The stain turns up in the bedroom, not on the balcony
Four point two metres by one point six, third floor, cantilever slab, tiles bedded straight onto the concrete because the drawing showed tiles and said nothing else. Nobody has complained about the balcony. The complaint is a brown ring on the bedroom ceiling roughly 300 mm inside the external wall, which darkens through November and has usually dried back to a shadow by April. Two contractors have already been out and both looked at the roof.
Lift the tiles and the slab is sound, the falls are poor but not catastrophic, and the concrete under the middle of the deck is dry. The water is coming in at the door. The aluminium threshold is screwed down through a bead of silicone onto bare concrete, there is no pan under it, and whatever waterproofing the deck once had stops dead at the line where the frame sits. That detail did not fail. It was never a detail.
A balcony over occupied space is a flat roof with a door in the middle of its highest edge, and almost everything the flat roofing trade already knows carries across unchanged: falls, upstands, outlets, movement, protection of the membrane from the trades that follow. The one thing that does not carry across is the doorway, because a flat roof never has to solve it. That is the whole subject of this article.
What a balcony threshold is made of
- Wearing surface on pedestals — the client's floor, not the waterproofing; carried level on supports that lengthen as the substrate falls away, so the fall underneath is never compromised to keep the finish flat Roof Paver Pedestal Grid Calculator
- Threshold flashing and cover — the lap that decides the whole balcony: it comes down over the membrane upstand and out across the deck, and it is measured in detail length rather than in area Liquid-Applied Polyurethane Balcony Flashing Seam Calculator
- Separation and protection layer — keeps scaffold boards, balustrade drilling and paver edges off a membrane that is only a couple of millimetres thick when cured Foundation Waterproofing Protection Board Calculator
- Liquid membrane and upstand — seamless across the field and turned up the wall behind the frame, so the vertical leg is part of the same pour rather than a joint in it Cold-Applied Liquid Waterproofing Membrane Volume Calculator
- Screed cut to fall — thickest at the doorway and thinning to nothing at the outlet, which is what makes its volume half of what its maximum depth suggests Floor Drain Slope Screed Volume Calculator
- Structural deck — usually a cantilever, so it deflects and creeps for years after casting and the fall you survey on handover is not the fall it keeps
One junction on the whole elevation faces the wrong way
Walk any elevation and every horizontal-to-vertical junction on it is arranged so that water arriving at the wall is already leaving: the window cill throws forward, the head flashing sheds onto the cill below, the damp-proof course pushes moisture outward, the verge and the eaves hand the roof plane to the gutter. The whole assembly is a sequence of outward handovers, and the trade instinct that goes with it is to detail everything as though the wall is dry on one side and wet on the other.
The balcony threshold reverses that instinct once, at one point, for a few hundred millimetres of width. The wet horizontal surface is outside, the dry horizontal surface is inside, they are within a handful of millimetres of the same level, and there is an opening between them that somebody expects to walk through with a tray of drinks. Worse, the threshold sits at the top of whatever fall the deck has, so any water that does arrive there has no gravity route away from it. Capillary action, wind pressure across an exposed elevation, splashback off a glass balustrade, snow that sits and then melts, and a blocked outlet that turns the deck into a shallow tank all end at the same line, and that line is the only one on the building where inside is downhill.
The upstand is a negotiation between two requirements that both win
Waterproofing practice wants a generous vertical leg at every abutment, and the figure most published guidance converges on for external above-ground work is 150 mm of membrane above the finished surface. BS 6229 works in those terms for flat roofs, NHBC Standards Chapter 7.1 applies the same thinking to flat roofs, terraces and balconies, and AS 4654.2 sets minimum upstands for external above-ground membranes; take the current number from whichever of those governs your job rather than from habit, because the figure and the exceptions attached to it have moved between editions.
Accessibility wants the opposite and is not negotiable either. Approved Document M pushes level access at principal entrances and in new dwellings, and the ADA Standards for Accessible Design cap a change in level at half an inch with anything above a quarter inch bevelled. Neither of those requirements yields to a waterproofing preference, and a designer who resolves the conflict by simply leaving the upstand out has not resolved it. What actually resolves it is a third element: a grated drainage channel immediately outside the door, running the full width of the opening and past it at both ends, into which a shortened membrane leg terminates. The channel replaces the height with a capture point.
That only works if the channel is a drain and not a decoration. It has to fall to the outlet, be connected to it with a pipe that will not freeze solid on a north elevation, and lift out for cleaning by somebody standing on the balcony with no tools. Channels that discharge into a blind sump, channels laid dead level, and channels grouted permanently into the tiling are all common, and all three convert a compliant detail into a reservoir sitting against the door frame. On existing work, lift the grating before you price anything: what is underneath tells you more about the building than the drawings will.
The door itself is the other half of the junction. A threshold with a drained and pressure-equalised sill is a different product from a domestic sill section with a strip of foam under it, and the difference shows up under wind-driven rain rather than under a hose. ASTM E2112 sets out installation practice for exterior doors and windows including the sill pan and its end dams, ASTM E1105 is the field water penetration test you use when the argument is about whether the leak is the door or the deck, and ASTM E2128 is the guide to evaluating an existing leak methodically instead of replacing components in order of price. The membrane and the door have to be sealed to each other in a defined order, with one of them lapping over the other, and that order belongs on a drawing before either trade arrives.
| Strategy | What the membrane does at the door | What has to be true for it to work |
|---|---|---|
| Full upstand behind the frame | Turns up to the full conventional height and terminates in a chase or under a cover flashing | A step out of the door that the accessibility requirement in force will actually accept |
| Shortened upstand with a threshold channel | Turns up a reduced leg into the back of a grated channel running past both ends of the opening | The channel falls to the outlet, is piped to it, and lifts out for cleaning without tools |
| Drained sill on a bonded pan | Terminates onto a pan beneath the frame, with the door's own weep path discharging over the deck | A tested drained sill sealed to the pan, with end dams, not a section screwed to bare concrete |
Survey the fall you inherited, then price the screed
A fall that exists on a section drawing is a design fall, and what survives onto a finished deck is always less: construction tolerance takes some, the screeder takes some flattening the last metre to meet an edge trim, and a cantilever slab takes the rest by deflecting and then creeping for years afterwards. BS 6229 handles that by designing to roughly twice the fall you want to end up with, so that the deck still drains once everything has moved. AS 4654.2 approaches external above-ground work from the same direction with a stated minimum fall in the region of one in a hundred. Both are worth reading in the current edition rather than quoting from memory, and both assume somebody checks the achieved fall rather than the drawn one.
On existing balconies, measure before you promise anything. A rotary laser and a rule, readings at the frame, at a metre out, at the nose, and at both ends, all written down on a sketch that goes in the file. Older balconies were frequently built falling back towards the building on purpose, so that runoff did not drip onto the pavement below, and that decision is survivable right up until somebody replaces the doors with a level threshold. If your survey finds a deck falling inward, the flashing conversation is over until the fall is fixed, and fixing it usually means a screed rather than a coating.
Falls on a balcony are also rarely a single plane. A deck draining to one corner outlet falls two ways at once, and a deck with a threshold channel along the building edge falls away from the building along its whole length and then along the channel to the outlet. Set the high point at the door, the low point at the outlet, and check the diagonal, because a plane that is correct on both edges can still pond in the middle if it was built as two triangles that do not meet.
For pricing, the useful property of a screed laid to falls is that it tapers to nothing at the drain, so its volume is well under what a uniform layer at the deep end would cost — but how far under depends on where the falls meet. A single plane running down to a channel along one side is a wedge and averages half its maximum depth. Four planes meeting at a central gully make a shallow upside-down pyramid, which holds a third of its box, so they average two-thirds, and a gully deck ordered at half comes up a quarter short.
Put the deck area and the depth at the far edge in and it returns the wedge volume rather than the slab volume, which is the number the mixer actually needs.
How the floor falls, which is what sets the average depth.
The floor area that slopes down toward the drain.
The screed thickness at the perimeter, where it is deepest, tapering to zero at the drain.
Screed volume needed
13.4 gal
Assumes a simple linear slope from the perimeter down to a single central drain — a floor with multiple drains or a non-uniform slope will need a more detailed volume takeoff.
They open the calculator with your figures already in it
Floor Drain Slope Screed Volume Calculator: 13.4 gal — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- The wedge tapers to nothing at the drain, and no screed can. A bonded sand-cement screed wants roughly 25 mm (1 in) at its thinnest and an unbonded or floating one 50 mm (2 in) or more, so the real pour is this wedge PLUS that minimum carried across the whole area — which on a small wet room is usually more material than the wedge itself. Feather it out below that instead and the thin ring around the drain debonds and cracks under the tile.
- Depth here is measured from a substrate assumed flat and level, which a deck rarely is. If the slab already falls the wrong way, or the drain body and its clamping flange sit proud of it, the maximum depth entered above stops describing the pour. Take levels off the drain flange and off the highest point of the slab before ordering — on a dished floor the make-up can be more material than the fall itself.
The field coat is the part that usually goes right
Cold liquid-applied membranes win on balconies for a geometric reason rather than a chemical one: a small deck is nearly all edge. A four-by-two balcony has under nine square metres of field and something like thirty metres of perimeter, upstand, corner and penetration, and a system that arrives as sheets has to be cut, welded or dressed at every one of them. A system that arrives in a tub follows the shape. The cost per square metre looks alarming next to sheet materials right up until you notice how little of a balcony is actually field.
The number that governs the order is dry film thickness, and the number that governs the tub count is solids content, because everything that is not solids evaporates during cure. A product at eighty per cent solids has to go down noticeably thicker wet than the thickness you want dry, and applicators who work to a coverage rate printed on a lid rather than to a wet film gauge routinely land under specification in the middle of a roller pass where nobody is looking. Use the comb, use it on every coat, and record the readings.
Specify the right family for the exposure while you are at it. ASTM C836 covers a cold liquid-applied elastomeric membrane intended to sit under a separate wearing course, ASTM C957 covers one with an integral wearing surface designed to be walked on directly, and ASTM C898 is the guide to using the first of those properly. Choosing a buried-membrane product and then leaving it as the finished floor of a balcony is one of the commonest specification errors on this detail, and it fails by ultraviolet degradation and abrasion rather than by leaking, which means it fails slowly and out of warranty. ASTM C1305 is the crack bridging test to ask about when the substrate is a concrete slab with a history.
Dry film thickness divided by the solids fraction gives the wet film you actually have to lay, and that is what turns a deck area into a number of tubs.
The total surface area to be waterproofed.
The cured (dry) membrane thickness required by the manufacturer's spec.
The percentage of the wet product that remains after solvent/water evaporates during cure.
Liquid membrane volume needed
25.2 gal
Solids content and dry film thickness requirements vary by manufacturer and application (horizontal vs. vertical, exposure condition) — confirm your specific product's technical data sheet for exact coverage rates.
- Required wet film thickness
- 75 mils
They open the calculator with your figures already in it
Cold-Applied Liquid Waterproofing Membrane Volume Calculator: 25.25 gal — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- A cold-applied system is resin plus reinforcement, and the reinforcement drinks far more than the field coat does. Polyester fleece has to be wetted out from underneath and above to be properly embedded, and every upstand, internal corner, outlet, penetration and movement joint takes a reinforced detail band laid before the field goes down. Detailing consumes material at a rate that has nothing to do with the flat area, and it is where jobs run short.
- The area entered is a flat surface, and a waterproofed roof is not one. Upstands of 150 mm (6 in) and more right round the perimeter, kerbs to every rooflight and plant base, gutter cheeks and the flange of every outlet are all additional surface, and on a small busy roof that detail area can rival the field it surrounds.
Everything that is not field is a seam, and seams are what you buy
In a liquid system the field coating is reinforced only where it needs to be, and every place it needs to be is a detail: the perimeter upstand, the threshold, every internal and external corner, the outlet flange, movement joints, day joints, substrate cracks, balustrade bases, and the penetrations somebody added for deck lighting. Each of those takes reinforcement fabric or a flashing strip embedded between coats, and each is measured in linear metres.
Run the numbers on a small deck and the proportions surprise people the first time. Take that four-point-two by one-point-six balcony: two long edges, two returns, the threshold across the door, four corners detailed individually, an outlet, a movement joint at the slab junction and four balustrade bases. The field is under seven square metres. The detail length is comfortably north of twenty-five metres. On a balcony, the reinforcement is not a rounding item on the order, it is the order.
Corners consume more than their length suggests, because fabric will not turn a three-way corner without being cut and lapped, and every splice needs overlap. Fabric also has to be fully wetted out — laid into wet base coat and worked through with a roller until the weave disappears — which takes more material than laying it dry and coating over it, and a great deal more than the theoretical length. A waste allowance in the high single figures is normal, and low double figures is realistic on a deck with a lot of corners.
Sequence matters as much as quantity. Details go in first, cure, and then the field coat runs over them, not the other way around, because a detail applied over a cured field coat depends on adhesion to a surface that has already skinned. On a threshold specifically, the reinforcement runs continuously from the deck, up the upstand, and returns into the door reveal or onto the pan, in one piece where the geometry allows it, so that the most loaded part of the system contains no splice.
Measure the detail run off the plan before the material is ordered, not off the deck on the day. The tub count and the fabric count are bought from different parts of a supplier's catalogue and arrive on different lead times, and a crew standing on a scaffold with enough coating and not enough scrim will detail the easy runs, leave the corners, and come back to them after the base coat has cured.
- Grind out and fill cracks, honour any moving joint as a joint rather than filling it, and prime to the system's own specification.
- Detail the outlet first, dressing fabric into the flange so the field coat later laps onto detail work rather than the reverse.
- Detail internal and external corners individually, cutting and lapping fabric rather than forcing a single piece to turn.
- Run the threshold in one continuous piece from deck to upstand to reveal or pan, avoiding any splice within the door width.
- Detail the perimeter upstands and any balustrade bases, then let the detail coat cure before the field goes on.
- Apply the field coats to the wet film thickness the gauge shows, and record the readings against the areas they were taken in.
Add up every metre of seam, upstand, corner and drain detail, add the overlap allowance, and this returns the reinforcement length to order — the line item small balconies are always short of.
SettingsSettings for this calculation
Waste is set to 8% by hand. Pick a tier above to replace it, or keep your own figure.
The combined length of all seams, drains, and edge details needing reinforcement.
Extra material to allow for overlaps, cutting waste, and detail transitions.
Seam flashing needed
88.56 ft
They open the calculator with your figures already in it
Liquid-Applied Polyurethane Balcony Flashing Seam Calculator: 88.56 ft — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- A length is not an order. Reinforcement fabric comes by the roll in a fixed band width, and the width follows the detail — how far the band runs up the upstand and back out onto the deck, commonly around 100 mm (4 in) each way at a wall junction and more at a drain. The fabric is also only half the material: it has to be laid into wet resin and then over-coated, and detail work consumes resin far faster per square metre than the flat deck does. Order the field coating off the deck area and the fabric off this figure, and the detailing is the part left short of resin — which is where the system is already thinnest.
- Fabric will not turn a sharp corner. Every internal angle — deck to upstand, upstand to door cill — needs a fillet or cove formed first, or the reinforcement bridges the angle and tents, leaving a void behind it with no bond on either side. That void is invisible under the top coat and it is the first thing to split when the deck moves. The filleting material, and the primer the substrate needs before any of it, are in neither this length nor its waste allowance.
- A movement joint counted as plain seam length gets the wrong detail. A joint designed to open cannot simply be reinforced across it: the membrane has to be free to stretch there, which means a bond-breaker tape or a loop of fabric laid with slack, and materially more length at that joint than the straight run someone measured. Reinforce a moving joint rigidly and it tears along exactly the line it was there to protect.
The holes somebody drills after you have left
A guarding post core-drilled and resin-anchored through a finished membrane is a leak with a date on it, and it is the single most reliable way to ruin work that was otherwise sound. It happens because the balustrade is a different trade on a different order with a different programme, and because the deck looks finished, so it looks like a surface you can drill.
There are three honest answers. Fix the balustrade to the fascia or the slab edge so nothing passes through the horizontal plane at all, which is the cleanest and is why so much new work does it. Set the posts and their base plates first and dress the membrane up and onto them as detailed penetrations, which puts the drilling before the waterproofing rather than after it. Or provide a bonded collar or puddle flange at each post position, installed as part of the membrane and left proud, with the balustrade fixed into it afterwards. What does not work is any of the three decided on site by whoever arrives second.
There is a structural conversation running underneath the waterproofing one, and it competes for the same material. Guarding has to resist a horizontal line load, that load goes into an anchor, and the anchor goes into a slab whose top fifty millimetres are also carrying the falls screed and the cover to the reinforcement. Settle anchor type, embedment and edge distance with whoever is designing the guarding before you commit to a build-up, and put a hold point in the programme after the posts and before the membrane. A hold point costs a day. Retrofitting a post penetration into a completed liquid system costs the deck.
Where the water leaves, and where it goes when it cannot
Most balconies drain through one outlet, which means most balconies have a single point of failure with leaves, moss, cigarette ends and a child's tennis ball all queuing to find it. BS EN 12056-3 covers roof drainage layout and calculation and BS EN 1253 covers gullies for buildings; between them they tell you what size the outlet should be and what the gully has to do, and neither of them can help once the grating is under a pot plant.
So the question worth asking on a balcony is not what happens when the drain works, it is what happens when it does not. On a roof the answer is a mandated secondary drainage path — the International Building Code chapter on roof assemblies and the plumbing code between them require an emergency route, sized from tributary area against the local design rainfall intensity, discharging somewhere visible so that a blockage announces itself. Balconies frequently sit outside that requirement, and yet a balcony with a level threshold and a blocked outlet floods a bedroom rather than a roof void. Borrow the roof logic even where nothing compels you to.
The practical version is a weep or scupper through the front fascia, set slightly above the deck at the low corner, discharging clear of the elevation below. It stains, and it is meant to: a mark on the render that appears three days after a storm is a maintenance call, whereas the same water going the other way is an insurance claim. Set the invert of the overflow above the deck rather than level with it so the primary outlet does the ordinary work and the overflow only ever runs in anger.
The tributary area is only the balcony, but the sizing factor still comes from the local rainfall intensity table — run it to check that the scupper you were going to drill is not a token gesture.
The roof area draining to this scupper or secondary drain.
The opening area required per unit of roof area, set by local design rainfall intensity and code drainage tables.
Required scupper opening area
77.4 in²
The sizing factor depends on your local design rainfall intensity and applicable plumbing code roof drainage table (e.g. IPC) — confirm the correct factor for your jurisdiction and roof drainage design (primary vs. secondary/emergency) before sizing scuppers.
They open the calculator with your figures already in it
Roof Scupper/Secondary Emergency Drain Sizing Calculator: 77.4 in² — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 77.4 in² — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- Returns an AREA, and a scupper is not sized by area alone. It spills as a weir, so what it passes depends on how WIDE the opening is and how deep the water stands above its invert, with flow climbing as roughly the 1.5 power of that depth. A tall narrow slot and a wide low one of the same area are not interchangeable — the wide one drains the roof, the narrow one needs far deeper standing water before it moves the same flow.
- Says nothing about how high to set the invert, and that is the number deciding how much water the structure has to hold. An overflow set high leaves a deeper layer standing over the whole tributary area before it spills, and that depth is a real load on deck and framing that has to be checked for ponding — an opening area cannot fix it.
The finish the client wanted is the layer that hides the evidence
Whatever goes on top of the membrane is a wearing surface and a client requirement, and it has no waterproofing duty at all. Treating it as though it does is how balconies end up tiled with a rigid bonded finish over a moving cantilever, with the grout cracking at the perimeter within two winters and everyone blaming the tiler.
Bonded tile over a liquid membrane can be done, but only inside a system rated for it — ANSI A118.10 describes the load bearing bonded waterproof membrane that thin-set tile is allowed to sit on, the TCNA Handbook carries the exterior deck methods, and BS 5385-3 covers external ceramic floor tiling practice. Three things then have to be right: perimeter and intermediate movement joints that actually pass through the tile and the bed, an adhesive rated for external freeze-thaw exposure, and drainage at the bedding layer rather than only at the tile surface, because water gets into the bed, sits on the membrane, and freezes there.
Pedestal-supported pavers dodge most of that by keeping the finish level and dry-laid over a falling substrate, with the water running away underneath at membrane level, and by leaving the membrane accessible rather than entombed. They introduce their own arithmetic — support grid, height range, wind uplift on a raised edge — which the pedestal terrace guide covers rather than this one.
Either way the membrane needs protecting from the trades that follow it, and that protection is measured over the field and the upstands together rather than over the floor plan. Scaffold boards, balustrade drilling swarf, a dropped tile cutter and paver edges all land on a cured film only a couple of millimetres thick. Protection board is cheap, and the alternative is a repair executed underneath somebody else's finished floor.
Take the deck area plus the developed area of every upstand, since the vertical legs are where boards get cut and where the coverage estimate normally goes wrong.
The total below-grade foundation wall area to be protected.
The area of a single protection board sheet.
Protection board sheets needed
17 sheets
They open the calculator with your figures already in it
Foundation Waterproofing Protection Board Calculator: 17 sheets — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- The count is wall area divided by sheet area, with no allowance for cutting waste, offcuts around window wells and pipe penetrations, or the extra coverage some specifications require at corners and footing turn-downs. Rounding up is not that allowance: 50 m² of wall on 2.88 m² boards gives 18 sheets, which is 1.84 m² of spare board across the whole job.
- Sheet area is the only property of the board this page uses, so a thin asphaltic hardboard, a dimpled polymer sheet and a rigid insulation panel all return the same count for the same wall. Whether the board's thickness and compressive strength survive the backfill material, the lift depth and the compaction plant is a separate judgement the sheet count does not make.
- Only the boards are counted. The mastic dabs, tape, termination bar and mechanical fixings that hold the board against the wall until backfill is placed are not in the result, and neither is the membrane, the primer or the perimeter drain the board exists to protect.
- The sheet area field runs from 1 to 6 m² (10.8 to 64.6 sq ft), so a protection course supplied as a roll cannot be entered as a single unit, and the wall area field replaces anything above its 1,000 m² maximum (about 10,760 sq ft) with that maximum. A wall larger than that has to be run in sections and the counts added, which rounds up once per section.
Fill it with water while you can still fix it
A flood test is the only check that exercises the whole assembly in the direction it will actually be loaded, and it costs a day. ASTM D5957 is the guide to flood testing horizontal waterproofing installations, and it sets out the head, the hold period and the structural checks; take those from the document rather than from what the last job did. The structural check is not a formality on a cantilever: a shallow pond over a small balcony is still several hundred kilograms sitting at the end of a lever arm, and somebody has to confirm the slab is happy holding it.
Dam the threshold, plug the outlet, fill, and then go and look at the soffit and the ceiling below rather than at the water. Where flooding is impossible — an occupied flat underneath, a deck with no way to dam the door, a structure nobody will sign off for the load — ASTM D7877 covers electronic methods for locating leaks in waterproof membranes, which find breaches in a cured film without needing a pond above it.
Photograph the detail work before anything covers it: the outlet before the field coat, the threshold reinforcement before the flashing, the wet film readings against the areas they came from, the protection board before the pavers. Balcony leaks surface years later and two storeys from where the argument starts, and the file is what turns a six-week dispute into a twenty-minute one. Where exterior elevated elements are subject to periodic inspection — California Senate Bill 721 and Senate Bill 326 being the best-known example of that regime — those photographs become somebody else's baseline as well as your defence.
Finally, none of it is worth a fall from the edge. The balustrade is usually off or not yet fitted while the membrane goes on, which is exactly when the deck is most attractive to walk backwards across with a roller. OSHA 29 CFR 1926 Subpart M governs fall protection on that work in the United States, and every jurisdiction has its equivalent; edge protection goes up before the tiles come off, not after the first coat.
Ordering a balcony outward from the door
Quantify from the threshold outward, because that is the order the risk runs in and because the detail items — reinforcement, protection, the overflow nobody drew — are the ones that get left off a takeoff built from floor area.
- Reinforcement and flashing, by the metre of detail — Perimeter, upstands, threshold, every corner, the outlet flange, movement joints and each balustrade base, plus overlap at splices. On a small balcony this exceeds the field in importance and often in cost.
- Field membrane, by tubs at wet film thickness — Dry film thickness divided by solids content gives the wet film; order against that, not against the coverage figure printed on the lid.
- Screed to falls, as a wedge — Maximum depth at the far edge tapering to nothing at the outlet: a single plane to a channel averages half the maximum, planes meeting at a gully two-thirds. Confirm the achieved fall by survey before ordering anything.
- Protection layer over field and upstands — Measured over the developed area including vertical legs, and ordered before the following trades arrive rather than after the first board is dropped.
- Outlet, threshold channel and the overflow — One outlet is one point of failure; price the secondary route through the fascia at the same time, sized from tributary area against local rainfall intensity.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.
