SettingsSettings for this calculationUS
Which way round the conversion runs.
Going from AWG you get an exact area and the metric size that sits nearest. Going from mm² you get the gauge that is not smaller, and the area you would actually receive if you bought it.
The gauge on the cable jacket or the drawing.
Gauge numbers run backwards — 14 AWG is thinner than 12, and each three steps roughly doubles the area. Above 1 AWG the numbering turns over and sizes are written 1/0 through 4/0, which are progressively thicker.
Conductor cross-section
13.3 mm²
6 AWG is 13.30 mm². The geometry is exact — AWG is a defined ratio series — but no metric size lands on it, which is why both the nearest size and the nearest size that is not smaller are given.
- Conductor diameter
- 0.16 in
- Nearest standard metric size
- 0.02 in²
- Nearest metric size that is not smaller
- 0.02 in²
- Difference from that size
- 20.28 %
They open the calculator with your figures already in it
AWG to mm² Wire Size Calculator: 13.3 mm² — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- AWG is defined geometrically: 4/0 is 0.4600 in and 36 AWG is 0.0050 in, with 39 equal ratio steps between them, so diameter = 0.005 in × 92^((36 − n)/39)
- NEC Chapter 9, Table 8 (conductor properties) gives the same areas to three significant figures: 12 AWG = 3.31 mm², 6 AWG = 13.3 mm², 4/0 AWG = 107 mm²
- IEC 60228 nominal cross-sectional areas for standard metric conductors: 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400 mm²
Inputs used
- Convert
- AWG → mm²
- AWG size
- 6 AWG
- Conductor cross-section (mm²)
- 16
Intermediate steps
- Conductor diameter
- 0.16 in
- Nearest standard metric size
- 0.02 in²
- Nearest metric size that is not smaller
- 0.02 in²
- Difference from that size
- 20.28 %
Confidence note: 6 AWG is 13.30 mm². The geometry is exact — AWG is a defined ratio series — but no metric size lands on it, which is why both the nearest size and the nearest size that is not smaller are given.
What this calculation does not cover
- An exact equivalent almost never exists, so every use of this number is a substitution, and substitution is an ampacity decision rather than an arithmetic one. Insulation temperature rating, installation method, ambient temperature, conduit fill and the rating of the terminals all bear on whether a size that matches on area is acceptable in a particular circuit.
- The two systems' standard sizes interleave rather than align. 6 AWG sits between 13 and 16 mm², 4 AWG between 21 and 25 mm² — so a designer working to one standard and buying to the other is always choosing to round up or down, and rounding down is the direction that removes margin.
- Nothing here checks voltage drop. Two conductors of the same area have the same resistance per metre whatever they are called, but the run length, load and acceptable drop decide the size at least as often as ampacity does, and on a long run they decide it outright.
Add the equipment this sizes
This result is a specification — 13.3 mm² — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-11 · v1.0.0
Regulatory standards & verification citations3
- AWG is defined geometrically: 4/0 is 0.4600 in and 36 AWG is 0.0050 in, with 39 equal ratio steps between them, so diameter = 0.005 in × 92^((36 − n)/39)
- NEC Chapter 9, Table 8 (conductor properties) gives the same areas to three significant figures: 12 AWG = 3.31 mm², 6 AWG = 13.3 mm², 4/0 AWG = 107 mm²
- IEC 60228 nominal cross-sectional areas for standard metric conductors: 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400 mm²
Which documents these citations point at
- National Electrical Code (NFPA 70) — Chapter 9 (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.
A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.
Cite this page
Your workspace
Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.