a detector (a cell's corner)
17.98 ft
Floor area each detector covers on this grid
645.17 ft²
Final result12 detectors

Confidence note: The fewest detectors in rows that keep a cell's farthest corner within the coverage radius for NFPA 72 spot detectors at their listed spacing.

What this calculation does not cover

  • A flat, smooth ceiling of one height. Pitched ceilings, beams deeper than a tenth of the ceiling height, and walls or partitions near the ceiling each change the layout, and each space is laid out on its own.
  • Ceiling height limits apply: BS 5839-1 gives 10.5 m (34 ft 5 in) for point smoke detectors in general, 7.5 m (24 ft 7 in) for fixed-temperature heat detectors and 9 m (29 ft 6 in) for rate-of-rise; NFPA 72 reduces heat detector spacing on high ceilings.
  • Detectors are kept at least 500 mm (20 in) from walls and obstructions under BS 5839-1 and away from air supply points; the grid positions are the arithmetic before those rules move them.
  • The system category, which decides which rooms are covered at all, comes first and is not part of this count.

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

30 ft98 ft5 at 30 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.

Sources checked 2026-09-22 · v1.0.0

Regulatory standards & verification citations3
  1. BS 5839-1:2025, clause 21: on a flat ceiling no point more than 7.5 m horizontally from the nearest point smoke detector or 5.3 m from the nearest point heat detector; in corridors under 2 m wide the coverage need not overlap
  2. NFPA 72, National Fire Alarm and Signaling Code, Chapter 17: spot detectors at their listed spacing (a nominal 30 ft, 9.1 m, for smoke on a smooth ceiling), with every point within 0.7 times the spacing of a detector
  3. Grid geometry: a rectangular cell's farthest point is its corner, at √((sx ÷ 2)² + (sy ÷ 2)²) from the detector

Which documents these citations point at

  • National Fire Alarm and Signaling Code (NFPA 72) (United States)Fire detection and alarm systems — device spacing, notification and monitoring.

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.

Cite this page

Your workspace

Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.

Now that you have the number

These guides cover the work this quantity is for — the first ones run this calculator inside the section that raises the question.

How to calculate fire detector spacing and count (BS 5839-1 and NFPA 72) in 5 steps

  1. Standard and Detector TypeSets the coverage: BS 5839-1 gives a radius per detector type; NFPA 72 works from the detector's listed spacing.
  2. Listed Spacing of the DetectorThe spacing the detector is listed for — a nominal 30 ft (9.1 m) for smoke detectors on a smooth ceiling.
  3. Room LengthThe room's longer dimension, wall to wall.
  4. Room WidthThe shorter dimension, wall to wall.
  5. Detectors neededThe tool computes the detectors needed from those figures and shows the formula, its sources, and a confidence rating alongside it.

Detectors needed by listed spacing of the detector

Page defaults, not your figures above.

Listed Spacing of the DetectorDetectors needed (detectors)
20 ft20
30 ft12
40 ft6
50 ft4
60 ft4

Frequently asked questions

Why not divide the floor area by the area of the circle?
Because circles do not tile. A 7.5 m (24 ft 7 in) radius traces a circle of about 177 m² (1,900 sq ft), but detectors go on a grid, and the largest square whose corners stay inside that circle is 10.6 m (34 ft 10 in) a side — 112.5 m² (1,211 sq ft), about 64 per cent of the circle. Dividing by the circle buys too few detectors.
Does the grid have to be square?
No. The only condition is that each cell's corner stays within the radius, so the two half-spacings squared and added must not exceed the radius squared. On a long, narrow floor a rectangular grid often saves detectors.
Why does a small store still need two detectors?
Because the rule is a distance, not an area. A 4 × 26 m (13 × 85 ft) store is under the area one detector's square covers, but one detector in the middle leaves both ends 13 m (43 ft) away. Once a room's longest dimension is more than twice the radius, area stops mattering.
Preliminary estimate, not certified engineering. This tool produces an indicative quantity calculation for planning purposes only — it is not a certified structural analysis, a guaranteed material takeoff, or a substitute for building department approval. Always verify measurements on-site and have a licensed contractor or structural engineer review any load-bearing, code-sensitive, or safety-critical work before purchasing materials or starting construction. Spotted an arithmetic or standards error? Report it to contact@craftquantities.com with your inputs — a confirmed fix gets a permanent check of its own, so the same mistake cannot come back.