Twenty-two millimetres between the top of the wall and the bottom of it
The room is empty and swept, the old kitchen went out on Tuesday, the delivery is Monday. A unit list on two sheets of paper, a laser on a tripod, a four-metre tape, nobody else in the building. First measurement across the back wall at skirting height: 4,220. Same wall at worktop height: 4,206. Same wall under where the units will hang: 4,198. Three numbers, one wall, all of them true.
Nothing on the unit list can absorb that. A 600 base is 600, a 400 is 400, and they arrive cut on a beam saw to a tolerance measured in tenths. The room is the variable and the kitchen is the constant — the reverse of how the showroom drawing presented it — and the whole of setting out is deciding where the difference between them is allowed to appear. Get it right and it appears as a 22 mm scribe against a wall nobody looks at. Get it wrong and it appears as a 6 mm taper in the gap over the oven door, at eye height, in the light from the window.
So the order of work for the next two hours is not the order the units will be fitted in. Establish one horizontal datum and never measure a height off the floor again. Mark the run on the floor, then lift it onto the wall. Locate the three things that cannot be moved later — the duct, the waste and the hob supply — before committing to anything that only looks like it matters. And write every dimension on the plaster, because on Monday there will be four trades in this room and only one of them was here when the marks were made.
One line round the room, and the floor is not invited
Set the laser, find the highest point of the floor, and strike a level line all the way round the room at a convenient height above it — a metre is the usual choice because it is easy to add and subtract from, and because it stays visible above a skirting board and below a wall-unit line. That line, not the floor, is the datum for everything with a height in it. The floor gets a vote on one dimension only, and it comes later.
The reason is that a kitchen reads as a set of long horizontals seen against each other. Worktop, underside of the wall units, cornice, top of the plinth: four parallel lines three or four metres long in one field of view, and the eye resolves a divergence between two of them at a fraction of a millimetre per metre. It cannot judge whether the worktop is 900 or 906 above the floor and does not care. Level the carcasses off a floor that falls 15 mm across the run and all four lines follow the floor down; level them off one line and the fall goes quietly into the adjustable legs, which is what the legs are for.
The exception is the appliance aperture. An integrated dishwasher, a built-under oven, a washing machine under a worktop: each has an aperture height on its own datasheet, measured from the finished floor to the underside of the worktop, because the machine stands on the finished floor and has to come back out over it. That single dimension is the floor's vote, it is taken at the worst point rather than the average, and it is why the floor build-up has to be a known number before the legs go anywhere near their final height.
| Dimension | What actually fixes it | What happens if it is taken off the floor |
|---|---|---|
| Worktop surface | Convention and the cook's own reach — around 900 mm in Europe and 36 in in North America. Where an accessibility standard applies, the ADA Standards put a work surface between 28 and 34 in above the finish floor. | The whole run follows the floor's fall, and the divergence shows against the window reveal and the door lining before anyone gets a tape out. |
| Base carcass top | Carcass height plus the adjustable leg, wound against the level line one unit at a time. | Legs wound to a fixed number instead of to a line, which is the same thing as not levelling at all. |
| Top of plinth | Whatever is left between the carcass underside and the finished floor once the legs are set. | It is set before the floor exists, and a 20 mm covering laid afterwards turns a 150 mm plinth into 130 and an appliance into a fixture. |
| Underside of the wall units | The splashback gap you want, measured up from the worktop line — nothing to do with the floor at all. | Two long horizontals that were meant to be parallel and are not, which is the most visible error available in the room. |
| Hood above the hob | The greater of the two figures in the hob's and the hood's own installation instructions, taken from the hob surface. | Not a floor dimension in any regime, and getting it from a magazine rather than the instructions is the version that fails an inspection. |
| Appliance aperture | The machine's datasheet, measured finished floor to worktop underside, at the worst point of the floor rather than the mean. | This is the one that must wait for the floor. Assume it and the dishwasher goes in once and never comes out. |
The gangway you are not allowed to borrow from
Every kitchen argument that ends badly is an argument about the space between two runs. It has no product attached to it, so it is what gets shaved when a 1000 mm unit will not fit, and it is the only dimension in the room that four people a day walk through with their hands full.
For an ordinary dwelling there is no code minimum: the International Residential Code sets no kitchen gangway and Approved Document M sets none for a general-purpose dwelling. The figures that do exist come from the accessibility standards and are worth knowing even on a job they do not cover, because they were arrived at by measuring people. ICC A117.1 Section 804 and the equivalent section of the ADA Standards require 40 inches between all opposing base cabinets, counters, appliances and walls in a pass-through kitchen, and 60 inches where counters, appliances or cabinets occupy three contiguous sides.
What governs the number on a private job is the door, not the walkway. An oven door drops forward. A dishwasher door drops forward and the basket then slides out over it. A fridge door only clears its own carcass past about a hundred and ten degrees.
Somebody has to stand in front of the open one, and the depth of a person bending is the real dimension. Take the deepest opening appliance, add its projection to the run depth, and check that what is left still lets a second person past.
Then the corners, where set-out drawings lie. Two runs meeting at ninety degrees swing a door or drawer front on one into the handle on the other, and the fix is a corner post or filler of 40 to 50 mm off the manufacturer's fitting instructions. The same clash appears where a run finishes against a return wall and where a tall unit stands beside a doorway — none of the three visible on a plan drawn as rectangles.
- Chalk both base runs on the floor at full carcass depth before anything is offered up to a wall.
- Measure the gangway between the chalk lines at three points along it — opposing walls are rarely parallel.
- Open the deepest appliance door on the chalk line, in the position it will occupy, and walk past it.
- Add the corner post or filler at every internal corner and return wall before totalling the run, not after.
- Check both diagonals before setting an island out: an island parallel to one wall in a room 15 mm out of square is visibly not parallel to the other.
Three points that will not move for you, and the order they get located in
Three services in a kitchen behave differently from everything else in it. The waste runs on gravity, so it goes only where a fall can be found. The hob supply is tied to an appliance whose position you are still choosing. And the extract duct has to reach the outside face of the building, which is the one requirement here that a plasterer cannot fix afterwards.
Locate the duct first, because it is the least negotiable and the most expensive to be wrong about. It crosses a ceiling void in a straight line if you are lucky and around a joist run if you are not, and joist direction is a fact about the building rather than a preference. Section M1503 of the International Residential Code governs domestic cooking exhaust equipment and requires the duct to terminate outdoors; Approved Document F Volume 1 sets the kitchen extract requirement in England — Wales, Scotland and Northern Ireland each publish their own equivalent — at a rate that depends on whether the extract sits adjacent to the hob, with ANSI/ASHRAE Standard 62.2 covering the same ground in North America. A recirculating hood is a decision to have no duct — defensible in a flat with a concrete soffit and no external wall in reach, but a layout decision taken now rather than a product substitution made later.
The waste comes second. Move the sink to the window and somebody has to establish that a branch reaches the stack at a permissible fall within the depth available under the floor — a measured number, not an assumed one. The arithmetic and the codes behind it are covered on the costing guide; what belongs here is where it falls in the sequence, which is before the sink position is agreed.
The hob comes third because it is the most movable of the three. It wants a landing length of worktop either side — somewhere to put a hot pan down with both hands, a set-out dimension nobody writes down. It should not sit at the end of a run, where a pan handle projects into a walkway, nor directly under a wall cabinet. Its clearances come from the appliance's own installation instructions: Section 110.3(B) of the National Electrical Code makes those enforceable for listed electrical equipment, the National Fuel Gas Code does the same for a gas appliance, and in Great Britain the Gas Safety (Installation and Use) Regulations 1998 put that duty on the registered engineer who connects it.
A hood is a length before it is an airflow
Capture is geometry. Hot air off a pan rises as a plume that widens as it goes, so a hood narrower than the appliance beneath it is being asked to catch something that has already spread past its edges, and every millimetre of extra mounting height widens the plume further before it arrives. The two dimensions fixed at set-out — the hood's length and its height above the hob — do more for the room than the fan curve does. Make the hood at least as long as the cooking surface, overhang it if the wall units allow, and take the mounting height from the instructions rather than from the eye level of the tallest person in the household. For a domestic hood the volume that matters is its own rated airflow, read against Approved Document F Volume 1 or ANSI/ASHRAE Standard 62.2, and then read again against the duct just routed.
The calculator below is not that. It applies International Mechanical Code Table 507.5, the code-minimum method for an unlisted, field-fabricated Type I commercial hood, rating exhaust per linear foot of hood by style and by the duty classification of the heaviest appliance under it. It belongs here because its governing input is a length, and that length is what you are settling with a pencil this afternoon. Run it if the range going in is a commercial or commercial-style appliance, or if the room is the back kitchen of a café rather than a house. Do not run it for an ordinary domestic hob: the answer will be large, correct for a kitchen that is not yours, and useless. NFPA 96 carries the same duty classifications, and a hood listed to UL 710 may use a lower published rate than the table.
One consequence of that table is worth carrying back into the layout even if you never run it. An island hood is rated higher per linear foot than a wall canopy of the same length and duty, because a hood standing in open air fights cross-draughts on four sides where a wall hood has one side closed for it already. Moving the hob to an island is not a neutral relocation: it extracts more air, through a longer duct, from a position with no wall to hide it in.
For a commercial or commercial-style cooking appliance only. Enter the hood length you have just marked out — the full front length of the hood, not the width of the appliances under it — with the style you have chosen and the duty of the heaviest appliance anywhere beneath it. A domestic hob is outside this table's scope, and the right reference for one is its own rated airflow against Approved Document F or ASHRAE 62.2.
Minimum required exhaust airflow (CFM)
2,400 CFM
- Hood length
- 8 ft2.44 m
- CFM per linear foot rate used
- 300 CFM/ft
The front edge is a straight line because you choose it; the wall is not
Once the carcasses are levelled and pushed back, the front edge of the run is dead straight — it has to be, because doors and drawer fronts hang off it in one plane and any deviation reads as a wavy shadow line. The wall behind is whatever the bricklayer left, and in the room this page opened with it is 22 mm out of parallel with that edge. Only two places will take the difference.
You can scribe the worktop's back edge to the wall, which keeps the junction tight and takes depth out of the counter where the wall bulges. Or you can hold a constant depth, leave a gap and close it with an upstand, which keeps the counter dimension honest and moves the problem to a sealant line. On a stone or engineered top the second is usual and the first is expensive; on laminate the first is normal and belongs to the jointing guide. Either way the number you order against is set by the worst point of the wall, not by the carcass depth in the brochure.
The set-out has just fixed the splashback too. The gap between the worktop line and the underside of the wall units is a height you chose an hour ago with the laser, and if it is going up in the same material as the worktop it stops being a gap and becomes area to be bought. Counter area is therefore a function of three set-out decisions, none of them the run length alone: the length marked through the corners, the depth the worst point of the wall forces, and the splash height the wall-unit line left behind.
Lay it out, row by row
Total the runs as chalked on the floor, through the corners rather than wall to wall. Set the depth to the deepest section the scribe forces on you, not to the nominal carcass depth, and set the backsplash height to the gap between your worktop line and your wall-unit line — the height you settled with the laser, and zero if the splash is going up in tile instead.
Estimated countertop area needed
65.2 sq ft (total)6.05 m²
- Countertop surface
- 36.83 sq ft3.42 m²
- Backsplash
- 28.33 sq ft2.63 m²
Two socket rules in one room, and they are not the same rule
A kitchen is the only room where the electrical layout is decided by the joinery. Every box has to land inside a wall that a carcass, a splashback or a tall unit is about to cover, and the fitter arriving after the plasterer cannot move one. So the sockets get set out with the units, on the same drawing, on the same afternoon.
Above the counter the North American rule is prescriptive and tight. Section 210.52(C) of the National Electrical Code puts a receptacle within 24 inches, measured along the wall line, of every point on the countertop, and requires one for any counter space 12 inches or wider. Section 406.5 forbids an ordinary receptacle installed face-up in a work surface, so the flush detail people ask for on islands has to be an assembly listed for countertop use rather than a socket dropped into the stone. Section 210.8 requires ground-fault protection and its scope has widened across editions, and the island and peninsula provisions in 210.52(C) have themselves changed twice recently — so confirm the edition your jurisdiction has adopted rather than the one you learned. In the United Kingdom BS 7671 sets no spacing rule at all, and the constraint that bites instead is Approved Document M in England, which holds switches and socket outlets in a new dwelling within a band measured from finished floor level.
Away from the counter the rule changes character. The dining end, the wall a bank of tall units stands against, the return by the back door: those fall under the general wall-space provision in Section 210.52(A), which requires that no point along the floor line of any wall space is more than six feet from a receptacle. Spaces narrower than two feet are exempt, and doorways and floor-length windows break a wall into separate runs. A different measurement, taken at a different height, on the parts of the room the kitchen drawing usually leaves blank.
Run this on the wall space that is not counter: the dining end, the wall behind the tall units, the run between the door and the corner. Measure each continuous run separately and leave out anything under two feet. The number it gives you is a code-minimum count for that run, and the countertop above the units is governed by its own tighter rule rather than by this one.
Minimum outlets for this wall space
4 outlets (minimum)
- Wall run length
- 39 ft11.89 m
The ceiling gets set out from the units, not from the room
Downlights on the ceiling centreline put your own shadow on the chopping board. Light from a recessed fitting falls more or less straight down, the person working stands at the front edge of the counter with their back to the room, and a fitting behind them lights their shoulders. So the working line of lights sits forward of the wall, roughly over the front third of the counter, set out from the chalk line on the floor and transferred up rather than from anything about the room's own shape.
The same logic governs the rest of the ceiling plan. Pendants over an island are centred on the island, and the island's centreline is almost never the room's. Under-cabinet lighting is drawn now because its driver has to live somewhere physical — inside a wall unit, above a cornice, in the void over a tall housing — and its cable has to leave the wall at a point that ends up inside a carcass rather than three inches to the left of one. The joists overhead have already decided which of your marked positions is available, in the same void the extract duct is crossing.
Then the load, which surprises people because the fittings are individually small. A contemporary scheme adds downlights, two or three strips of under-cabinet lighting, plinth lights, an island pendant group and sometimes a lit cornice, and hangs the lot off whatever circuit already serves that floor. Count driver input wattage rather than the incandescent equivalent on the box — the second is a marketing figure, not a load — and check the total against the continuous-load limit in Sections 210.19 and 210.20 of the National Electrical Code rather than the breaker's face value.
Count every fitting on the ceiling plan you have just drawn, including the under-cabinet runs and the plinth lights, and enter the driver input wattage. Read the answer against the breaker already protecting lighting on that floor, and against eighty per cent of its rating rather than its full value.
Total connected lighting load
720 W
- Circuit current draw
- 6 A
- Maximum continuous load (80% of breaker)
- 16 A
The circuit's current draw is 6.0 A, at or below 16.0 A — 80% of the breaker rating, which NEC 210.19 and 210.20 set for a continuously-loaded circuit. Under BS 7671 the design check is instead Ib ≤ In ≤ Iz — load under device, device under cable capacity — with no 80% derate for lighting, so this comparison is on the cautious side of the British rule rather than a statement of it. Being inside the rating on this one check settles nothing about the rest of the circuit — the conductors, the overcurrent device, and the work as installed are all outside it.
Finished floor level is a set-out dimension, and it is the one people leave until last
One number in this room cannot come off the level line: the thickness of a floor that has not been laid. Tile plus adhesive is commonly twenty to thirty millimetres of build-up, and everything measured from finished floor upward — plinth height, the aperture the dishwasher stands in, the point at which the back door stops closing — moves by that amount after the units are levelled, unless it is built into the leg height on the day.
The second decision is extent: tile the whole footprint before the carcasses land, or tile the visible field and stop where the plinth will sit. That choice changes the area you are ordering against by the depth of the run times its length — over three square metres on a single 5.2 m run, and more again once a return is counted. The floor's own set-out — where the first full tile lands, which cut the threshold gets, how the grid meets the plinth line — belongs to the tiling guide. And a trap sits between the two decisions: lay a new covering in front of an integrated appliance whose aperture was set to the old floor and the machine never comes out for service again without the floor being cut. Five minutes with a datasheet and a tape, before the legs are wound, is the whole of the fix.
- Write the intended build-up — covering plus bedding — on the wall in pencil before a leg is adjusted.
- Set the leg height so the worktop lands on the level line with that build-up allowed for, then check what plinth height is left.
- Take every integrated appliance's aperture off its own datasheet and confirm it at the worst point of the floor.
- Decide the tiling extent before ordering, and take the area off that extent rather than off the room.
- Check thresholds and door clearance last, with the finished level marked, while a fouling door can still be trimmed.
Enter the area you have actually decided to cover — the whole room if the tile runs under the carcasses, the room less the footprint of the base run if it stops at the plinth. Set the tile size and lay pattern you have chosen, because pattern moves the waste allowance far more than tile size does, and a diagonal or herringbone field in a room this cut-up will consume noticeably more than a straight lay.
Tiles required
36 tiles
- Boxes to order
- 6 boxes
- Tiles before waste
- 32.5 tiles
The chalk lines have already spent some of the money
Three of the quantities that drive a kitchen's cost have now stopped being estimates. Base run and wall run are the lengths on the floor, measured through the corners with the posts and fillers already added; worktop area is that length, the depth the wall forced, and the splash height the wall-unit line left. None of it came off a showroom plan, and it is the first honest version of those numbers anyone has had.
That makes the afternoon of the set-out the cheapest moment to test a layout change. The gangway argument usually resolves by deleting a unit — a 1000 mm base goes, the walkway gets its hundred millimetres, the run shortens. Price the two versions against each other with your own rates before agreeing to it, because the answer is sometimes that the deleted unit was the cheap way to buy the storage and the island replacing it is not. Fill the services and finishes lines with real figures from the trades who have now seen the room: everything located in the last two hours sits in those lines, and they are the half of a kitchen that cannot be changed later without taking the visible half back out.
Enter the run lengths and the worktop area exactly as your set-out produced them, then run it a second time with the unit the gangway forced you to delete taken out. The difference between the two totals is what the walkway costs, and it is a number worth having in front of you before the decision is made rather than after the delivery arrives.
Use the Kitchen Remodel Cost calculatorMarks that have to survive the plasterer
A set-out is worth nothing that is not written where the next trade will find it. Mark the level line, the run line and the wall-unit line on the substrate as well as the finish, and write every service position in figures rather than symbols — specific enough that a plumber who has never met you can work from it. Not a cross labelled sink, but the offset from the end of the run, the height above finished floor, and which side of the stud the pipe passes.
Get a camera on every surface in the hour before the boards go on — each wall, the whole floor, a tape lying in shot for scale — and keep the pictures with the appliance instructions rather than the receipts. In ten years somebody will want to hang a shelf on the wall the hob circuit runs up, and that photograph is the only thing standing between them and it. Then dry-stand the tall units and the corner base against the marks before the plasterer starts: a corner 15 mm tighter than the drawing is a morning's work while the wall is bare and a week's once it is finished.
Try the calculation
Six readings off an empty room
All of them taken with a laser, a tape and an hour, before any material is ordered and while every one of them can still change the layout rather than the invoice.
- Each wall measured at three heights — skirting, worktop and wall-unit line — Design the run against the smallest of the three. Walls lean, and the height at which a wall is narrowest is not the height at which you first measured it.
- Both diagonals of the floor, and the highest point of it — The diagonals tell you whether an island can be parallel to two walls at once. The high point is where the level line and every leg setting are referenced from.
- Gangway between the chalked runs, taken at three points along its length — Against 40 in between opposing runs, and 60 in for a counter on three contiguous sides, in ICC A117.1 Section 804 and the ADA Standards. An ordinary dwelling has no minimum, which is a reason to measure rather than a reason not to.
- Projection of the deepest appliance door, added to the run depth — Oven, dishwasher and fridge, opened on the chalk line in the position they will occupy. This governs the walkway more often than any published figure does.
- Duct route from the hood position to the outside face of the building, with the joist direction — Located first because it is the least negotiable service in the room. IRC Section M1503 requires it to terminate outdoors; Approved Document F Volume 1 sets the requirement in England, with its own equivalent in each of the other UK administrations.
- Intended floor build-up, and the aperture height of every integrated appliance — Covering plus bedding, written on the wall before a leg is wound. The aperture is the one dimension in the room that has to be confirmed against the finished floor rather than the level line.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.