The fire-rated glazing product category.
The categories do genuinely different jobs, and picking the wrong one is not a detail. Some products resist the passage of flame and smoke only; others also block radiant heat, and only those may be used where the code limits radiant transmission to protect an escape route or a neighbouring property. What a product is permitted to do comes from its listing, and this page reports a clearance rather than deciding whether an assembly is acceptable.
The frame material the glazing is set into.
The rating belongs to the ASSEMBLY, not to the glass. The same product in a different frame is a different tested assembly, and it may carry a different rating or none at all — the frame has to hold the glass in place while it distorts, and materials do that differently. Use the frame the listing names rather than the one on the drawing, and where they disagree, resolve that before ordering anything.
Typical listed edge clearance
0.37 in
This is a TYPICAL reference figure only, not a calculated or code-compliant value — fire-rated glazing edge clearance is set entirely by the specific tested and listed assembly (UL 9/UL 10B/UL 10C, NFPA 80/257). Always verify the exact bite/clearance against your specific product's UL listing and the manufacturer's installation instructions before installation; deviating from the tested clearance voids the fire rating.
They open the calculator with your figures already in it
Fire-Rated Glazing Typical Edge Clearance Reference: 0.374 in — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- Fire-rated glazing edge clearance is NOT governed by a calculable thermal-expansion formula — it is set entirely by the specific tested and listed assembly per UL 9/UL 10B/UL 10C and NFPA 80/257. The values below are commonly-cited TYPICAL figures for reference only.
Inputs used
- Fire-Rated Glazing Type
- Traditional wired glass
- Frame Material
- Hollow metal
Confidence note: This is a TYPICAL reference figure only, not a calculated or code-compliant value — fire-rated glazing edge clearance is set entirely by the specific tested and listed assembly (UL 9/UL 10B/UL 10C, NFPA 80/257). Always verify the exact bite/clearance against your specific product's UL listing and the manufacturer's installation instructions before installation; deviating from the tested clearance voids the fire rating.
What this calculation does not cover
- A fire rating is not an impact rating. Glazing in a door, a sidelite or any other hazardous location has to satisfy safety-glazing impact requirements as well, and traditional wired glass is where the two collide — it is weaker under impact than plain annealed glass of the same thickness, and its use in those locations has been restricted for years. Confirm the lite is listed for both before the edge clearance matters at all.
- One figure is returned for every lite size, and listings do not always work that way. A larger lite expands more, so a listing can give a different clearance band for a big lite than for a small one, and this page never asks how big the opening is. Read the size ranges in the listing before treating the figure as fixed.
Add the equipment this sizes
This result is a specification — 0.37 in — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-06 · in the site-wide review of 2026-09-06 · v1.0.1
Regulatory standards & verification citations1
- Fire-rated glazing edge clearance is NOT governed by a calculable thermal-expansion formula — it is set entirely by the specific tested and listed assembly per UL 9/UL 10B/UL 10C and NFPA 80/257. The values below are commonly-cited TYPICAL figures for reference only.
Which documents these citations point at
Standards referenced: NFPA 80 (National Fire Protection Association, United States); UL 9, UL 10B, UL 10C (UL Solutions, United States).