Electrical

Cable Voltage Drop Calculator (mm², Copper or Aluminium)

The voltage a copper or aluminium cable loses on a run, worked from its IEC 60228 resistance at the conductor temperature, single or three phase.

  • Answers as you type
  • Every formula cited
  • Calculated in your browser
SettingsSettings for this calculationUS
Market
Imperial · sales tax
Copper, or aluminium — the conductor metal on the cable's data sheet.

Aluminium carries about 1.6 times copper's resistance for the same area, and IEC 60228 lists aluminium conductors only from 10 mm²; it is met mainly on larger submains and supply cables.

The cross-section of one conductor, as printed on the cable.

The area of a single conductor, not the whole cable: a cable marked 3 × 2.5 mm² has three conductors of 2.5 mm² each. For aluminium, IEC 60228 starts at 10 mm².

The cable's maximum operating temperature, from its data sheet.

A conductor's resistance rises with its temperature — about 0.4% per °C (0.22% per °F) for copper — and the published voltage-drop tables are worked at the cable's maximum operating temperature, so that is the figure to choose. Prysmian's 6242Y twin and earth is 70 °C (158 °F); thermosetting cables run to 90 °C (194 °F).

A single-phase or DC circuit, or a balanced three-phase one.

A single-phase circuit loses voltage in both the line and the neutral, so the resistance counts twice. A balanced three-phase circuit uses √3 in place of the 2, and the drop is between lines.

The route length from the origin of the circuit to the load, one way.

Measure the route the cable takes, including rises and drops, not the straight line. The return conductor is already counted by the 2 for single phase.

The circuit's design current, in amps.

Use the current the wiring rules tell you to calculate with — usually the design current of the load. For three phase, the current in one line.

The nominal supply voltage — line to line for three phase.

The voltage does not change the volts lost; it is what the percentage is taken of. For a DC circuit or any other supply, choose another voltage and type it.

Voltage drop

7.251 V

High confidence

Worked from the conductor's IEC 60228 resistance at the chosen temperature: the same quantity the published mV/A/m tables give for a cable this size, where reactance is negligible. Compare the percentage with the limit your wiring rules set.

Voltage drop as a share of the supply
3.15 %
Voltage at the load
222.75 V
Conductor size in mm²
2.5 mm²
Voltage drop per amp per metre (mV/A/m)
18.02
Conductor resistance at the chosen temperature (Ω/km)
9.01
IEC 60228 resistance at 20 °C (68 °F), Ω/km
7.41
Then change the inputs to see how far the answer moves.

Show calculation logic

How this was calculated

Formula source(s)

  • Bayerische Kabelwerke AG (Bayka), Conductor resistance at 20 °C (68 °F) acc. to EN 60228: maximum DC resistance of plain copper and aluminium conductors, class 1 and 2 — 2.5 mm² copper 7.41 Ω/km (2.26 Ω per 1,000 ft), 16 mm² copper 1.15 (0.351), 25 mm² aluminium 1.20 (0.366) — and of flexible (class 5 and 6) and tinned copper, mostly higher: flexible 2.5 mm² copper 7.98 (2.43), tinned and flexible 8.21 (2.50)
  • Prysmian 6242Y data sheet (BS 6004 flat twin and earth): maximum conductor temperature 70 °C (158 °F); conductor resistance at 20 °C (68 °F) 18.1, 12.1, 7.41, 4.61, 3.08, 1.83 and 1.15 Ω/km for 1 to 16 mm² (5.52, 3.69, 2.26, 1.41, 0.939, 0.558 and 0.351 Ω per 1,000 ft); current ratings referred to BS 7671 Table 4D5
  • NBS Handbook 100, Copper Wire Tables (National Bureau of Standards): the annealed copper standard, 0.017241 Ω·mm²/m (10.371 Ω·cmil/ft) at 20 °C (68 °F), with a temperature coefficient of 0.00393 per °C (0.00218 per °F) at 20 °C
  • NBS Handbook 109, Aluminum Wire Tables (National Bureau of Standards with The Aluminum Association), Table 1: EC-H19 aluminium at 61.0% IACS, 0.028264 Ω·mm²/m (17.002 Ω·cmil/ft) at 20 °C (68 °F), temperature coefficient 0.00403 per °C (0.00224 per °F) at 20 °C
  • Voltage drop from resistance: a single-phase or DC circuit loses I × R on the way out and again on the way back, 2 × R per metre; a balanced three-phase circuit loses √3 × R per metre between lines. Ω/km is numerically mV/A per metre, and 0.3048 times it is mV/A per foot

Inputs used

Conductor
Copper
Conductor size (mm²)
2.5 mm²
Conductor temperature
75 °C (167 °F) — cable whose insulation carries that rating
Circuit
Single phase or DC, out and back
Length of run (one way)
66 ft
Current (A)
20
Supply voltage
230 V single phase
Voltage you are working at (V)
48

Intermediate steps

Voltage drop as a share of the supply
3.15 %
Voltage at the load
222.75 V
Conductor size in mm²
2.5 mm²
Voltage drop per amp per metre (mV/A/m)
18.02
Conductor resistance at the chosen temperature (Ω/km)
9.01
IEC 60228 resistance at 20 °C (68 °F), Ω/km
7.41
Final result7.25 V

Confidence note: Worked from the conductor's IEC 60228 resistance at the chosen temperature: the same quantity the published mV/A/m tables give for a cable this size, where reactance is negligible. Compare the percentage with the limit your wiring rules set.

What this calculation does not cover

  • Resistance only. BS 7671's Appendix 4 and AS/NZS 3008.1.1 tabulate an impedance for the larger cables, which adds the conductor's reactance to its resistance; from about 25 mm² that reactive part is a growing share of the drop and this page leaves it out, so for a large cable the published table's figure is the one to use. Neither table is reproduced here.
  • The conductor temperature is the one chosen, held along the whole run. The published tables assume the cable is at its maximum operating temperature; a lightly loaded cable runs cooler and drops a little less, and one bunched or in hot surroundings may sit at its limit sooner than the current suggests.
  • The √3 for three phase holds only while the three line currents are equal and the neutral carries nothing. A load fed from one line and the neutral of a 400 V supply is a 230 V single-phase circuit, and should be entered as one; an unbalanced three-phase load needs each line worked on its own.
  • The current used is the one entered. The wiring rules say which current a calculation should use — the design current, or for a circuit whose load is spread along it, a figure they set — and which length; this page takes both as typed.
  • Voltage drop is not current-carrying capacity. A cable inside the voltage-drop limit can still be too small for the current once its installation method, grouping and surroundings are applied, and that is a separate selection under the wiring rules, made by the electrician who designs and certifies the circuit.
  • The limit the drop is judged against belongs to the wiring rules in force — BS 7671's Appendix 4 in the UK and, in Australia and New Zealand, AS/NZS 3000 — and to any tighter figure an equipment maker sets. The page reports the percentage and does not judge it.
  • The resistances are IEC 60228's for plain conductors of class 1 and 2, the solid and stranded conductors of fixed wiring. Bayka lists flexible conductors (classes 5 and 6) and tinned ones at a higher resistance for most sizes — flexible 2.5 mm² copper 7.7% above the plain figure, flexible 1.5 mm² 9.9%, tinned flexible 2.5 mm² 10.8% — so a flexible cord or an extension lead drops more than this page shows.

Add the equipment this sizes

This result is a specification — 7.251 V — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

66 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.

Sources checked 2026-10-05 · v1.0.0

Regulatory standards & verification citations5
  1. Bayerische Kabelwerke AG (Bayka), Conductor resistance at 20 °C (68 °F) acc. to EN 60228: maximum DC resistance of plain copper and aluminium conductors, class 1 and 2 — 2.5 mm² copper 7.41 Ω/km (2.26 Ω per 1,000 ft), 16 mm² copper 1.15 (0.351), 25 mm² aluminium 1.20 (0.366) — and of flexible (class 5 and 6) and tinned copper, mostly higher: flexible 2.5 mm² copper 7.98 (2.43), tinned and flexible 8.21 (2.50)
  2. Prysmian 6242Y data sheet (BS 6004 flat twin and earth): maximum conductor temperature 70 °C (158 °F); conductor resistance at 20 °C (68 °F) 18.1, 12.1, 7.41, 4.61, 3.08, 1.83 and 1.15 Ω/km for 1 to 16 mm² (5.52, 3.69, 2.26, 1.41, 0.939, 0.558 and 0.351 Ω per 1,000 ft); current ratings referred to BS 7671 Table 4D5
  3. NBS Handbook 100, Copper Wire Tables (National Bureau of Standards): the annealed copper standard, 0.017241 Ω·mm²/m (10.371 Ω·cmil/ft) at 20 °C (68 °F), with a temperature coefficient of 0.00393 per °C (0.00218 per °F) at 20 °C
  4. NBS Handbook 109, Aluminum Wire Tables (National Bureau of Standards with The Aluminum Association), Table 1: EC-H19 aluminium at 61.0% IACS, 0.028264 Ω·mm²/m (17.002 Ω·cmil/ft) at 20 °C (68 °F), temperature coefficient 0.00403 per °C (0.00224 per °F) at 20 °C
  5. Voltage drop from resistance: a single-phase or DC circuit loses I × R on the way out and again on the way back, 2 × R per metre; a balanced three-phase circuit loses √3 × R per metre between lines. Ω/km is numerically mV/A per metre, and 0.3048 times it is mV/A per foot
Cite this page

Your workspace

Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.

Protection this work requires

  • Stop and check first. Textured ceiling coatings, board behind panels, floor tiles and bitumen adhesive in older buildings — built before asbestos was banned or phased out where you are — can contain asbestos, and drilling or sanding them releases fibres. Do not disturb it — have it sampled first. This is not a job for better PPE.

Tools and safety for this job

To first-fix electrical. Generic types, no brands, no prices.

  • Assume every cable is live until proved dead at the point you will touch, with a two-pole tester you have just proved on a known source.

First-fix electrical: This site does not publish a tool list for electrical installation work. In every market it serves, fixed wiring is either reserved to a registered electrician or notifiable to a building authority, and the failure mode is a fire or an electrocution months later rather than a visibly bad job on the day. The calculator gives you the quantities to discuss and to buy against. The installation is a job for a qualified electrician, and the certificate they issue is the point of them.

Now that you have the number

These guides cover the work this quantity is for.

How to calculate cable voltage drop (mm², copper or aluminium) in 9 steps

  1. ConductorCopper, or aluminium — the conductor metal on the cable's data sheet.
  2. Conductor size (mm²)The cross-section of one conductor, as printed on the cable.
  3. Conductor temperatureThe cable's maximum operating temperature, from its data sheet.
  4. CircuitA single-phase or DC circuit, or a balanced three-phase one.
  5. Length of run (one way)The route length from the origin of the circuit to the load, one way.
  6. Current (A)The circuit's design current, in amps.
  7. Supply voltageThe nominal supply voltage — line to line for three phase.
  8. Voltage you are working at (V)Any nominal voltage the list does not carry.
  9. Voltage dropThe tool computes the voltage drop from those figures and shows the formula, its sources, and a confidence rating alongside it.

Voltage drop by length of run (one way)

Page defaults, not your figures above.

Length of run (one way)Voltage drop (V)
40 ft4.39
60 ft6.59
80 ft8.79
100 ft11
120 ft13.2

Frequently asked questions

Why doesn't the page show BS 7671's mV/A/m figure?
Because BS 7671 is sold by the IET and its tables cannot be reproduced. The page works the same quantity from the conductor's published IEC 60228 resistance at the cable's maximum operating temperature, which for cables up to 16 mm² is the whole of what the table's figure contains. For 2.5 mm² copper at 70 °C (158 °F) that is 17.73 mV/A/m, or 5.40 mV per amp per foot of run; from 25 mm² up the table adds reactance, so use its impedance figure for big cables.
How is this different from the AWG voltage drop page?
That page is the US method: conductor areas in circular mils, a K constant at 75 °C (167 °F) taken from the NEC's Chapter 9, and the code's 3% and 5% suggestions. This one works in square millimetres from the IEC 60228 resistances British, European and Australian cables are made to, at the temperature you choose, and leaves the limit to the wiring rules you work under.
Which temperature should I choose?
The cable's maximum operating temperature, from its data sheet, because that is what the published tables assume and it gives the larger, safer drop. Prysmian's 6242Y twin and earth is 70 °C (158 °F); thermosetting cables such as XLPE run to 90 °C (194 °F). Between the two the same copper conductor's resistance, and so its drop, differs by about 7%.
Why does aluminium drop so much more?
Its resistance is about 1.6 times copper's for the same area — 1.20 Ω/km (0.366 Ω per 1,000 ft) for 25 mm² aluminium against 0.727 (0.222) for copper at 20 °C (68 °F) — and it rises slightly faster with temperature. To hold the same drop, the aluminium conductor is two sizes larger than copper of 10 to 70 mm², and three sizes larger from 95 mm² up; the copper-to-aluminium page finds the size with no more resistance than a given copper one.
What does mV/A/m mean?
Millivolts lost per amp of current per metre of run. Multiply it by the current and by the length in metres, and divide by 1,000 to get volts; for a run measured in feet, multiply the feet by 0.3048 first. It is the same number as the conductor's resistance in Ω/km, doubled for a single-phase circuit or multiplied by √3 for a three-phase one.
Preliminary estimate, not certified engineering. This tool produces an indicative quantity calculation for planning purposes only — it is not a certified structural analysis, a guaranteed material takeoff, or a substitute for building department approval. Always verify measurements on-site and have a licensed contractor or structural engineer review any load-bearing, code-sensitive, or safety-critical work before purchasing materials or starting construction. Spotted an arithmetic or standards error? Report it to contact@craftquantities.com with your inputs — a confirmed fix gets a permanent check of its own, so the same mistake cannot come back.