Electrical

Watts to Amps Calculator (120 V)

Convert an appliance wattage into the current it draws on a 120 V circuit, for breaker and cable checks.

  • Answers as you type
  • Every formula cited
  • Calculated in your browser
SettingsSettings for this calculationUS
Market
Imperial · sales tax
The appliance's rated power in watts.

Take the running wattage from the rating plate. Appliances with motors or compressors draw considerably more than this for the first moments of starting.

Current draw

12.5 A

High confidence

I = P ÷ V at 120 V single phase. For a continuous load, compare the answer against 80% of the breaker rating rather than the full rating.

Conversion factor applied
0.01 A per W
Then change the inputs to see how far the answer moves.

Show calculation logic

How this was calculated

Formula source(s)

  • Rearranged Ohm's law: I = P / V
  • NEC 210.20(A) sizes the overcurrent device at 125% of a continuous load, and 210.19(A)(1) does the same for the conductor — which is the same rule read the other way round, as the familiar 80% ceiling on the breaker rating

Inputs used

Power (W)
1500

Intermediate steps

Conversion factor applied
0.01 A per W
Final result12.5 A

Confidence note: I = P ÷ V at 120 V single phase. For a continuous load, compare the answer against 80% of the breaker rating rather than the full rating.

What this calculation does not cover

  • This is a unit conversion, not a load calculation. It gives what one appliance draws in isolation and accounts for nothing else already on the circuit, no diversity or demand factors, and no service-level total. Sizing a branch circuit, feeder or panel needs a full load calculation to the code in force where you are.
  • The division treats the figure you enter as though voltage and current were in phase. On a motor, compressor, LED driver or switch-mode supply the current the supply actually has to deliver is higher than watts divided by 120, by the reciprocal of the power factor. Where the rating plate gives a VA figure, enter that one instead.
  • Starting current is excluded. A motor or compressor can pull several times its running current for the first moments after switch-on, and that surge is what governs breaker curve choice and nuisance tripping. Nothing in this result reflects it.
  • The arithmetic assumes exactly 120 V at the outlet. Delivered voltage sags under load and with distance from the transformer, and a constant-power load draws proportionally more current as the voltage falls. No voltage drop along the run is calculated here.
  • No conductor is sized by this figure. Ampacity depends on the insulation temperature rating, ambient temperature, and how many current-carrying conductors share a raceway or cable, and the continuous-load uplift cited in the sources is not applied to the answer either. The comparison against 80% of the breaker rating is left for you to make.

Add the equipment this sizes

This result is a specification — 12.5 A — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.

Sources checked 2026-09-02 · in the site-wide review of 2026-09-06 · v1.0.1

Regulatory standards & verification citations2
  1. Rearranged Ohm's law: I = P / V
  2. NEC 210.20(A) sizes the overcurrent device at 125% of a continuous load, and 210.19(A)(1) does the same for the conductor — which is the same rule read the other way round, as the familiar 80% ceiling on the breaker rating

Which documents these citations point at

  • National Electrical Code (NFPA 70) — 210.20(A) (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.

Cite this page

Your workspace

Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.

The practical question behind this conversion is almost always whether something can be plugged in where you want to plug it. Dividing wattage by 120 V gives the current, and current is what the breaker and the conductor care about. The trap is the continuous-load rule: a circuit expected to run for three hours or more is generally limited to 80% of its rating, which turns a 15 A circuit into a 12 A allowance, or roughly 1,440 W. That is precisely why a 1,500 W space heater is a nuisance on a general-purpose circuit despite appearing to fit. Note also that appliances rated in VA rather than watts are already stating volts times amps, so the VA figure is the one to divide — using the watt figure on an inductive load will understate the current the supply actually has to deliver.

How to calculate watts to amps (120 V) in 2 steps

  1. Power (W)The appliance's rated power in watts.
  2. Current drawThe tool computes the current draw from those figures and shows the formula, its sources, and a confidence rating alongside it.

Watts to Amps Calculator (120 V) at common values

Page defaults, not your figures above.

Power (W)Current draw (A)
2001.67
5004.17
1,0008.33
2,00016.7
5,00041.7
10,00083.3

Frequently asked questions

How much of a 15 A circuit can I actually use?
For a continuous load — one running three hours or more — the usual limit is 80% of the breaker rating, so 12 A on a 15 A circuit, or about 1,440 W at 120 V. That is why a 1,500 W heater is awkward on a 15 A circuit even though the arithmetic says it fits.
Does this cover starting current?
No. A motor can pull several times its running current while it comes up to speed. That surge rarely changes the cable size, because it is too brief to heat the conductor, but it does influence breaker type and can cause nuisance tripping on a device with a fast magnetic response.
What if the appliance is rated in VA rather than watts?
Use the VA figure directly for current calculations — it is already volts times amps. Watts is the smaller number on an inductive load, and using it would understate the current the supply has to deliver.
Preliminary estimate, not certified engineering. This tool produces an indicative quantity calculation for planning purposes only — it is not a certified structural analysis, a guaranteed material takeoff, or a substitute for building department approval. Always verify measurements on-site and have a licensed contractor or structural engineer review any load-bearing, code-sensitive, or safety-critical work before purchasing materials or starting construction. Spotted an arithmetic or standards error? Report it to contact@craftquantities.com with your inputs — a confirmed fix gets a permanent check of its own, so the same mistake cannot come back.