  "slug": "cable-voltage-drop-calculator",
  "category": "electrical",
  "title": "Cable Voltage Drop Calculator (mm², Copper or Aluminium)",
  "description": "The voltage a copper or aluminium cable loses on a run, worked from its IEC 60228 resistance at the conductor temperature, single or three phase.",
  "url": "https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/cable-voltage-drop-calculator.json",
  "inputCount": 8,
  "testCaseCount": 39,
  "sourceCount": 5,
  "lastVerified": "2026-10-05",
  "citation": {
    "author": "Craft Quantities",
    "title": "Cable Voltage Drop Calculator (mm², Copper or Aluminium)",
    "version": "1.0.0",
    "sourcesChecked": "2026-10-05",
    "url": "https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Cable Voltage Drop Calculator (mm², Copper or Aluminium). Version 1.0.0. Sources checked 2026-10-05. https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/",
      "apa": "Craft Quantities. (2026). Cable Voltage Drop Calculator (mm², Copper or Aluminium) (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/",
      "harvard": "Craft Quantities (2026) Cable Voltage Drop Calculator (mm², Copper or Aluminium) (Version 1.0.0). Available at: https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/",
      "bibtex": "@misc{craftquantities-calculators-electrical-cable-voltage-drop-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Cable Voltage Drop Calculator (mm², Copper or Aluminium)},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "material",
      "label": "Conductor",
      "type": "select",
      "defaultValue": "copper",
      "options": [
        {
          "value": "copper",
          "label": "Copper"
        },
        {
          "value": "aluminium",
          "label": "Aluminium (aluminum)"
        }
      ],
      "help": "Copper, or aluminium — the conductor metal on the cable's data sheet."
    },
    {
      "id": "size",
      "label": "Conductor size (mm²)",
      "type": "select",
      "defaultValue": "2.5",
      "options": [
        {
          "value": "1",
          "label": "1 mm²"
        },
        {
          "value": "1.5",
          "label": "1.5 mm²"
        },
        {
          "value": "2.5",
          "label": "2.5 mm²"
        },
        {
          "value": "4",
          "label": "4 mm²"
        },
        {
          "value": "6",
          "label": "6 mm²"
        },
        {
          "value": "10",
          "label": "10 mm²"
        },
        {
          "value": "16",
          "label": "16 mm²"
        },
        {
          "value": "25",
          "label": "25 mm²"
        },
        {
          "value": "35",
          "label": "35 mm²"
        },
        {
          "value": "50",
          "label": "50 mm²"
        },
        {
          "value": "70",
          "label": "70 mm²"
        },
        {
          "value": "95",
          "label": "95 mm²"
        },
        {
          "value": "120",
          "label": "120 mm²"
        },
        {
          "value": "150",
          "label": "150 mm²"
        },
        {
          "value": "185",
          "label": "185 mm²"
        },
        {
          "value": "240",
          "label": "240 mm²"
        },
        {
          "value": "300",
          "label": "300 mm²"
        }
      ],
      "help": "The cross-section of one conductor, as printed on the cable."
    },
    {
      "id": "conductorTemp",
      "label": "Conductor temperature",
      "type": "select",
      "defaultValue": "75",
      "options": [
        {
          "value": "70",
          "label": "70 °C (158 °F) — thermoplastic (PVC) cable such as 6242Y twin and earth"
        },
        {
          "value": "75",
          "label": "75 °C (167 °F) — cable whose insulation carries that rating"
        },
        {
          "value": "90",
          "label": "90 °C (194 °F) — thermosetting (XLPE), or other cable rated for it"
        }
      ],
      "help": "The cable's maximum operating temperature, from its data sheet."
    },
    {
      "id": "phase",
      "label": "Circuit",
      "type": "select",
      "defaultValue": "single",
      "options": [
        {
          "value": "single",
          "label": "Single phase or DC, out and back"
        },
        {
          "value": "three",
          "label": "Three phase, balanced"
        }
      ],
      "help": "A single-phase or DC circuit, or a balanced three-phase one."
    },
    {
      "id": "length",
      "label": "Length of run (one way)",
      "type": "number",
      "dimension": "length",
      "defaultValue": 20,
      "min": 0.1,
      "max": 2000,
      "step": 0.1,
      "help": "The route length from the origin of the circuit to the load, one way."
    },
    {
      "id": "current",
      "label": "Current (A)",
      "type": "number",
      "defaultValue": 20,
      "min": 0.1,
      "max": 2000,
      "step": 0.1,
      "help": "The circuit's design current, in amps."
    },
    {
      "id": "voltage",
      "label": "Supply voltage",
      "type": "select",
      "defaultValue": "230",
      "options": [
        {
          "value": "230",
          "label": "230 V single phase"
        },
        {
          "value": "240",
          "label": "240 V single phase"
        },
        {
          "value": "400",
          "label": "400 V three phase, line to line"
        },
        {
          "value": "415",
          "label": "415 V three phase, line to line"
        },
        {
          "value": "other",
          "label": "Another voltage — type it"
        }
      ],
      "help": "The nominal supply voltage — line to line for three phase."
    },
    {
      "id": "customVoltage",
      "label": "Voltage you are working at (V)",
      "type": "number",
      "defaultValue": 48,
      "min": 6,
      "max": 1500,
      "step": 1,
      "help": "Any nominal voltage the list does not carry."
    }
  ],
  "sources": [
    {
      "label": "Bayerische Kabelwerke AG (Bayka), Conductor resistance at 20 °C (68 °F) acc. to EN 60228: maximum DC resistance of plain copper and aluminium conductors, class 1 and 2 — 2.5 mm² copper 7.41 Ω/km (2.26 Ω per 1,000 ft), 16 mm² copper 1.15 (0.351), 25 mm² aluminium 1.20 (0.366) — and of flexible (class 5 and 6) and tinned copper, mostly higher: flexible 2.5 mm² copper 7.98 (2.43), tinned and flexible 8.21 (2.50)",
      "url": "https://www.bayka.de/en/service/technical-information/conductor-resistance"
    },
    {
      "label": "Prysmian 6242Y data sheet (BS 6004 flat twin and earth): maximum conductor temperature 70 °C (158 °F); conductor resistance at 20 °C (68 °F) 18.1, 12.1, 7.41, 4.61, 3.08, 1.83 and 1.15 Ω/km for 1 to 16 mm² (5.52, 3.69, 2.26, 1.41, 0.939, 0.558 and 0.351 Ω per 1,000 ft); current ratings referred to BS 7671 Table 4D5",
      "url": "https://datasheet.prysmian.com/pdf/datasheet/en-GB/312416/GB00_6242Y"
    },
    {
      "label": "NBS Handbook 100, Copper Wire Tables (National Bureau of Standards): the annealed copper standard, 0.017241 Ω·mm²/m (10.371 Ω·cmil/ft) at 20 °C (68 °F), with a temperature coefficient of 0.00393 per °C (0.00218 per °F) at 20 °C",
      "url": "https://nvlpubs.nist.gov/nistpubs/Legacy/hb/nbshandbook100.pdf"
    },
    {
      "label": "NBS Handbook 109, Aluminum Wire Tables (National Bureau of Standards with The Aluminum Association), Table 1: EC-H19 aluminium at 61.0% IACS, 0.028264 Ω·mm²/m (17.002 Ω·cmil/ft) at 20 °C (68 °F), temperature coefficient 0.00403 per °C (0.00224 per °F) at 20 °C",
      "url": "https://nvlpubs.nist.gov/nistpubs/Legacy/hb/nbshandbook109.pdf"
    },
    {
      "label": "Voltage drop from resistance: a single-phase or DC circuit loses I × R on the way out and again on the way back, 2 × R per metre; a balanced three-phase circuit loses √3 × R per metre between lines. Ω/km is numerically mV/A per metre, and 0.3048 times it is mV/A per foot"
    }
  ],
  "testCases": [
    {
      "name": "the opening: 2.5 mm² copper at 70 °C (158 °F), 20 m (65.6 ft) at 20 A single phase drops 7.09 V",
      "inputs": {
        "material": "copper",
        "size": "2.5",
        "conductorTemp": "70",
        "phase": "single",
        "length": 20,
        "current": 20,
        "voltage": "230"
      },
      "expected": 7.092852,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 3.0838486956521733,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 222.907148,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 2.5,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 17.732129999999998
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 8.866064999999999
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 7.41
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "the same 2.5 mm² run at 75 °C (167 °F), the opening for other markets: 7.21 V",
      "inputs": {
        "material": "copper",
        "size": "2.5",
        "conductorTemp": "75",
        "phase": "single",
        "length": 20,
        "current": 20,
        "voltage": "230"
      },
      "expected": 7.209337,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 3.1344944347826087,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 222.7906628,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 2.5,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 18.023343
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 9.0116715
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 7.41
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "three phase against single phase: 16 mm² copper at 90 °C (194 °F), 50 m (164 ft), 32 A three phase drops 4.06 V",
      "inputs": {
        "material": "copper",
        "size": "16",
        "conductorTemp": "90",
        "phase": "three",
        "length": 50,
        "current": 32,
        "voltage": "400"
      },
      "expected": 4.06371,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 1.0159274729762946,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 395.9362901080948,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 16,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 2.5398186824407363
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 1.466365
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.15
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "the same run single phase drops 2/√3 times as much: 4.69 V",
      "inputs": {
        "material": "copper",
        "size": "16",
        "conductorTemp": "90",
        "phase": "single",
        "length": 50,
        "current": 32,
        "voltage": "230"
      },
      "expected": 4.692368,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 2.0401599999999998,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 225.307632,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 16,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 2.93273
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 1.466365
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.15
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "aluminium against copper at 25 mm², 70 °C (158 °F), 30 m (98.4 ft), 63 A: aluminium 5.45 V",
      "inputs": {
        "material": "aluminium",
        "size": "25",
        "conductorTemp": "70",
        "phase": "single",
        "length": 30,
        "current": 63,
        "voltage": "230"
      },
      "expected": 5.450004,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 2.369566956521739,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 224.549996,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 25,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 2.8836
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 1.4418
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.2
        }
      ],
      "basis": "cited",
      "sourceIndex": 3
    },
    {
      "name": "copper on the same 25 mm² run: 3.29 V",
      "inputs": {
        "material": "copper",
        "size": "25",
        "conductorTemp": "70",
        "phase": "single",
        "length": 30,
        "current": 63,
        "voltage": "230"
      },
      "expected": 3.288054,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 1.4295886043478259,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 226.71194621,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 25,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 1.7397109999999998
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.8698554999999999
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.727
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "a typed 48 V DC circuit: 10 mm² copper at 70 °C (158 °F), 10 m (32.8 ft), 40 A drops 1.75 V",
      "inputs": {
        "material": "copper",
        "size": "10",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 40,
        "voltage": "other",
        "customVoltage": 48
      },
      "expected": 1.751676,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 3.6493249999999997,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 46.248324,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 10,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 4.3791899999999995
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 2.1895949999999997
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.83
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "no aluminium conductor below 10 mm²",
      "inputs": {
        "material": "aluminium",
        "size": "6",
        "conductorTemp": "70",
        "phase": "single",
        "length": 20,
        "current": 20,
        "voltage": "230"
      },
      "expected": 0,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "low",
      "steps": [
        {
          "label": "Conductor size in mm²",
          "value": 6,
          "unit": "mm²"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a 240 V supply loses the same volts as a 230 V one: 7.09 V",
      "inputs": {
        "material": "copper",
        "size": "2.5",
        "conductorTemp": "70",
        "phase": "single",
        "length": 20,
        "current": 20,
        "voltage": "240"
      },
      "expected": 7.092852,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 2.9553549999999995,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 232.907148,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 2.5,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 17.732129999999998
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 8.866064999999999
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 7.41
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a 415 V three-phase supply: 16 mm² at 90 °C (194 °F), 50 m (164 ft), 32 A drops 4.06 V",
      "inputs": {
        "material": "copper",
        "size": "16",
        "conductorTemp": "90",
        "phase": "three",
        "length": 50,
        "current": 32,
        "voltage": "415"
      },
      "expected": 4.06371,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.9792072028687177,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 410.9362901080948,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 16,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 2.5398186824407363
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 1.466365
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.15
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "1 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 4.33133 V",
      "inputs": {
        "material": "copper",
        "size": "1",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 4.33133,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 1.8831869565217392,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 225.66867,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 1,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 43.3133
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 21.65665
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 18.1
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "1.5 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 2.89553 V",
      "inputs": {
        "material": "copper",
        "size": "1.5",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 2.89553,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 1.2589260869565218,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 227.10447,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 1.5,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 28.955299999999998
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 14.477649999999999
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 12.1
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "2.5 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 1.773213 V",
      "inputs": {
        "material": "copper",
        "size": "2.5",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 1.773213,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.7709621739130433,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 228.226787,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 2.5,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 17.732129999999998
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 8.866064999999999
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 7.41
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "4 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 1.103173 V",
      "inputs": {
        "material": "copper",
        "size": "4",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 1.103173,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.47964043478260854,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 228.896827,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 4,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 11.03173
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 5.515865
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 4.61
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "6 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.737044 V",
      "inputs": {
        "material": "copper",
        "size": "6",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.737044,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.3204539130434782,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.262956,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 6,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 7.370439999999999
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 3.6852199999999997
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 3.08
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "10 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.437919 V",
      "inputs": {
        "material": "copper",
        "size": "10",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.437919,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.19039956521739132,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.562081,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 10,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 4.3791899999999995
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 2.1895949999999997
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.83
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "16 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.275195 V",
      "inputs": {
        "material": "copper",
        "size": "16",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.275195,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.11964999999999996,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.724805,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 16,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 2.7519499999999995
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 1.3759749999999997
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.15
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "25 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.1739711 V",
      "inputs": {
        "material": "copper",
        "size": "25",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.1739711,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.07563960869565217,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.8260289,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 25,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 1.7397109999999998
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.8698554999999999
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.727
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "35 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.1253932 V",
      "inputs": {
        "material": "copper",
        "size": "35",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.1253932,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.05451878260869566,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.8746068,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 35,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 1.253932
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.626966
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.524
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "50 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0926091 V",
      "inputs": {
        "material": "copper",
        "size": "50",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0926091,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.040264826086956515,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9073909,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 50,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.926091
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.4630455
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.387
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "70 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0641324 V",
      "inputs": {
        "material": "copper",
        "size": "70",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0641324,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.027883652173913046,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9358676,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 70,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.641324
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.320662
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.268
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "95 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0461849 V",
      "inputs": {
        "material": "copper",
        "size": "95",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0461849,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.020080391304347828,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9538151,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 95,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.46184899999999995
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.23092449999999998
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.193
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "120 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0366129 V",
      "inputs": {
        "material": "copper",
        "size": "120",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0366129,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.015918652173913042,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9633871,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 120,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.366129
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.1830645
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.153
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "150 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0296732 V",
      "inputs": {
        "material": "copper",
        "size": "150",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0296732,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.012901391304347826,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9703268,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 150,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.296732
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.148366
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.124
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "185 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.02371463 V",
      "inputs": {
        "material": "copper",
        "size": "185",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.02371463,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.010310708695652173,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.97628537,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 185,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.23714629999999998
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.11857314999999999
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0991
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "240 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.01804322 V",
      "inputs": {
        "material": "copper",
        "size": "240",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.01804322,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.007844878260869563,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.98195678,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 240,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.18043219999999996
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.09021609999999998
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0754
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "300 mm² copper, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.01438193 V",
      "inputs": {
        "material": "copper",
        "size": "300",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.01438193,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.00625301304347826,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.98561807,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 300,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.14381929999999998
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.07190964999999999
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0601
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "10 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.740124 V",
      "inputs": {
        "material": "aluminium",
        "size": "10",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.740124,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.3217930434782609,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.259876,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 10,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 7.4012400000000005
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 3.7006200000000002
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 3.08
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "16 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.458973 V",
      "inputs": {
        "material": "aluminium",
        "size": "16",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.458973,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.19955347826086955,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.541027,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 16,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 4.589729999999999
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 2.2948649999999997
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.91
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "25 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.28836 V",
      "inputs": {
        "material": "aluminium",
        "size": "25",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.28836,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.12537391304347825,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.71164,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 25,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 2.8836
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 1.4418
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 1.2
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "35 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.2085804 V",
      "inputs": {
        "material": "aluminium",
        "size": "35",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.2085804,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.0906871304347826,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.7914196,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 35,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 2.085804
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 1.042902
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.868
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "50 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.1540323 V",
      "inputs": {
        "material": "aluminium",
        "size": "50",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.1540323,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.06697056521739131,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.8459677,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 50,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 1.540323
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.7701615
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.641
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "70 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.1064529 V",
      "inputs": {
        "material": "aluminium",
        "size": "70",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.1064529,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.0462838695652174,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.8935471,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 70,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 1.064529
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.5322645
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.443
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "95 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.076896 V",
      "inputs": {
        "material": "aluminium",
        "size": "95",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.076896,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.03343304347826087,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.923104,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 95,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.76896
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.38448
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.32
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "120 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0607959 V",
      "inputs": {
        "material": "aluminium",
        "size": "120",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0607959,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.026433,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9392041,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 120,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.607959
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.3039795
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.253
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "150 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0495018 V",
      "inputs": {
        "material": "aluminium",
        "size": "150",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0495018,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.021522521739130437,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9504982,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 150,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.49501799999999996
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.24750899999999998
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.206
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "185 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0394092 V",
      "inputs": {
        "material": "aluminium",
        "size": "185",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0394092,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.017134434782608694,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9605908,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 185,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.394092
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.197046
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.164
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "240 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.0300375 V",
      "inputs": {
        "material": "aluminium",
        "size": "240",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.0300375,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.013059782608695652,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.9699625,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 240,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.300375
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.1501875
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.125
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "300 mm² aluminium, 10 m (32.8 ft) at 10 A and 70 °C (158 °F): 0.02403 V",
      "inputs": {
        "material": "aluminium",
        "size": "300",
        "conductorTemp": "70",
        "phase": "single",
        "length": 10,
        "current": 10,
        "voltage": "230"
      },
      "expected": 0.02403,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop as a share of the supply",
          "value": 0.010447826086956524,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 229.97597,
          "unit": "V"
        },
        {
          "label": "Conductor size in mm²",
          "value": 300,
          "unit": "mm²"
        },
        {
          "label": "Voltage drop per amp per metre (mV/A/m)",
          "value": 0.2403
        },
        {
          "label": "Conductor resistance at the chosen temperature (Ω/km)",
          "value": 0.12015
        },
        {
          "label": "IEC 60228 resistance at 20 °C (68 °F), Ω/km",
          "value": 0.1
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    }
  ]
}