SettingsSettings for this calculationUS
The AWG size of the copper conductor, as printed on the jacket.
AWG runs backwards: a smaller number is a bigger conductor. 14 AWG is a lighting circuit, 12 AWG a general power circuit, 10 AWG a small cooker or shower feed. The list holds exactly the sizes Table 310.16 publishes. The table does not run through every number: it steps 8, 6, 4, 3, 2, 1, so 3 and 1 have rows while 7, 5 and 9 have none, and only the sizes with a published ampacity are offered. Aluminium is not covered; its ampacity is materially lower for the same size.
Allowable ampacity at 75 °C
25 A
NEC Table 310.16, copper, 75 °C column headline. Table value only — apply the adjustment and correction factors for conduit fill and ambient temperature, and never exceed the 240.4(D) cap on 14, 12 and 10 AWG.
- 60 °C column
- 20 A
- 75 °C column
- 25 A
- 90 °C column
- 30 A
- Maximum overcurrent protection — NEC 240.4(D)
- 20 A
They open the calculator with your figures already in it
Wire Gauge to Amperage Calculator: 25 A — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- NFPA 70 (NEC) Table 310.16 — Allowable Ampacities of Insulated Conductors, copper, 60/75/90 °C columns, ambient 30 °C, not more than three current-carrying conductors
- NEC 240.4(D) — small-conductor overcurrent limits: 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG copper
Inputs used
- Conductor size
- 12 AWG
Intermediate steps
- 60 °C column
- 20 A
- 75 °C column
- 25 A
- 90 °C column
- 30 A
- Maximum overcurrent protection — NEC 240.4(D)
- 20 A
Confidence note: NEC Table 310.16, copper, 75 °C column headline. Table value only — apply the adjustment and correction factors for conduit fill and ambient temperature, and never exceed the 240.4(D) cap on 14, 12 and 10 AWG.
What this calculation does not cover
- Copper only. Aluminium has its own column with materially lower values — using the copper figure on aluminium oversizes the protection, which is the dangerous direction.
- Assumes ambient 30 °C and not more than three current-carrying conductors in the raceway. Outside either condition, the table value must be derated — see the derating calculator.
- The temperature column that governs is the lowest rating in the whole path: conductor, terminations and equipment. Most breakers are listed at 75 °C and much residential equipment at 60 °C.
Add the equipment this sizes
This result is a specification — 25 A — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-01 · in the site-wide review of 2026-09-06 · v1.1.1
Regulatory standards & verification citations2
- NFPA 70 (NEC) Table 310.16 — Allowable Ampacities of Insulated Conductors, copper, 60/75/90 °C columns, ambient 30 °C, not more than three current-carrying conductors
- NEC 240.4(D) — small-conductor overcurrent limits: 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG copper
Which documents these citations point at
- National Electrical Code (NFPA 70) — 240.4(D) (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.
A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.
Cite this page
Your workspace
Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.
The reverse lookup an electrician actually performs on an existing installation: the cable is already in the wall and the question is what it may safely be protected at. That is a different task from sizing a new circuit, and it is the one where the small-conductor rule in 240.4(D) most often surprises people.