SettingsSettings for this calculationUS
The circuit's breaker rating.
15A and 20A are the standard breaker sizes for general-purpose receptacle circuits.
General-use receptacle circuits are standard 120V.
This calculator is for standard 120V general-use receptacle circuits, not 240V appliance circuits.
Estimated maximum outlets
10 outlets (estimated maximum)
This is a general planning guideline based on the NEC's standard per-receptacle load value, not a strict maximum-outlet-count rule — actual safe count depends on what's actually plugged in and used simultaneously, which can be far less than this theoretical maximum.
- Safe continuous circuit capacity
- 1,920 VA
They open the calculator with your figures already in it
Outlets Per Circuit Calculator: 10 outlets (estimated maximum) — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- NEC 220.14(I) values each general-use receptacle at 180 VA for load calculation purposes; combined with the 80% continuous-load rule, this gives a widely used planning estimate of receptacle count per circuit
Inputs used
- Breaker Rating
- 20 A
- Circuit Voltage
- 120 V
Intermediate steps
- Safe continuous circuit capacity
- 1,920 VA
Confidence note: This is a general planning guideline based on the NEC's standard per-receptacle load value, not a strict maximum-outlet-count rule — actual safe count depends on what's actually plugged in and used simultaneously, which can be far less than this theoretical maximum.
What this calculation does not cover
- IN A DWELLING THIS IS A RULE OF THUMB, NOT A CODE LIMIT. The NEC assigns no load to a general-purpose receptacle outlet in a dwelling unit — lighting and receptacles are covered together by a volt-amps-per-square-foot figure — so there is no code maximum number of outlets on a house circuit. The 180 VA per outlet this uses is the NON-DWELLING rule, and applying it to a house gives a sensible answer for the wrong reason.
- Counts general-purpose outlets only. Kitchen small-appliance circuits, bathroom, laundry and any dedicated appliance circuit are required to be separate and are not part of this count.
- A single high-draw appliance can exceed the whole circuit on its own, so the count is meaningless once anything substantial is plugged in. A space heater is most of a 15 A circuit by itself.
- Says nothing about conductor size, voltage drop over the run, or the arc-fault and ground-fault protection the location requires.
- Local amendments are common on this subject and can impose a hard maximum where the model code has none.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-02 · in the site-wide review of 2026-09-06 · v1.0.1
Regulatory standards & verification citations1
- NEC 220.14(I) values each general-use receptacle at 180 VA for load calculation purposes; combined with the 80% continuous-load rule, this gives a widely used planning estimate of receptacle count per circuit
Which documents these citations point at
- National Electrical Code (NFPA 70) — 220.14(I) (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.
A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.
Cite this page
Your workspace
Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.
Protection this work requires
- Stop and check first. Textured ceiling coatings, board behind panels, floor tiles and bitumen adhesive in older buildings — built before asbestos was banned or phased out where you are — can contain asbestos, and drilling or sanding them releases fibres. Do not disturb it — have it sampled first. This is not a job for better PPE.
Tools and safety for this job
To first-fix electrical. Generic types, no brands, no prices.
- Assume every cable is live until proved dead at the point you will touch, with a two-pole tester you have just proved on a known source.
First-fix electrical: This site does not publish a tool list for electrical installation work. In every market it serves, fixed wiring is either reserved to a registered electrician or notifiable to a building authority, and the failure mode is a fire or an electrocution months later rather than a visibly bad job on the day. The calculator gives you the quantities to discuss and to buy against. The installation is a job for a qualified electrician, and the certificate they issue is the point of them.