Materials & Quantities

Lighting Circuit Connected Load Calculator

Calculate a lighting circuit's total connected load and check it against the standard 80% continuous-load derating limit.

  • Answers as you type
  • Every formula cited
  • Calculated in your browser
SettingsSettings for this calculationUS
Market
Imperial · sales tax
The total number of light fixtures on this circuit.

On THIS circuit, not in the room. Rooms are routinely split across two circuits precisely so one tripped breaker does not take the lights out, and counting a room's fixtures onto a single circuit both overloads the calculation and misses the reason the split exists. Emergency fittings are usually fed separately and do not belong in this count.

The rated wattage of each fixture (or lamp/driver combination).

The INPUT power the fixture draws from the circuit, driver included — not the lamp's own rating and not the incandescent-equivalent figure printed on retail packaging, which describes brightness rather than consumption. An LED driver takes more than the array it feeds. Where fixtures on the circuit differ, use the largest rather than an average: the breaker sees the sum, and the sum of averages is not the sum.

The nominal voltage supplying the circuit.

120/240 V is North American residential, 277 V US commercial lighting (480 V wye), 347 V Canadian commercial lighting (600 V wye), and 230 V UK/EU. Use the line-to-neutral voltage the fixtures actually see, not the service voltage.

The rating of the protective device on this circuit.

UK domestic lighting is normally a 6 A MCB, sometimes 10 A; a US lighting branch circuit is normally 15 A, occasionally 20 A. Enter the device that is actually in the board, not the one you would like — the check below is only as good as that number.

Total connected lighting load

720 W

ComparisonA comparison, not a check — no result here is an approval.

The circuit's current draw is 6.0 A, at or below 16.0 A — 80% of the breaker rating, which NEC 210.19 and 210.20 set for a continuously-loaded circuit. Under BS 7671 the design check is instead Ib ≤ In ≤ Iz — load under device, device under cable capacity — with no 80% derate for lighting, so this comparison is on the cautious side of the British rule rather than a statement of it. Being inside the rating on this one check settles nothing about the rest of the circuit — the conductors, the overcurrent device, and the work as installed are all outside it.

Circuit current draw
6 A
Maximum continuous load (80% of breaker)
16 A
Then change the inputs to see how far the answer moves.

Show calculation logic

How this was calculated

Formula source(s)

  • Connected load = fixture count × watts per fixture; per NEC 210.19/210.20, a continuously-loaded branch circuit's total load must not exceed 80% of the breaker's rating (equivalently, the breaker must be rated at least load ÷ 0.8)

Inputs used

Number of Light Fixtures
12
Watts per Fixture
60
Circuit Voltage (V)
120
Breaker Rating (A)
20

Intermediate steps

Circuit current draw
6 A
Maximum continuous load (80% of breaker)
16 A
Final result720 W

Confidence note: The circuit's current draw is 6.0 A, at or below 16.0 A — 80% of the breaker rating, which NEC 210.19 and 210.20 set for a continuously-loaded circuit. Under BS 7671 the design check is instead Ib ≤ In ≤ Iz — load under device, device under cable capacity — with no 80% derate for lighting, so this comparison is on the cautious side of the British rule rather than a statement of it. Being inside the rating on this one check settles nothing about the rest of the circuit — the conductors, the overcurrent device, and the work as installed are all outside it.

What this calculation does not cover

  • Watts divided by volts is the current only at unity power factor, and lighting is not at unity. LED drivers and ballasts pull current out of phase with the voltage, so the real figure is watts divided by volts times power factor — at 0.9 that is 11% more current than shown here, and uncorrected budget drivers sit nearer 0.5, which roughly doubles it. The breaker responds to current, not to watts.
  • Steady-state load says nothing about the moment of switch-on. Electronic drivers charge their input capacitors in the first milliseconds at many times running current, and enough drivers on one circuit will trip a B-curve MCB or a thermal-magnetic breaker every time the lights are turned on, on a circuit that clears this check with room to spare. That is a driver-count and breaker-curve question, and it is decided nowhere on this page.

Add the equipment this sizes

This result is a specification — 720 W — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

Part of bigger jobs

This trade is one line of several job takeoffs. Run the whole job and every other trade comes back with it, off the same measurements.

Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.

Sources checked 2026-09-06 · in the site-wide review of 2026-09-06 · v1.0.1

Regulatory standards & verification citations1
  1. Connected load = fixture count × watts per fixture; per NEC 210.19/210.20, a continuously-loaded branch circuit's total load must not exceed 80% of the breaker's rating (equivalently, the breaker must be rated at least load ÷ 0.8)

Which documents these citations point at

  • National Electrical Code (NFPA 70) — 210.19 (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.

Cite this page

Your workspace

Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.

Now that you have the number

These guides cover the work this quantity is for — the first ones run this calculator inside the section that raises the question.

Called something else where you work? Ring final and branch circuits — the term in each market, how close the equivalence really is, and the standard that governs it.

Already gone wrong? My lights flicker or dim

How to calculate lighting circuit connected load in 5 steps

  1. Number of Light FixturesThe total number of light fixtures on this circuit.
  2. Watts per FixtureThe rated wattage of each fixture (or lamp/driver combination).
  3. Circuit Voltage (V)The nominal voltage supplying the circuit.
  4. Breaker Rating (A)The rating of the protective device on this circuit.
  5. Total connected lighting loadThe tool computes the total connected lighting load from those figures and shows the formula, its sources, and a confidence rating alongside it.

Total connected lighting load by number of light fixtures

Page defaults, not your figures above.

Number of Light FixturesTotal connected lighting load (W)
2120
5300
10600
201,200
503,000
1006,000

Frequently asked questions

Why is the 80% continuous-load rule applied?
Because NEC 210.19/210.20 limits a branch circuit supplying a continuous load, one on for 3 hours or more as most lighting circuits are, to 80% of the breaker's rating. Equivalently, the breaker must be rated at least the load divided by 0.8. This calculator checks the circuit's actual current draw against that 80% threshold.
How is the connected load calculated?
Connected load in watts is simply the number of fixtures multiplied by the watts per fixture. Dividing that by the circuit voltage gives the circuit's current draw in amps, which is then compared to 80% of the breaker rating.
What if my circuit fails the 80% check?
A failing result means the connected load draws more current than the continuous-load limit allows for the breaker size entered. Reduce the number of fixtures or wattage per fixture on that circuit, or move to a higher-rated breaker and conductor sized to match.
Preliminary estimate, not certified engineering. This tool produces an indicative quantity calculation for planning purposes only — it is not a certified structural analysis, a guaranteed material takeoff, or a substitute for building department approval. Always verify measurements on-site and have a licensed contractor or structural engineer review any load-bearing, code-sensitive, or safety-critical work before purchasing materials or starting construction. Spotted an arithmetic or standards error? Report it to contact@craftquantities.com with your inputs — a confirmed fix gets a permanent check of its own, so the same mistake cannot come back.