Insulation

Insulating a Suspended Timber Ground Floor

The void under a period floor is a drying machine. Insulate between the joists without switching it off, and the floor gets warm instead of rotten.
  • 21 minReading time
  • 13Sections
  • 8Calculators inline
  • Last reviewed

One Board Up in the Bay Window

The board comes up with a bolster and a wrecking bar, and underneath is not what the owner expected. No concrete. A dark drop of four or five hundred millimetres onto bare earth, a low honeycomb wall of brickwork carrying a timber plate across the middle of it, joists sitting on that plate at something near four hundred centres, and a slow movement of cold air you can feel on the back of your hand before you can see anything at all. Out at the front elevation, below the damp course, a terracotta airbrick is feeding it.

The owner's complaint is the floor is freezing and the rug lifts off it in a gale. Both symptoms come from the same place, and only one of them is a heat-loss problem. Conduction through a bare 22 mm softwood deck is real but modest; the air arriving through the gaps between shrunken square-edge boards, drawn up by the stack effect of a house with an open flue, is the part that makes a room unusable at the ankles. A job that fixes only the conduction leaves the client still cold and still complaining.

The trap is the obvious fix. Stuff the void solid, block the airbricks so the draught stops, and the floor will be warmer for two winters — after which the joist ends bearing into a solid brick wall have nothing drying them, the plate on the sleeper wall has been sitting at a raised moisture content since the first autumn, and the repair is structural. Everything below is written to keep both outcomes on the table at once: a warm floor and a void that still works.

Why the Hole in the Wall Is There

A suspended timber ground floor is timber suspended over damp ground with nothing between the two but moving air. That air is the entire moisture strategy. Soil beneath the oversite gives up water vapour continuously, at a rate set by ground temperature rather than by anything happening indoors, and the only mechanism removing it is cross-ventilation from one elevation through to the opposite one. Stop the flow and the vapour has nowhere to go but into the nearest cellulose, which is the underside of your joists.

In England the requirement sits in Approved Document C of the Building Regulations, Site preparation and resistance to contaminants and moisture, which sets out a ventilated air space beneath a suspended timber ground floor with openings on opposing external walls. Remember the form the figure takes rather than the figure: an opening area per metre run of external wall or per square metre of floor, whichever produces more, so a long thin room and a large square one do not get the same answer. The under-floor ventilation provisions of the International Residential Code reach the same place by different arithmetic, expressing minimum net free area as a ratio to the area of the under-floor space, reduced where an approved ground vapour retarder is laid.

Free area is where estimates go wrong. The gross opening of a clay airbrick and the free area through its slots are nowhere near each other, the maker publishes the figure for that exact pattern, and a telescopic vent through a cavity gives back less again. Count what is there, then check each one is clear: raised patios, decking, rendered plinths and flower beds bury airbricks by the thousand, and a buried airbrick still reads as an airbrick on a survey sketch.

There is a second reason not to close them, and it has nothing to do with timber. Where radon protection has been designed around a ventilated sub-floor void, the airbricks are the sump and stack, and BRE Report BR 211, Radon: Guidance on protective measures for new buildings, is the document that put them there. Before restricting under-floor ventilation anywhere, establish whether the property sits in an affected area — that changes the job from a comfort improvement into a health one.

What sits between the carpet and the dirt

A suspended timber ground floor in section, from the walking surface down: floorboards, a warm-side vapour control layer, insulation held between the joists, the joists themselves on their plate, the membrane or netting slung underneath to carry the insulation, and the cross-ventilated void over bare oversite.
  1. Floorboards — the walking surface and, once the gaps between shrunken boards are closed, a large part of the air barrier as well
  2. Warm-side vapour control layer — laid over the joists and lapped up at the perimeter, so indoor moisture cannot reach the cold face of the insulation Vapor Barrier Calculator
  3. Insulation between the joists — cut oversize to friction fit each bay, held tight to the underside of the boards with no air gap above it Mineral Wool Insulation Batt Calculator
  4. Joists, plate and sleeper wall — the structure and, at roughly one part in eight of the floor area, an unavoidable repeating thermal bridge through it Ceiling Joist Spanning Lineal Lumber Aggregator
  5. Support membrane or netting — the sling that carries the insulation for the life of the floor; vapour open, so the void can still dry the assembly from below
  6. Cross-ventilated void over oversite — the drying mechanism the whole floor depends on, fed by airbricks on opposing elevations and never to be sealed

Surveying a Floor Nobody Set Out

Modern joists are laid to a spacing because a span table and a sheet material both demand it. A Victorian floor was laid to whatever the carpenter had on the cart. Expect nominal four hundred centres and find three hundred and eighty at one end, four hundred and forty at the other, a doubled pair where a partition used to stand, and one bay half its neighbours' width against the chimney breast. Each is a different cut, and a quantity worked from one assumed spacing is short in the direction that matters.

Do the take-off in two passes. The first is arithmetic: room length, joist span, nominal spacing, and out comes a baseline joist count and the lineal run of timber that the netting, the battens and the perimeter tape all follow. The second is a tape in every bay, recorded on a sketch, with the odd ones circled. The first pass tells you what to order; the second tells you how much of it will be cut waste, and on a period floor that difference is not a rounding error.

Run the room's length, the joist span and the nominal centres to get the baseline joist count and the total lineal timber — the number the netting, the counter-battens and the perimeter sealing all key off, before you go bay by bay and correct it.

Total ceiling joist lumber needed

507 ft155 m

Number of joists
26
Whole bays between joists
24

Deciding What Number You Are Aiming At

Two regimes describe the same floor from opposite ends, and it is worth being explicit about which one the specification is written in. British and European practice states a target as a maximum U-value in W/m²K, calculated to BS EN ISO 6946, Building components and building elements — Thermal resistance and thermal transmittance — Calculation methods. North American practice states a minimum R-value, and insulation is labelled that way at the merchant. They are exact reciprocals of each other within a unit system, and they are not interchangeable across unit systems: a metric U in W/m²K and an imperial U in BTU/hr·ft²·°F differ by a factor near 5.68, which is quite large enough to make a wrong answer look plausible.

Where the target comes from depends on why the work is happening. Approved Document L, Conservation of fuel and power, sets limiting standards for thermal elements being renovated as well as for new ones, and a ground floor being taken up is squarely in that territory — subject to what is technically and functionally feasible, which is exactly the argument a two hundred millimetre joist and a fixed threshold height forces you to have. The International Energy Conservation Code sets floor insulation minima by climate zone for floors over unconditioned space. Neither is a number to carry in your head between jobs; both are confirmed against the edition the jurisdiction has adopted, local amendments included.

One provision is worth quoting in spirit because it kills more floor insulation jobs than any thermal figure: the IECC requires floor insulation to be installed so that it maintains permanent contact with the underside of the subfloor. Insulation drooping in a sling with a thirty millimetre gap above it has an air layer on its warm side, and that air layer will convect. The declared performance was measured on a specimen in full contact — to ASTM C518, Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus — and nothing about a sagging batt resembles that specimen.

Which document sets the target, and what it actually constrains
DocumentStates the target asWhat it will not settle for you
Approved Document L (England)Maximum U-value for a renovated thermal elementWhether your joist depth makes that value feasible on this floor
International Energy Conservation CodeMinimum R-value by climate zone, floors over unconditioned spaceWhich edition and amendments the jurisdiction has adopted
BS EN ISO 6946The calculation method, not a valueThe declared conductivity of the product you buy
Approved Document C / IRC under-floor ventilationVentilation openings that must survive the workWhether existing airbricks are clear, or buried behind a patio
BS 5250Where the vapour control belongs in the build-upThe interstitial risk of your particular layer order
Which document sets the target, and what it actually constrains

When the specification arrives as a U-value and the product on the shelf is labelled in R, invert it once — and only once, at the end, after the layers have been added up. The field takes the imperial U in BTU/hr·ft²·°F, so a W/m²K figure lifted off a regulation has to be divided by 5.678 before it goes in; put the metric number in raw and the R that comes back is about five times too flattering.

Equivalent R-value

20 hr·ft²·°F/BTU

Adding the Layers Back Up

Resistances add along the path heat takes; transmittances do not. Total every layer of the assembly first — deck, insulation, any board under the joists, and the surface air films at each face — and take the reciprocal at the very end. Summing the U-values of individual layers is the error that produces a floor apparently performing several times better than physics allows, and it survives review because each individual number in it is correct.

The honest layer list here is short, and the deck contributes less than people expect. Twenty-two millimetres of softwood is a real but small resistance; the insulation is almost the whole answer; and the ventilated void counts as outdoor air rather than a still cavity, so it earns you nothing. Note which way that cuts at the boundary: BS EN ISO 6946 has you disregard the void and every layer beyond it, then close the assembly with an external surface resistance for still air rather than the low, windswept figure an exposed wall is given. The void is ventilated, not weathered, and a sub-floor U-value quoted with a wall's exposed film on it is pessimistic rather than safe. ASHRAE Handbook—Fundamentals is the reference to defend the film and cavity figures you used, and BS EN ISO 13370, Thermal performance of buildings — Heat transfer via the ground — Calculation methods, is the one that puts the whole suspended ground floor together, void ventilation and ground included, rather than treating it as a wall lying down.

Stack the deck, the insulation and any board beneath the joists into one total and let the air film allowance sit on top of it, so the assembly number you quote is the one the whole build-up earns rather than the one printed on the batt. Keep every layer in imperial R while you do it — the allowance it adds is an imperial figure, and dropping metric RSI values into the same column silently mixes two unit systems in one sum.

R-Value Calculator

Total assembly R-value

15.8 R-value

Sum of material layers
14.95 R
Air film allowance
0.85 R

What Actually Goes Between the Joists

The material choice on a ventilated timber floor is not a free one. Whatever sits between those joists spends every winter with cold, moving, sometimes near-saturated air on one face, and has to tolerate that indefinitely without slumping, without holding water, and without stopping the timber either side of it from drying. Mineral wool — glass or stone — does that: vapour open, non-wicking, and forgiving enough to friction fit a bay nineteen millimetres wider at one end than the other, which is the ordinary condition here.

Specify by declaration rather than by trade name. Factory-made mineral wool products are covered by BS EN 13162, Thermal insulation products for buildings — Factory made mineral wool (MW) products — Specification, and in North America by ASTM C665, Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing. The declared thermal conductivity is on the label and it varies meaningfully between product lines at the same nominal thickness, so the R or lambda you design with should be lifted from the declaration of the product being delivered, not from a generic table.

Density and format matter more here than in a wall. A semi-rigid slab holds its own shape in a bay and can be cut ten to fifteen millimetres oversize to grip on both sides; a soft roll of the same conductivity will sag out of a wide bay within a season unless the support underneath is genuinely continuous. Slabs also handle the awkward geometry better — around a sleeper wall, past a doubled joist, into the tapering bay at the chimney breast — because you can trim them square and they stay square.

ASTM C1320, Standard Practice for Installation of Mineral Fiber Batt and Blanket Thermal Insulation for Light Frame Construction, is worth following even where nothing enforces it: fill the cavity completely, no compression at the edges, no voids at the ends of the bay, and cuts made around obstructions rather than the obstruction buried. A batt tucked past a pipe instead of split around it leaves a gap either side, and gaps scale badly — a few percent of a floor left uninsulated costs far more than a few percent of the performance.

Build it up, layer by layer

Once the bay areas are measured, turn them into sealed packages at the coverage your chosen product's data sheet actually states, because coverage per pack moves with thickness and product line rather than staying constant across the brand.

Mineral wool packages needed

10 packages

The Rigid Board Route, and What It Costs You

Where joist depth is the binding constraint — a shallow floor, a threshold that cannot move, a client who will not accept a step at the door — rigid polyisocyanurate does more with less depth than anything else you can push into a bay. Products to BS EN 13165, Thermal insulation products for buildings — Factory made rigid polyurethane foam (PU) products — Specification, declare conductivities well below what mineral wool reaches, and on a floor with a hundred and fifty millimetres to play with that difference can be the whole argument.

The catch is that rigid board only performs when it fits, and nothing in a period floor fits. Every bay is a different width, every cut has to be within a millimetre or two, and the honest fix for the gap you cannot avoid is foam or tape at every edge of every board, on a floor that may hold two hundred board edges. That is slow work, and slow work gets skipped in the middle of a room nobody will see. A three millimetre air path around a board convects, and unlike a compressed batt it does not announce itself by looking wrong.

The other consequence is moisture. Foil-faced PIR is close to vapour closed on both faces, so it becomes the vapour control layer whether you designed it that way or not, and the timber either side of it now dries in one direction only. That is workable — it is how thousands of floors are built — but it has to be a decision, with the seal deliberately on the warm side and the cold side left able to breathe, rather than something you discover afterwards. Rigid board also needs mechanical support: battens fixed to the joist sides at a set-down that puts the board's top face hard against the underside of the deck, never friction alone.

Convert the field area into whole boards at the sheet size your merchant actually stocks — the North American 4x8 ft board and the metric 2400x1200 mm board are not the same area, so the count genuinely differs by market.

Foam board sheets needed

15 sheets (4x8 ft)

Area to cover (with waste)
473 sq ft43.94 m²

Holding It All Up for Forty Years

The support system is the part of this job that decides whether the floor is still insulated in 2066. Insulation between joists is fighting gravity for its whole service life, with no plasterboard beneath it and no one ever looking. Netting stapled up in a continuous run, or a vapour-open membrane draped over the joists to form a sling in each bay before the insulation drops in, are the two methods that survive; loose offcuts of batten pushed in at intervals are the method that does not.

Work from above where the boards are coming up anyway, because the sling method needs top access: the membrane goes over the joists, is pushed down into each bay to form a hammock, takes the insulation, and the deck goes back over the lot. Work from below only if the void is genuinely crawlable and you accept every fixing overhead — a sub-floor void may meet the definition of a confined space, and that risk assessment is not a formality.

  1. Clear the void of builders' rubble, old lath and offcuts before anything goes in; buried debris bridges the oversite to the timber.
  2. Confirm every airbrick is open and unobstructed, inside and out, and note any that have been buried by later ground works.
  3. Check joists, plate and joist ends with a probe and a moisture meter, and stop the job if you find active decay rather than insulating over it.
  4. Drape the support membrane or fix the netting bay by bay, leaving enough slack that the insulation sits against the deck rather than pulling the sling flat.
  5. Cut each batt to the measured bay width plus a grip allowance, and fit it hard up to the underside of the boards.
  6. Split, do not compress, around pipes, cables and noggins, so the material closes behind the obstruction.
  7. Lay the warm-side vapour control layer over the joists, lap and tape the seams, and turn it up at the perimeter before the boards go back.

The Perimeter Band Where the Heat Leaves

The edge of the floor loses heat out of proportion to its area and is the part most often left out of the take-off entirely. Where a rim board or perimeter joist exists — standard in North American framing and in newer suspended floors here — it is a continuous band the height of the joist running the full perimeter of the building, quantified as perimeter multiplied by joist depth rather than as part of the field.

In construction with a rim board, that band takes rigid foam cut to fit and sealed at every edge, and it is a defensible detail because there is a board there to seal against. In a period floor with joist ends built into solid brickwork, it is not. Those joist ends rely on air movement in the pocket around them to shed the moisture that comes through the wall, and foaming them in trades a small thermal gain for a rot mechanism you cannot inspect. Insulate up to the bearing and stop; leave the pocket ventilated.

The same restraint applies to the sleeper walls in the middle of the floor. They are honeycomb — laid with deliberate gaps — for the sole purpose of letting air cross the void from one elevation to the other. Packing insulation into those gaps to tidy up the edge of a bay closes the cross-flow at the exact point the whole ventilation strategy depends on, and it is invisible from the moment the boards go down.

Where the floor does have a rim board, take the perimeter and the joist depth and get the band's own sheet count, since this is the strip that gets forgotten and then bought in ones and twos at retail price.

Foam board sheets needed

4 sheets (4x8 ft)

Rim joist band area
100.21 sq ft9.31 m²

Which Face the Moisture Sees

The layer order is settled by one fact: in a heating climate the vapour drive runs outward, from the warm room towards the cold void, for most of the year. Vapour control therefore belongs on the warm side, above the insulation and immediately under the deck, and the cold side stays open so anything that does get through can leave. Reverse them and you have built a moisture trap onto the underside of the floorboards. BS 5250, Management of moisture in buildings — Code of practice, is the document to argue from here; the vapor retarder class provisions of the International Residential Code do the equivalent work in North America, with classes defined by permeance measured to ASTM E96/E96M, Standard Test Methods for Water Vapor Transmission of Materials.

Permeance is the number to specify by and the number nobody checks. A polyethylene sheet, an intelligent membrane and a coated building paper are three very different materials that all look like a roll on a pallet, and only the declared permeance separates them. On the cold side the sling must be vapour open — breather membrane or netting, never a second sheet of poly, which sandwiches the insulation between two barriers and leaves condensate nowhere to go.

The oversite is worth a sheet in its own right on a floor where the ground is visibly damp or the void smells of earth. A membrane laid across the soil, lapped and dressed up to the sleeper walls, cuts the vapour load reaching the timber at source, and unlike blocking the airbricks it reduces the moisture without removing the mechanism that deals with the rest. It is also the change that makes the biggest difference to how the void reads on a return visit two winters later.

Rolls are the unit these come in, and the wastage is in the laps rather than the cuts. A generous overlap at every seam, taped rather than spot-fixed, is what turns a set of sheets into a layer — and the roll count has to allow for it before the van is loaded.

Convert the floor area — or the oversite area, if you are covering the ground as well — into whole rolls with the seam overlap already allowed for, so the seams are generous by plan rather than mean by the end of the room. It counts the standard six-mil polythene roll; an intelligent membrane or a breather for the sling comes on a narrower, shorter roll, so re-run that count against the roll size on your own delivery note.

Vapor barrier rolls needed

2 rolls

Area to cover (with overlap allowance)
1,188 sq ft110.37 m²

Ordering for a Floor Where No Two Bays Match

A wall take-off can run on a nominal bay width because the framing was set out to one. This floor cannot, and the waste allowance is where that difference gets priced. Ten percent is the habitual number and it is roughly right for a plain rectangular room with regular joists; it is optimistic the moment the room has a chimney breast, a bay window, a hearth, a doubled joist under a former partition, or a run of pipework crossing three bays at an angle.

Take off the field area of the room, apply a waste factor chosen from what the sketch shows rather than from habit, then add the awkward areas as their own small quantities. Under-ordering costs a second delivery and a lost morning; over-ordering by one pack costs the price of one pack, and mineral wool stores dry in a garage indefinitely. The asymmetry is not close.

What pushes the waste allowance up on a period floor
Condition on the sketchEffect on cut wasteWhere the offcuts go
Regular joists, plain rectangleHabitual allowance is about rightEnd trims only, mostly reusable
Spacing wandering across the roomEvery bay a bespoke widthOne-sided trims, rarely fit the next bay
Chimney breast or bay windowTapering and short baysSmall pieces, high proportion scrapped
Doubled joists under a removed partitionTwo narrow bays where one wide one was assumedLong thin strips, usually usable
Pipe runs crossing bays diagonallySplitting rather than notching the battTwo halves per crossing, both used
What pushes the waste allowance up on a period floor

Take the room's length and width, the coverage printed on the pack you are actually buying, and a waste factor set by the sketch rather than by habit — this is the whole-floor number the merchant order goes in against.

Estimated insulation batt needed

12 packages

Area to insulate
1,014 sq ft94.2 m²
Area with waste factor
1,115.4 sq ft103.62 m²

Everything Already Living in the Void

A sub-floor void is where a century of services ended up. Water pipes run through it, waste pipes cross it, gas may run in it, and cables have been dropped through it by every trade that has worked in the house. Insulating the floor makes that void colder than it has ever been, because the heat leaking through the boards was the only thing keeping it above the outside temperature on a still January night.

Water pipes therefore move or get lagged, and the choice is not a toss-up: a pipe relocated to sit above the insulation, in the warm, is protected permanently, while a lagged pipe below it is protected only as well as the lagging was fitted at the awkward bend nobody could reach. Anything left below the line gets continuous insulation with no gaps at fittings, and the stop tap and the rising main deserve particular attention because they are usually at the coldest, most ventilated corner of the void.

Cables are the other one, and they are a regulatory matter rather than a preference. Conductors surrounded by thermal insulation carry less current safely, and both BS 7671, Requirements for Electrical Installations (IET Wiring Regulations), and NFPA 70, National Electrical Code, set out how ampacity is derated for that condition. Burying an existing cable in a batt without checking what it feeds is how a floor job creates an electrical defect. Where the cable is clipped to a joist and cannot move, notch nothing and consult the electrician — the limits on notches and holes in floor joists come from Approved Document A and the TRADA span tables in the UK, and from the cutting and notching provisions of the International Residential Code in North America.

Putting the Floor Back So It Stops the Draught

The insulation deals with conduction. The draught the client complained about is dealt with when the boards go down, and it deserves to be its own operation rather than tidying up. The vapour control layer, lapped, taped and turned up behind the skirting, is doing double duty as the air barrier — which is why the perimeter detail matters more than the seams mid-room. Nearly all remaining leakage on a reinstated floor is at the wall junction, the hearth and pipe penetrations, not through the field.

Refix rather than renail. Screws pull the boards onto joists that are no longer flat and hold them there through the shrinkage cycle; nails work loose and give you the squeak the client rings about in March. Number the boards as they come up, keep them in order, and put the least presentable ones back under where the furniture stands. If the square-edge boards have shrunk far enough that the gaps are themselves the draught, closing them — with slivers, with a filler strip, or by cramping the whole floor tighter — is a separate decision with its own cost, and it belongs before the insulation goes in rather than after the client has paid for a floor that is warmer and still whistles.

How this job fails, and how the failure presents on the return visit
What was doneMechanismWhat the client reports
Airbricks blocked to stop the draughtVoid loses its drying path; timber moisture content climbs and stays upMusty smell, then springy boards near an external wall, two or three years on
Insulation slung with a gap above itAir layer on the warm face convects around the insulationFloor still cold; measured improvement far below the quote
Poly sheet used both above and belowInsulation sandwiched between barriers, no drying directionDamp insulation found whenever a board is next lifted
Rigid board cut short and not sealedContinuous air bypass around every board edgeCold patches that track the joist lines, worst in wind
Existing cable buried in a battAmpacity derating ignored for a circuit already loadedFound at the next inspection, not by the occupant
Boards renailed rather than screwedFixings work loose over the first shrinkage cycleSqueaking within a season, on a floor that is otherwise fine
How this job fails, and how the failure presents on the return visit

Try the calculation

Ordering a floor take-off bay by bay

Quantify in the order the layers go in, from the sling upward, so the two items that get bought twice — perimeter board and vapour control roll — are counted before the delivery rather than after it.

  • Joist count and lineal timber — Baseline from length, span and nominal centres, then corrected against a tape in every bay; the lineal figure is what netting, battens and perimeter tape all follow.
  • Insulation for the field, by pack — Field area against the coverage printed on the pack being bought, with the waste factor set by what the sketch shows rather than by the habitual ten percent.
  • Support membrane or netting — Continuous over the whole floor with slack allowed for the sling; vapour open, and never a second sheet of the warm-side material.
  • Warm-side vapour control, by roll — Floor area plus generous seam laps, plus the perimeter upstand behind the skirting — the lap allowance is the part that runs out first.
  • Perimeter band, where a rim board exists — Perimeter multiplied by joist depth, taken as its own quantity; stop at built-in joist ends in solid masonry and leave those pockets ventilated.
  • Oversite membrane, where the ground is damp — Ground area under the whole footprint, lapped and dressed up to the sleeper walls; it reduces the vapour load without touching the ventilation.
Open this as a workspace →

Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.

Drawn from

  • Approved Document C, The Building Regulations 2010 (England) — Site preparation and resistance to contaminants and moisture: ventilated air space beneath suspended timber ground floors
  • Approved Document L, The Building Regulations 2010 (England) — Conservation of fuel and power: limiting standards for renovated thermal elements
  • Approved Document A, The Building Regulations 2010 (England) — Structure: notching and drilling of floor joists
  • International Residential Code — under-floor space ventilation, vapor retarder classes, and cutting and notching of floor framing
  • International Energy Conservation Code — floor insulation by climate zone, and the requirement for permanent contact with the underside of the subfloor
  • BS 5250, Management of moisture in buildings — Code of practice
  • BS EN ISO 6946, Building components and building elements — Thermal resistance and thermal transmittance — Calculation methods
  • BS EN ISO 13370, Thermal performance of buildings — Heat transfer via the ground — Calculation methods
  • BS EN 13162, Thermal insulation products for buildings — Factory made mineral wool (MW) products — Specification
  • BS EN 13165, Thermal insulation products for buildings — Factory made rigid polyurethane foam (PU) products — Specification
  • ASTM C665, Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing
  • ASTM C1320, Standard Practice for Installation of Mineral Fiber Batt and Blanket Thermal Insulation for Light Frame Construction
  • ASTM C518, Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus
  • ASTM E96/E96M, Standard Test Methods for Water Vapor Transmission of Materials
  • ASHRAE Handbook—Fundamentals — surface film and air cavity thermal resistances
  • BS 7671, Requirements for Electrical Installations (IET Wiring Regulations) — derating of conductors surrounded by thermal insulation
  • NFPA 70, National Electrical Code — conductor ampacity adjustment
  • BRE Report BR 211, Radon: Guidance on protective measures for new buildings
  • Confined Spaces Regulations 1997 — HSE Approved Code of Practice L101, Safe work in confined spaces
  • TRADA, Span Tables for Solid Timber Members in Floors, Ceilings and Roofs for Dwellings
  • Historic England, Energy Efficiency and Historic Buildings: Insulating Suspended Timber Floors

Guidance, not a specification. Local codes, the engineer of record and the product manufacturer’s instructions govern where they differ from anything written here.