Reading the Water Before Anything Comes Off
Walk the roof two days after a soaking rain, not the morning of. Water still standing forty-eight hours after precipitation stops is what the trade calls ponding; anything that clears by mid-morning is drainage working slowly, which is a different and cheaper problem. Chalk the outline of each pond while it is still wet. The silt and algae ring left behind once it dries reads fainter than the real thing and it lies — wind pushes the scum line out past the true edge, and you will price twenty percent more taper than the roof needs.
Depth governs the remedy more than area does. Lay a straightedge across each pond at its widest and measure down at the centre; that dimension is what a taper design has to overcome, on top of whatever slope the finished roof is required to hold. An inch of water spread over twenty feet and three inches held in eight feet look identical on a plan view and cost nothing alike.
Note what each pond sits on. Standing water over a steel deck bay tells one story, over structural concrete another, over lightweight insulating concrete a third. Cut a core through the worst pond and a second through dry field for comparison. Insulation that weeps when squeezed has lost its R-value and its compressive strength both, and it will not carry tapered board — anything laid over it telegraphs every fastener within a season.
The Dead Field Between Drains
Between drains, a level deck has no reason to move water in any direction at all. Slope has to be manufactured, and tapered insulation is how most low-slope roofs manufacture it. Panels come in per-foot slopes — an eighth, a quarter and a half inch per foot being the usual increments — and the arithmetic that matters on a ladder is thickness equals slope times run. Quarter-inch panels carried twenty-four feet from a ridge arrive six inches thicker than where they started. Those six inches have to be absorbed somewhere, and each one is a separate decision at the parapet, at every curb, and at the roof hatch.
Drain spacing sets the run, but the diagonal sets the failure. Two drains sixty feet apart on the same low line give thirty feet of run from the ridge between them — and the field corner farthest from either drain is running considerably longer than that. A section drawing that works fails at the corner unless the layout carries proper hips and valleys cut from the same slope, sump to sump.
Slope is also a code question, not only a drainage one. The model building code sets a quarter inch per foot as the minimum for most low-slope membrane roofs, with a narrower allowance for coal-tar systems, and the amendments adopted in your jurisdiction govern the number you actually have to meet. A re-roof frequently triggers a slope requirement the original roof was never held to; confirm it before pricing an eighth-inch system on an existing deck.
Polyisocyanurate board itself is specified under ASTM C1289 'Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board', which is worth quoting on the submittal alongside the taper layout — the slope drawing and the board specification are two halves of the same order.
The build-up that manufactures a slope
- Single-ply membrane — roll direction is settled once, at layout, and it decides how many rolls come off the truck and which seams end up sitting in water EPDM Single-Ply Roofing Roll Calculator
- Cover board — the substrate the membrane is bonded or fastened to, and what stops foot traffic and hail printing every board joint beneath it Roof Insulation Cover Board Calculator
- Tapered panels — thickness equals slope times run, so every inch gained at the high point is an inch taken out of the flashing height at the parapet Tapered Roof Insulation Slope Calculator
- Flat base board — carries the thermal duty and lifts the taper to where it needs to start; cheaper per inch than tapered stock and worth using for all the depth it can Foam Board Insulation Calculator
- Structural deck — sets what can be fastened and how much added dead load is available; a pond sitting mid-bay rather than in a low corner is pointing at this layer Roof/Floor Deflection Limit Calculator
Slope, run and finished thickness resolve into one number here, and that number is what decides whether the perimeter details you are about to inherit still work.
The horizontal distance from the roof's high point to the drain or low point.
The target drainage slope, expressed as a ratio (rise ÷ run).
The thinnest board in the system, laid AT the drain or scupper — the taper builds up from here.
The board's width measured along the run, which is the direction the taper climbs.
The thickest board in the tapered range, where the sequence has to restart.
Maximum insulation thickness needed
11.36 in
- Thickness rise across the run
- 9.36 in
- Board courses from the drain to the high point
- 10
- Rise across one board
- 0.96 in
- Width of the last course
- 36 in
- Courses before the taper restarts on fill
- 2
- Flat fill under the high end
- 7.36 in
They open the calculator with your figures already in it
Tapered Roof Insulation Slope Calculator: 11.36 in — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 11.36 in — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- Gives thickness, not R-value, and the thin end is where the energy code bites. The starter board at the drain is the lowest R anywhere in the assembly, so check the required minimum against that thinnest point — and against the assembly average if your code path allows one — before ordering, because raising the starter thickness raises every board above it and the whole build-up with it.
- Solves one straight fall and leaves the water between the drains. Areas behind curbs, between adjacent drains and along the high line need crickets and saddles, and because a cricket falls diagonally its own slope has to be steeper than the field — commonly double it. A roof tapered only in the direction calculated here ponds in every one of those corners.
- The last course is ripped to whatever the run has left, and a ripped tapered board carries only its own share of the rise — so the board against the high point is not the thickest board in the range, even though it sits at the thickest place. Where the rip lands is a decision the page does not make: put it at the high point and the cut edge is buried under the flashing, put it at the drain and it is under the sump, and the two are not the same job.
- The board rows assume one tapered range at exactly the slope you asked for, laid in full-width courses from the drain outwards. Real schedules are lettered sets with their own fixed slopes, and the nearest one to your target is what gets delivered — so a 1 in (25 mm) 50 target is normally built with 1/4-in-per-foot board, which is 1 in (25 mm) 48, and the finished fall is the board's, not yours. Take the courses and the fill as the shape of the system rather than as an order.
- Nothing here checks that the total fits what surrounds it, and on a deep build-up that is the constraint that bites first: flashing height at the parapet, door sills, curb heights and the depth of the drain bowl itself. A roof that needs more fill than the upstand allows is re-drained or re-divided rather than re-tapered, and that decision sits upstream of every figure on this page.
The Drain That Sits Proud of Its Own Sump
Water can reach a drain and still not leave. A drain body set level with the structural deck disappears under three inches of insulation and membrane, and what you have built is a bowl with a plug in the rim. Sumps fix this three ways: dropping the deck at the drain, cutting the insulation back and infilling with tapered edge strip, or setting a prefabricated sump pan.
Size the sump off the clamping ring, not by eye. The pan needs flat bearing all round the ring so the membrane lies down, clamps and stays clamped. Crowd the bolts with taper and the ring will not pull even; oversize the pan and you have built a fresh pond with a hole in the middle of it. The drain sump pan sizing calculator linked below works this against ring diameter and the surrounding taper.
Torque clamping rings in a cross pattern and come back to them once the membrane has relaxed. A ring pulled hard on one side lifts the sheet on the other, and that leak surfaces in the ceiling below at a point nowhere near the drain. Leave strainer domes fitted and tell the building what they are for — one plastic bag across an unstrained drain does in an afternoon what a decade of settlement could not.
ANSI/SPRI RD-1 'Design Standard for Roof Drainage' and the plumbing code adopted locally between them set how many drains the roof needs and how big they are. Drain count is not a detail you get to adjust on site to suit a taper layout; the taper layout adjusts to the drains.
Pan area follows the pipe and the clearance the ring needs around it, and that single dimension is the difference between a sump and a fresh pond with a hole in the middle.
The outside diameter of the roof drain pipe.
The clearance required on all sides between the pipe and the sump pan edge.
Required sump pan area
1.396 sq ft
- Pan diameter
- 16 in
They open the calculator with your figures already in it
Roof Drain Sump Pan Sizing Calculator: 1.4 sq ft — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
What this calculation does not cover
- Sizes the pan and says nothing about getting water to it. A sump drains only what reaches it, which means the insulation around it has to be tapered down into the pan and crickets have to run between drains and behind any curb up-slope of one. On a dead-flat deck this pan is simply the lowest 0.13 m² (1.4 sq ft) of a field that ponds everywhere else.
- Takes clearance as a hydraulic figure when it is usually a hardware one. The width around the pipe is driven by the drain body's clamping ring diameter and by the membrane lap needed outboard of it to make the flashing — check the drain manufacturer's ring dimension before this number, because a pan that does not clear the ring cannot be sealed to the membrane at all.
- Cutting the recess is a structural decision. The opening has to fall clear of the joists, purlins or deck flutes underneath, or the deck needs framing around it — and a drain landing on the centreline of a structural member cannot be sumped where the drawing puts it, whatever plan area this returns.
Upslope of Every Curb
Anything standing across the flow line is a dam. A four-foot mechanical curb set square to the slope collects water on its upslope face and holds it hard against base flashing — the single detail on the roof where the membrane is turned up and terminated at a fastened edge. Crickets and saddles behind curbs are not decorative detailing; they are the only thing keeping a permanent pond off a termination.
Build crickets steeper than the field. Doubling field slope is common — half-inch crickets in a quarter-inch field — because the run is short and the water arriving there has already lost its head. Width has to cover the obstruction plus enough beyond each corner to carry water clear, and the cricket must die out into the field cleanly. A cricket that stops at a step has simply moved the dam three feet upslope.
Clusters of small penetrations do more damage than single large ones. Pipe stands, gas line supports and conduit racks set in rows across the flow line make dozens of little obstructions, and the leaf litter collecting between them completes the job. Run supports along the slope where the mechanical layout allows, keep them off the low line entirely, and use individual sleepers rather than continuous rails bedded flat on the membrane.
Base flashing wraps the whole curb, not the upslope face the cricket protects, so the material comes off the perimeter of every unit standing on this roof.
SettingsSettings for this calculation
Waste is set to 8% by hand. Pick a tier above to replace it, or keep your own figure.
The full perimeter of the rooftop unit curb.
Extra material to allow for corner cuts, overlaps, and offcuts.
Curb flashing needed
28.08 ft
Curb flashing is measured on the curb's perimeter, but its performance depends on the curb's height above the finished roof surface and on whether the upslope side sheds water around the curb rather than into it.
They open the calculator with your figures already in it
Rooftop Unit Curb Flashing Calculator: 28.08 ft — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- Excludes the cricket or saddle needed on the upslope side of any wide curb, which is a fabricated item sized from the curb width and the roof slope.
- Corner pieces are fabricated units rather than cut from a run and are priced individually.
- Does not verify curb height. A curb too low for the covering system leaves nowhere for the upstand to terminate above standing water.
The Parapet, the Scupper and the Height Budget
Every inch added at the high point is taken out of the vertical dimension available at the perimeter. Base flashing must terminate above the highest level water will ever stand, and the flashing height that was adequate on the old roof is now short by exactly the thickness of the new build-up. Door thresholds, hatch curbs, window sills, louvre bottoms and through-wall scuppers all reset against the new surface, and any one of them can be the item that forces a lower slope than you wanted.
Secondary drainage is a code requirement, not a courtesy. Overflow drains or scuppers set above the primary drainage level are mandated by the adopted plumbing and building codes, and their invert height governs two things at once: the depth of water the structure has to be designed to carry, and the height your flashing has to reach. Raise the roof surface without raising the scupper inverts and you have converted the design head into permanent standing water.
At the edge itself, ANSI/SPRI ES-1 'Wind Design Standard for Edge Systems Used with Low Slope Roofing Systems' governs fascia and coping. A thicker roof means a taller fascia face, and a taller face changes what the tested assembly requires of the continuous cleat. Existing edge metal does not get re-used over a thickened roof, however sound it looks from the ground.
Opening area comes off tributary area and the local rainfall figure, and since the invert of that opening caps the whole height budget, the two are worth settling in one sitting.
The roof area draining to this scupper or secondary drain.
The opening area required per unit of roof area, set by local design rainfall intensity and code drainage tables.
Required scupper opening area
77.4 in²
The sizing factor depends on your local design rainfall intensity and applicable plumbing code roof drainage table (e.g. IPC) — confirm the correct factor for your jurisdiction and roof drainage design (primary vs. secondary/emergency) before sizing scuppers.
They open the calculator with your figures already in it
Roof Scupper/Secondary Emergency Drain Sizing Calculator: 77.4 in² — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 77.4 in² — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- Returns an AREA, and a scupper is not sized by area alone. It spills as a weir, so what it passes depends on how WIDE the opening is and how deep the water stands above its invert, with flow climbing as roughly the 1.5 power of that depth. A tall narrow slot and a wide low one of the same area are not interchangeable — the wide one drains the roof, the narrow one needs far deeper standing water before it moves the same flow.
- Says nothing about how high to set the invert, and that is the number deciding how much water the structure has to hold. An overflow set high leaves a deeper layer standing over the whole tributary area before it spills, and that depth is a real load on deck and framing that has to be checked for ponding — an opening area cannot fix it.
Laps That Spend Their Lives Underwater
A seam sitting in the bottom of a pond lives a different life to the same seam on a crown. Correctly made EPDM and thermoplastic seams are watertight under standing water — that is the design intent, and ASTM D4637/D4637M 'Standard Specification for EPDM Sheet Used in Single-Ply Roof Membrane' and ASTM D6878 'Standard Specification for Thermoplastic Polyolefin Based Sheet Roofing' cover the sheet itself. What standing water removes is margin. Contamination, a cold-weather bond, a fishmouth at a T-joint: any of them survives on a crown and none of them survives submerged.
Lay the sheet so field seams run with the slope toward the drains. Seams crossing the flow line sit in water by definition; a seam laid down the middle of a valley sits in water permanently. Roll direction is settled once, at layout, and everything downstream follows from it — how many rolls come off the truck, where field seams land relative to the ponds you chalked, and how many linear feet of tape or adhesive those seams add up to.
Sheet width and roof geometry drive roll count harder than square footage does. A rectangular field with clean edges wastes little; the same area broken by six curbs, two skylights and a stepped parapet eats sheet in ways an area figure never shows. Price the offcut, and price the seam length that comes with it — the seam adhesive and tape calculator linked below turns a layout into linear feet.
Cold weather is the other variable that decides whether a submerged lap holds. Cleaner flash-off slows, primer sets differently, and roller pressure that is adequate at seventy degrees is not adequate at forty. Manufacturers publish minimum application temperatures for a reason, and the seams that fail first are almost always the last ones made on the coldest afternoon of the job.
Roll direction and count are committed before a single lap goes down, so the sheet gets worked out against the roof's real geometry at exactly this moment rather than against a bare area figure.
The total roof area to be covered with EPDM membrane.
The area a single roll of EPDM membrane covers.
EPDM rolls needed
5 rolls
They open the calculator with your figures already in it
EPDM Single-Ply Roofing Roll Calculator: 5 rolls — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- The same roll count buys any thickness. EPDM is stocked at 45, 60 and 90 mil, reinforced and unreinforced, and thickness is what the warranty term and the hail and foot-traffic tolerance key off. The area arithmetic is identical for all of them, so this figure cannot tell you the wrong sheet came off the truck.
- Says nothing about what holds it down. Fully adhered, mechanically attached and ballasted roofs need different quantities of bonding adhesive, plates and fasteners or ballast, and that density rises sharply in the perimeter and corner zones set by wind uplift on the particular building. Those lines are usually the larger part of the order and none of them follow from area.
- Roll width decides how much seam the roof has. Covering the same area in wider sheets roughly halves the length of field seam, and seams are where single-ply roofs leak — entering a bare coverage area hides that trade-off completely.
The Deck That Sinks Under the Pond It Made
Ponding is a load, and a load that deflects a deck opens room for more water, which deflects it further. ASCE 7 'Minimum Design Loads and Associated Criteria for Buildings and Other Structures' addresses rain load and ponding instability directly, and long-span steel joists and open-web systems are the usual candidates for the progressive version of it. A pond sitting mid-bay rather than in a low corner points at the structure, not the insulation.
Weigh the remedy before you order it. Tapered polyiso over a large field is several inches of board at the high point plus flat fill beneath, a recover adds an entire system on top of the one already there, and a ballasted assembly adds more again. Where a deck is already deflecting, a section that adds dead load to solve a drainage problem needs the structural engineer's eyes before the material lands on site.
Deck type also limits what can be done at all. Steel deck takes fasteners and can be re-sloped with board; structural concrete tolerates weight but resists mechanical attachment; lightweight insulating concrete can be re-sloped in fill but has to be dry and sound to hold anything. Establish deck type and condition at the core cuts rather than from the drawings — additions and past re-roofs make liars of record documents.
What the Old Roof Has Already Decided
Recover or tear off is settled by the substrate, not by the budget. Codes generally cap the number of roof coverings permitted on a building, and wet insulation disqualifies a recover regardless of that count — water trapped under a new membrane has nowhere to go and will delaminate the new system from beneath. Two dry existing plies over a sound deck are a recover candidate; a saturated field is not.
Survey the moisture, then verify it by cutting. Infrared and capacitance surveys map suspicion; cores confirm it and tell you the actual assembly thickness, which the tapered design and the fastener schedule both depend on. Take cores in the ponds, in dry field, and near every parapet — perimeter wetting from failed counterflashing is common and reads differently from field saturation.
Recalculate fastener lengths against total finished thickness, not against the boards you are adding. Embedment into steel deck is specified by the assembly's approval, and a plate that penetrates a flute without gripping it holds nothing under uplift. FM Global's data sheet on roof loads and drainage and the manufacturer's own approved assembly govern here; pull tests on the actual deck settle arguments cheaply and early.
What Each Remedy Costs in Build-Up
Turn every drainage fix on the roof into inches at the high point and the job becomes a ledger. A pond in mid-field costs taper across its whole run; a pond behind a curb costs a cricket and nothing else; a pond around a drain may cost nothing at all when the fix is a sump cut down rather than board built up. The cheapest remedies, measured in build-up, are the ones that lower the low points instead of raising the high ones.
Built-up and modified bitumen systems bring their own arithmetic to a tapered field. Base sheet coverage is calculated against net area with laps, and cut-up fields with crickets everywhere generate cap sheet scrap that a flat square-foot figure understates badly — the BUR base sheet and mod bit scrap calculators linked below exist because that gap otherwise turns into a second material order. Torch work near curbs, parapets and any combustible wall carries a fire watch obligation the schedule has to carry too.
Sequence the work so the roof drains every night. Tapered systems are laid from the low point up, which leaves the field at its most vulnerable in the middle of the run; water cut-offs made at the end of each day and stripped the next morning cost far less than one overnight storm into an open deck. Keep temporary drainage clear at the sumps throughout, and never let a stack of board sit across the only flow line the roof still has.
| Remedy | Where it applies | Build-up it costs |
|---|---|---|
| 1/8 in per ft taper, 24 ft run | Shallow fields with a tight height budget | 3 in at the high point, before any flat fill |
| 1/4 in per ft taper, 24 ft run | Meeting a code-minimum slope on a re-roof | 6 in at the high point, before any flat fill |
| 1/2 in per ft cricket, 8 ft run | Behind a curb sitting across the flow line | 4 in at the curb's upslope face |
| Tapered edge strip into a sump | Drain body not recessed into the deck | Removes build-up locally instead of adding it |
| Recover over a sound, dry existing roof | Two coverings or fewer, deck verified | Adds the full thickness of the new system everywhere |
Base sheet is laid to net area plus every lap, and a field broken by crickets spends that lap allowance far faster than a square-foot figure ever admits.
The total roof area to be covered with base sheet.
The usable coverage area per roll after the manufacturer's standard side and end laps.
Extra material to allow for additional side/end laps and trim waste.
Base sheets needed
12 sheets
They open the calculator with your figures already in it
Built-Up Roofing (BUR) Base Sheet Calculator: 12 sheets — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- Felt is the cheaper half of a built-up roof. The plies are bonded with hot asphalt or a cold adhesive at a rate the specification sets for each ply, and that bitumen is usually the larger part of both the weight going up the hoist and the invoice — a sheet count with no mopping quantity behind it leaves the kettle idle and the crew waiting.
- Fastener quantity is not one number across the roof. Where the base sheet is mechanically attached, the uplift design tightens the pattern along the perimeter and tightens it again in the corners, so a field spacing applied to the whole area under-counts fasteners in precisely the two zones where a roof starts to peel.
Taking Off a Low-Slope Re-Roof
Work the take-off in the same order the water does — low points first, then the runs feeding them, then the vertical dimension the whole thing has to fit inside.
- Membrane area with perimeter and corner offsets — Sheet width and roof geometry drive roll count harder than net square footage; count the offsets separately.
- Tapered board schedule by panel slope and run — List longest diagonal run per drain, not just the section run — the corner sets the thickest board.
- One sump assembly per roof drain — Size against the clamping ring, and confirm whether the deck is being dropped or the insulation cut back.
- Cricket or saddle for every obstruction across the flow line — Typically double the field slope; width covers the obstruction plus run-off clearance at both corners.
- Height budget check: flashing, thresholds, scupper inverts — Every item that terminates against the roof surface resets by the full build-up thickness.
- Fastener lengths recalculated on total finished thickness — Embedment comes from the approved assembly; pull test the actual deck before ordering.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.
