Passive fire protection

Hanging a Fire Door to the Gap Tolerances

The inspector arrives with a gap gauge rather than a spirit level, so the millimetres round the leaf, the seal runs and the latch are the whole job.
  • 19 minReading time
  • 10Sections
  • 4Calculators inline
  • Last reviewed

Nine readings, and two of them fail

Forty-one flat entrance doors on a nine-storey block, all replaced two years earlier, all with the plug in the top edge and the paperwork in the file. The quarterly check took a gap gauge round each leaf at nine points — three down each stile, three across the head — and thirty-nine doors came back with at least one reading over. Not one of them was hung badly by any ordinary standard. The margins were even to the eye, every leaf closed sweetly, and the decorator had left them looking better than the day they went in. They failed because on a fire doorset an even margin is not the same thing as a correct margin, and because the number the gauge is being compared against is not a number anybody on the fitting crew had ever read.

That is the whole difference between this work and hanging a door. Everywhere else in joinery the leaf is the adjustable part: you scribe it, plane it, ease the lock stile, hang it twice and let the architrave hide the rest. Here the leaf is the one thing you may not touch beyond a stated allowance measured in single millimetres, because it was tested as part of an assembly and every shaving takes it further from the thing that was tested. So the adjustment has to happen somewhere else, and the only place left is the opening. You build the hole to suit the doorset instead of easing the doorset into the hole.

Everything awkward on site follows from that inversion. The structural opening acquires a maximum as well as a minimum. The void behind the frame is a specified fill rather than whatever foam is on the van. The seals have to be continuous through the hinge positions. And the door has to latch every time, against a closer somebody will later want turned down because a resident finds it heavy. None of it is difficult. All of it is measured afterwards by a person holding a gauge, which is not true of any other door in the building.

What the gauge is actually reading

There are four gaps and they are not one specification. Head and both stiles are commonly quoted as a 3 mm nominal with a millimetre either way, and that pairing is deliberate on both sides: too tight and the leaf binds as timber takes up moisture, or as the intumescent begins to swell and has nowhere to go except against a leaf that then cannot shut; too slack and there is more gap than the seal was tested to bridge, so the fire finds a slot before the seal has closed it. The gap under the leaf behaves differently again, and it varies far more between schedules than the other three, because a doorset with a smoke classification has to close that gap with a drop seal or a brush while a plain fire door without one is generally allowed more.

The operative number is not in a code. BS 8214, Timber-based fire door assemblies — Code of practice, is the document that governs how a timber fire doorset is installed in the UK, and NFPA 80, Standard for Fire Doors and Other Opening Protectives, does the equivalent job in North America, where it states clearances at the top and vertical edges for wood and for steel leaves separately and caps the clearance under the bottom of the door. Read the edition your jurisdiction has actually adopted rather than a figure somebody remembers. Underneath both of them sits the thing that really decides it: the certification schedule and field of application for the specific doorset in front of you, issued by whoever tested it to BS EN 1634-1 or BS 476-22, or to NFPA 252 and UL 10C. Where the schedule and a remembered rule of thumb disagree, the schedule wins and the rule of thumb is what gets you a remedial.

Get that document onto the site before the first frame is fixed, not after the first inspection. It is a page or two, it names the gaps, the seal sizes and positions, the hinge grade, the permitted trim and the permitted ironmongery, and every argument that happens on this job later is settled by it. Crews that have it pinned inside the site cabin door hit the tolerances; crews working from what worked last time do not.

The four gaps round a leaf — what each one is doing and what actually sets the figure you will be measured against — and, on the last row, the clearance behind the frame, which is not a gap round the leaf at all and is governed by a different document again.
GapWhat it is forWhat sets the number
HeadRoom for the leaf to move and for the head seal to expand intoThe doorset's certification schedule; BS 8214 and NFPA 80 give the practice around it
Hinge stileThe same, interrupted at every hinge position, which is where continuity is lostThe schedule, plus whether the hinge blade or an intumescent pad occupies the seal groove
Lock stileThe same again, and the gap the latch has to bridge before it can throwThe schedule, and the latch's own backset and throw
ThresholdClearance over the finished floor, and a smoke path unless something closes itThe schedule and the smoke classification; a drop seal or brush changes it entirely
Frame to structureWorking space to plumb the frame, then a fire-stopped jointThe manufacturer's installation instructions, which state a maximum void and what fills it
The four gaps round a leaf — what each one is doing and what actually sets the figure you will be measured against — and, on the last row, the clearance behind the frame, which is not a gap round the leaf at all and is governed by a different document again.

A timber fire doorset cut through at the jambs

A certified doorset seen in plan through both jambs: architrave lying over the joint on each face, the leaf between the two frame legs, intumescent and smoke seals set in the frame rebate with the measured gap between them and the leaf edge, the frame itself, the packed and sealed void behind it, and the rated wall the opening was cut through.
  1. Architrave over the joint, both faces — covers the perimeter joint on each face and, where the installation instructions call for it, is a component of the tested assembly rather than trim Door & Window Casing Calculator
  2. The leaf, with its lipping — the one part of the assembly that may not be adjusted to suit the opening beyond the trim allowance printed on its schedule
  3. Intumescent and smoke seals in the rebate — swell to close the measured gap long before flame arrives, which is why that gap has a maximum and a minimum rather than a target Weatherstripping Calculator
  4. Frame legs and planted stop — fixed plumb and square without being drawn in by the screws, because a racked frame is a frame whose gap runs out down one stile Fenestration Rough Opening Calculator
  5. Packed and sealed void behind the frame — filled with the material the doorset was tested with, to the depth the instructions name, all the way round rather than in the corners only Acoustic Sealant Bead Volume Calculator
  6. The rated wall the opening was cut in — carries its own certificate, and a doorset fitted to a partition with no evidence behind it is an opening protective in a wall that is not Multi-Layer Fire-Rated (Type X) Gypsum Sheet Calculator

The hole gets a maximum, which is new

On ordinary joinery a generous opening costs a thicker shim stack and nothing else, which is why every rough-opening habit in the trade errs upward. Here it costs you the installation. The void between the back of the frame and the structure has a stated maximum in the manufacturer's instructions — commonly around ten millimetres, though it is theirs to set and it varies with what the void is filled with — because that joint was tested at a width, with a material, to a depth. An opening framed forty millimetres oversize on one side because the studs drifted is not a shimming problem. It is a joint nobody has evidence for.

So the arithmetic runs the other way from habit. Take the frame's outside dimensions from the schedule, add the void the instructions permit at each jamb and at the head, and treat that as a target with a tight band round it rather than a minimum to beat. The out-of-square allowance that a window opening carries as free insurance is exactly the term to drive toward zero here: every millimetre of it lands in the void, and the void is capped. Where the opening is already built and already wrong, the honest fixes are to re-frame the jack studs, to line the reveal in a material the instructions accept, or to order a frame that fits — not to bridge fifty millimetres of nothing with expanding foam and cover it with a wider architrave.

Square matters more than plumb-in-isolation, and the reason is the gauge. Fix a frame that is ten millimetres out of square across its diagonals and the head gap tapers from two to five across the leaf, so one reading passes at the hinge side and the same door fails at the lock side with nothing visibly wrong. Pull both diagonals before the second fixing goes in on each leg, and hold the frame off the structure on packers at every fixing so the screw cannot draw the leg inward — a leg pulled in by three millimetres at the middle fixing is a leaf that binds at mid-height and shows daylight at the top.

  1. Read the frame's outside width and height off the schedule, not off the leaf and not off the old frame.
  2. Add the permitted void at each jamb and at the head, and note it as a band rather than a single figure.
  3. Check the built opening against that band at head, mid-height and floor before the frame leaves the pallet.
  4. Set the hinge leg plumb in both planes on packers at every fixing point, and fix it before the other leg is touched.
  5. Set the head and the second leg to the leaf itself, then pull both diagonals and correct before final fixing.
  6. Offer the leaf up dry, gauge all four gaps, and correct at the frame — never at the leaf — before anything is filled.

Run it with the frame's scheduled outside size, the permitted void as the jamb and head figures, and the out-of-square allowance set to zero: on a certified doorset that allowance is not free insurance, it is void you are not permitted to have.

Overall outside frame width of the window or door unit.

Overall outside frame height of the unit, sill to head.

The clear gap the manufacturer requires at each jamb.

The clear space required above the head of the unit.

Thickness of the pan the unit will sit on at the sill.

Any packer, sloped bevel or sub-sill placed under the pan.

Extra carried for a rough opening that will not be perfectly true.

Rough opening width

35.99 in

High confidence
Rough opening height
48 in
Shim stack at each jamb
0.37 in
Clear space at the head
0.5 in
Build-up under the sill
0.25 in
Rough opening area
12 ft²

Add the equipment this sizes

This result is a specification — 35.99 in — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

2.92 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • The manufacturer's installation instructions govern. Where they state a rough opening directly, use theirs rather than this reconstruction of it.
  • Structural clearance under a header that will deflect, and any allowance for frame shrinkage, are design decisions this sum does not make.

Filling the void with the thing that was tested

The perimeter joint behind the frame is a fire-stopped joint and it is specified like one. What goes in it is named in the installation instructions — a mineral wool packing with a sealant capping, an intumescent mastic, or a tested foam where the instructions actually permit a foam — and the depth matters as much as the material, because a bead run into a joint of the wrong depth-to-width ratio is a bead that will not hold. Two things get this wrong on site with equal frequency: filling the corners and calling it sealed, and using whatever cartridge is in the gun because the right one is on next week's delivery.

It is also a quantity, and on anything bigger than a house it is a quantity people badly underestimate. A single doorset's perimeter is two legs and a head — call it five metres — and the joint is worked from both faces, so the run doubles. Forty doorsets in a corridor block is four hundred metres of joint before anybody has sealed a service penetration, and the volume that consumes depends entirely on the cross-section the instructions call for. Nine millimetres square takes more than twice what six millimetres square takes over the same run, which is the difference between one box on the van and three.

Do the arithmetic once for the standard doorset on the job, multiply by the schedule, and order in one go. Running out at door thirty-three means either a gap left open under an architrave that is already pinned, or a second product introduced halfway down a corridor with no record of which doors got which — and the record is what the whole exercise is for.

The sum is the same one a linear fire-stopped joint takes: run length by bead width by bead depth. Enter the doorset perimeter multiplied by the number of doors and by two for both faces, and take the width and depth from the doorset's installation instructions rather than from the cartridge.

The total length of the perimeter joint being sealed.

The width of the sealant bead as applied.

The depth of the sealant bead as applied.

Acoustic sealant needed

0.2143 gal

High confidence

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

66 ft0.25 in0.25 in
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • The bead is specified here; the GAP is what should be specifying it, and the page never asks. Three millimetres under a board edge takes the default bead and holds. A head track over a bowed slab, or a deflection head built to move, can open 15 or 20 mm (0.79 in) — no bead bridges that, it slumps through and leaves exactly the air path it was meant to close. Anything past about 10 mm (0.39 in) gets packed first, with mineral wool or a closure strip, and sealed second; the volume that follows is a different figure from length x width x depth.
  • What a cartridge actually delivers is set by the nozzle, and the nozzle is cut by hand. One size larger than intended turns a 6 mm (0.24 in) bead into a 9 mm (0.35 in) one — 2.25 times the sealant over the same run, and the usual reason a job estimated to the millimetre runs dry two walls early. Add the dead length the gun cannot reach in each cartridge, and order in whole cartridges above this figure rather than at it.

Seals that stop at the hinge

An intumescent seal works by being continuous. It swells to many times its own volume and closes the gap it sits beside, and a run that is continuous for nine tenths of its length has left a slot at the tenth — which is where the smoke goes, because smoke is looking for exactly that. So the failures worth hunting are all failures of continuity rather than of specification, and they cluster in four places.

The corners are the first. Where a head run meets a stile run the two either butt tight or are mitred, depending on what the schedule shows, and a five-millimetre shortfall at the top of each stile is two holes in the same door. The hinge positions are the second, and they are the ones that catch experienced fitters: on many frames the seal groove runs straight through the hinge recess, and a hinge blade let in over it either interrupts the run or has to be paired with an intumescent hinge pad behind the blade, which is a listed component and not a washer somebody improvises. The third is decoration. A seal painted over four times has a skin on it, and a seal that has been painted, filled and sanded with the architrave has lost the fins on a brush type entirely. The fourth is substitution — a smoke seal swapped for a plain intumescent because the merchant was out, on a doorset whose classification depends on the smoke half.

Smoke is the quieter half of the specification and the half that gets dropped. Ambient-temperature smoke leakage is tested separately under BS EN 1634-3 and classified under BS EN 13501-2, and a doorset carrying that classification has a brush or a fin or a blade seal doing work that the intumescent does not do at all — intumescent is inert until it gets hot, and by the time it has activated the smoke has been moving for several minutes. This is why the threshold gap is a specification question rather than a joinery one: a leaf hung to a generous undercut for return air is a leaf with a smoke path along its whole width, and the answer is a drop seal or a sealed threshold rather than a leaf trimmed to a gap somebody guessed.

Set the seals after the frame is fixed and before the architrave goes on, and gauge the four gaps with the leaf hung and the seals in — not before, because a seal proud of its groove by a millimetre changes every reading you took. Where the schedule puts the seals in the leaf edge rather than the frame, that is where they go; the two are not interchangeable and the tested arrangement is the one on the certificate.

  1. Check the seal size, type and position against the schedule before opening the first pack, including which of the two components carries them.
  2. Run each length full, butted or mitred at the corners exactly as the schedule shows, with no short pieces made up from offcuts.
  3. At every hinge, confirm whether the run continues behind the blade or whether an intumescent hinge pad is specified — and fit the pad if it is.
  4. Keep paint, filler and caulk off the seals entirely, and mask them before the decorator arrives rather than cleaning them afterwards.
  5. Hang the leaf, gauge all four gaps with the seals in place, and photograph the readings while the perimeter joint is still open.

Closing is not the test — latching is

A fire door that closes but does not latch has failed. Not marginally: the leaf is held against the stop by nothing but a spring, and the pressure differential across a door in a fire is more than enough to push it open again. Every certified assembly is tested with the latch engaged, so the latch is a structural part of the thing, and the single commonest defect found on inspection is a door that swings shut, touches the keep and stops a few millimetres short of throwing.

The cause is nearly always the last few degrees of travel. A closer to BS EN 1154 is classed by power size, the schedule names a minimum, and somebody has wound it below that minimum because a resident complained the door was heavy — which reduces the latching action precisely where the door is fighting the latch spring, the smoke seal and whatever air the corridor is moving. Latch and lock cases carry their own route in BS EN 12209, panic and emergency hardware in BS EN 1125 and BS EN 179, and hinges in BS EN 1935; on a certified doorset all of it is named on the schedule and none of it is a like-for-like substitution made at the merchant's counter. Free-swing and hold-open devices to BS EN 1155 are a legitimate answer to the heavy-door complaint where the doorset permits them, because they release on the alarm and let the closer do its job at full power — but they are a specified item with a wiring implication, not an adjustment.

Test it the way it will be tested. Open the leaf to ninety degrees, let go, and watch it through the last twenty degrees without helping it. Do it again from about thirty degrees, which is the position a door in real use is most often released from and the one that finds a weak closer. Then check that the bolt has actually thrown rather than resting on the lip of the keep — a bolt that has to be nudged home with a finger has not latched. Where the keep is a fraction out, the fix is the keep or the frame, because the leaf is not available to you: this is the point where the habits from ordinary door hanging have to be consciously put down.

The force argument, and the landing it changes

Two requirements pull against each other on every fire door in a public building and neither of them is optional. The door has to self-close and latch reliably from any angle, which wants closing power. And it has to be openable by the people using the building, which limits how much power there can be. Approved Document M sets opening forces for doors on an accessible route in England — one figure through the first part of the swing and a lower one beyond it — and the 2010 ADA Standards for Accessible Design set a maximum opening force for interior hinged doors while explicitly exempting fire doors to the minimum the authority having jurisdiction allows, along with a minimum closing time measured from ninety degrees. Read together, the honest reading is that a fire door is allowed to be heavier than an ordinary one and is not allowed to be arbitrary about it, and that the resolution is usually a hold-open or free-swing device rather than a closer wound down.

The part that surprises people is what the pairing does to the floor. The ADA maneuvering clearance table treats a door with both a closer and a latch as its own case on several approaches, and requires more space than the same door with neither — because the user is holding a latch retracted and working against a closing device at the same moment. A fire door is by definition the door that always has both. So the doors most likely to be squeezed into a corridor recess or a lobby corner are the doors the table is most generous to, and the space has to be found at design stage rather than argued about after the frame is in. The general ground on approach direction, push and pull sides and clear width belongs to the doorway guide next door; what belongs here is only that the closer-and-latch column is the one your door lands in.

Check both faces separately and check them with the hardware that is actually going on. A projecting closer arm eats clear width. A pull handle on the leading face changes the approach. And a landing that measured correctly against a bare opening can fail once a door with a closer on it is swinging into the same space.

Set the closer and the latch both to fitted — that is the fire door case and it is the one that grows the requirement — and run it once for each face of the door, because the approach and the side are different on the two sides of a corridor wall.

The direction someone arrives at the door from in a wheelchair.

Whether the door swings toward the person or away from them.

Whether the door has a self-closing device.

Whether the door has a latch that must be released to open it.

The clear width through the doorway with the door open ninety degrees.

Required clear depth at the door

60 in

High confidence

The clear opening entered is at or above the 32 in minimum. The space alongside is measured beyond the latch side for front and latch approaches; for a hinge-side approach, check the figure in 404.2.4.1 for which jamb it is taken from before setting out. The maneuvering space must be level, within a slope of 1:48 in any direction, and must be clear of the door's own swing. Matching the figures quoted is not compliance. The rest of the requirement, and the installed work, are outside what this page can see.

Clear space required alongside the doorway
18 in
Total clear width of the maneuvering space
50 in
Minimum clear opening width at the door
32 in

Add the equipment this sizes

This result is a specification — 60 in — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

2.67 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • Manual swinging doors and gates only. Sliding, folding, automatic and power-assisted doors are covered by different provisions, and doorways without doors different again.
  • Does not cover doors in series, recessed doors, or the additional clearance a recess deeper than 8 in (203 mm) imposes on the approach.
  • Says nothing about opening force, closing speed or hardware operability, which are separate requirements a compliant landing does not satisfy on its own.

Architrave is not the decoration here

On a certified doorset the architrave is frequently doing a job. Some installation instructions call for timber architrave of a stated minimum section covering the perimeter joint on both faces, and where they do it is a component of the tested assembly: a doorset finished with a slim MDF profile because it suited the scheme, on a schedule that named a hardwood section, is a doorset installed outside its field of application. It is worth asking the question before the trim order goes in, because nobody wants to strip forty freshly-painted openings to change a profile.

It is also the thing that hides the evidence, which is the other reason to think about it early. The perimeter joint, the packers and the fixings are all under the architrave, and once it is pinned and filled the only way to prove any of it exists is a photograph taken before it went on. Count the trim for the whole schedule in one order, in a stock length that runs a leg without a seam, and remember that a doorset is cased on both faces — the corridor side and the room side — so the count is twice the door schedule rather than equal to it. Ordering room by room down a corridor is how a job ends up with two batches of a nominally identical profile and a visible step at the seventeenth door.

It prices one face at a time — two legs and a head — so run it with the opening count doubled for a doorset cased on both sides, and pick the stock length that clears a doorset leg in a single piece rather than accepting a seam on a fire-rated perimeter joint.

SettingsSettings for this calculation
Who is doing the work?

The standard allowance most suppliers and estimating guides assume for ordinary work.

Doors are cased on both jambs and the head; windows are cased on all four sides.

The height of the rough opening.

The width of the rough opening.

How many identical door or window openings you're casing.

The length casing stock is sold in at your supplier.

Extra casing for mitre offcuts and a recut joint.

Casing needed

17.6 linear ft

High confidence
Casing needed (before waste)
16 linear ft
Sticks needed
3 x 7 ft sticks

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

3 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • The stick figure is a length division — the run with waste divided by the stock length and rounded up — and it takes no account of which piece has to come out of which stick. A 2.032 m door leg cut from an 8 ft (2.44 m) stick leaves 406 mm, too short for the 864 mm head, so four identical doors take ten sticks on the bench against the nine that division returns. Openings of different sizes have to be run separately and their stick counts added, because offcuts from one run are not pooled into another.
  • No casing width is collected, so the run is the bare opening and nothing else. A mitred picture frame round a window adds about eight times the casing width, since each of the four pieces runs past the opening at both ends: 456 mm for a 57 mm profile and 712 mm for an 89 mm one. A door adds about four times the casing width, roughly 0.75 linear ft on a standard opening with a 2 1/4 in architrave, which is already half of the default 10% allowance before a single mitre offcut is cut.
  • Rough opening, finished jamb and door leaf are three different heights and the calculator simply uses whichever you type. The 2.032 m default is an 80 in leaf rather than a rough opening, and it is not the leg length either: a leg is cut from the finished floor to the top of the head casing, which with an 89 mm architrave over that leaf sits past 2.13 m and will not come out of a 2.1 m stick at all, even though the total-length arithmetic accepts that stock length without complaint.
  • The window option assumes a four-sided picture frame. A window finished with a stool and apron is cased on three sides instead, so the four-sided figure overstates it by one opening width per window — 0.9 m on a 1.2 m by 0.9 m opening — while the stool itself, which runs past the legs by a horn at each end, and the apron beneath it are different sections this page does not produce.
  • Plinth blocks and corner rosettes change the geometry the figure assumes: a plinth block takes its own height, commonly 130 to 150 mm, off the foot of each leg, and rosettes remove the mitres so the head is cut square between them rather than long-point to long-point. Extension jambs or a jamb rip, needed wherever the wall finish stands proud of the jamb face, are a separate material in a separate width and are outside this total. The height and width fields stop at 3 m, so a 12 ft (3.66 m) patio slider or a wide bifold opening has to be split across runs.

The paperwork is half the installation

An installed fire doorset is a claim, and the claim needs evidence attached to it or it is worth nothing at the first inspection. Photograph the perimeter joint packed and sealed before the architrave goes on. Photograph the plug or label in the top edge with the door number visible in the same frame. Record the gap readings at the nine points, the closer make and power setting, the hinge and latch models actually fitted, and any deviation from the schedule with the reason for it. Third-party installation schemes exist precisely because this record is the difficult part — the BWF Fire Door Alliance and the BM TRADA Q-Mark installation schemes both require it and both give the building owner something an inspector can read.

The ongoing regime is somebody else's duty and it is worth knowing anyway, because it tells you what your work will be measured against for the next thirty years. In England the Fire Safety (England) Regulations 2022 place duties on the responsible person for higher blocks — checks of fire doors in the common parts on a quarterly cycle and best endeavours to check flat entrance doors annually — sitting under the Regulatory Reform (Fire Safety) Order 2005. NFPA 80 requires fire door assemblies to be inspected and tested not less than annually with a written record of the result. Both regimes measure the same things you have just built: the gaps, the seals, the self-closing action and whether the door latches.

So hand over a schedule written for the person holding the gauge in three years: which doorsets are on the job, what each one's certificate says its gaps should be, and where those documents live. A door that passes on the day with no record behind it gets argued about.

Where this page stops

Steel doorsets are a different discipline with a different specification route — ANSI/SDI A250.8 in North America, and the European product standard BS EN 16034 covering the fire and smoke characteristics of doorsets alongside their base product standard — and while the gap logic is the same, the tolerances, the frame fixing and the permitted field modifications are not. Glazed apertures are not a site operation on any leaf: the aperture, the beads and the glass are a tested system, and specifying that system has a page of its own on this site. Upgrading an existing panelled door with intumescent products is a question about test evidence for a specific construction rather than a fitting technique, and it belongs with the guidance on which openings need a fire door in the first place.

The claim here is deliberately narrow: build the opening to the doorset, fill the perimeter with what was tested, keep the seals continuous through the hinges and corners, and prove the thing latches from thirty degrees rather than from ninety. Clear width, the height chain, scribing a leaf and marking a keep are ordinary joinery covered elsewhere on this site — necessary here, and nowhere near sufficient.

Have these settled before the first frame is fixed

Five things that cost nothing while the doorsets are still on the pallet and cost a corridor of remedials once the architrave is painted.

  • The certification schedule for this specific doorset, on site — Gaps, seal sizes and positions, hinge grade, permitted trim, permitted ironmongery. Where it disagrees with habit, it wins.
  • The opening band, not the opening minimum — Frame outside size plus the void the instructions permit at each jamb and the head — and an out-of-square allowance driven toward zero, because the void is capped.
  • Perimeter fill material, cross-section and total quantity — Named in the installation instructions, worked from both faces, ordered for the whole schedule in one go rather than corridor by corridor.
  • Closer power size, hold-open strategy and the landing it needs — The schedule's minimum power size is a floor, not a starting point; the maneuvering clearance is the closer-and-latch case on both faces.
  • Architrave profile, section and count — Check whether the instructions specify it as a component, then count both faces of every opening in a stock length that runs a leg without a seam.
  • What gets photographed before it is covered — Packed and sealed perimeter joint, the label in the top edge with the door number, and the gap readings — none of it recoverable once the trim is on.
Open this as a workspace →

Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.

Drawn from

  • BS 8214, Timber-based fire door assemblies — Code of practice
  • BS EN 1634-1, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware — Part 1: Fire resistance test for door and shutter assemblies and openable windows
  • BS EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware — Part 3: Smoke control test for door and shutter assemblies
  • BS EN 13501-2, Fire classification of construction products and building elements — Part 2: Classification using data from fire resistance tests
  • BS 476-22, Fire tests on building materials and structures — Method for determination of the fire resistance of non-loadbearing elements of construction
  • BS EN 16034, Pedestrian doorsets, industrial, commercial, garage doors and openable windows — Product standard, performance characteristics — Fire resisting and/or smoke control characteristics
  • BS EN 1935, Building hardware — Single-axis hinges — Requirements and test methods
  • BS EN 1154, Building hardware — Controlled door closing devices — Requirements and test methods
  • BS EN 1155, Building hardware — Electrically powered hold-open devices for swing doors — Requirements and test methods
  • BS EN 12209, Building hardware — Mechanically operated locks and locking plates — Requirements and test methods
  • BS EN 1125, Building hardware — Panic exit devices operated by a horizontal bar for use on escape routes
  • BS EN 179, Building hardware — Emergency exit devices operated by a lever handle or push pad for use on escape routes
  • NFPA 80, Standard for Fire Doors and Other Opening Protectives — installation clearances, and the periodic inspection and testing of fire door assemblies
  • NFPA 252, Standard Methods of Fire Tests of Door Assemblies
  • UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies
  • ANSI/SDI A250.8, Recommended Specifications for Standard Steel Doors and Frames
  • 2010 ADA Standards for Accessible Design, U.S. Department of Justice — 404.2.4.1 and Table 404.2.4.1 maneuvering clearances, 404.2.8 closing speed, 404.2.9 door opening force
  • Approved Document B, Fire safety (England)
  • Approved Document M, Access to and use of buildings (England) — opening forces on doors in an accessible route
  • The Fire Safety (England) Regulations 2022, regulation 10 — fire door checks in buildings with a storey above 11 m
  • The Regulatory Reform (Fire Safety) Order 2005
  • BS 9999, Code of practice for fire safety in the design, management and use of buildings
  • British Woodworking Federation Fire Door Alliance — fire door installation and certification guidance
  • BM TRADA Q-Mark Fire Door Installation scheme documentation

Guidance, not a specification. Local codes, the engineer of record and the product manufacturer’s instructions govern where they differ from anything written here.