Building envelope

Draught-Proofing an Old House, Opening by Opening

A candle finds the gaps; the merchant needs lengths. Surveying an old house opening by opening, then turning the round into rolls, sweeps, film and tubes.
  • 19 minReading time
  • 10Sections
  • 5Calculators inline
  • Last reviewed

A candle, a clipboard, and one trip to the merchant

The round works best on the first properly cold evening of October, with the heating up, the wind steady from one quarter and the house shut. A candle held at knee height inside the front door will lean before you have finished closing it behind you. What you are compiling as you walk is not a fault list, though it will feel like one. It is a purchase list, and every line on it has to end in a length, a leaf width, an area or a count, because those are the four ways the things you are about to buy are sold.

Most of these jobs go wrong at the counter rather than on the house. Somebody walks the rooms, writes down front door, hall, back bedroom sash, landing, and then stands in front of two racks of profile guessing at a gap nobody measured, on a door nobody checked for square. Carry a tape, a torch, a smoke source finer than a flame, and a sheet with a column for gap widths. The survey costs an hour. It saves the second trip, which otherwise happens on the Saturday of the first hard frost, in the dark, with half the house already stripped.

What the flame is telling you, and what it is not

A house with a warm inside and a cold outside is a chimney with rooms in it. Warm air rises, leaves through whatever is open near the top — loft hatch, ceiling roses, the boxing around a soil stack — and cold air is pulled in low to replace what left. Somewhere between the two sits a level where inside and outside pressure match, and at that level nothing moves at all. Hold a candle there, over a gap you could post a letter through, and the flame stands straight up.

That is why a survey done on a still evening reports ground-floor doors and almost nothing upstairs, and why the upstairs openings that read as blameless are the ones supplying the pull downstairs. Both ends of the stack are leaks. Only the lower end announces itself in a way you can feel on the back of a wet hand.

Wind rewrites the whole sheet. The elevation the wind lands on is pressurised, the lee face and usually both flanks are in suction, and an opening that dragged on Tuesday sits quiet on Thursday because the weather turned ninety degrees. If there is only going to be one round, do it in wind, write the direction at the top of the sheet, and treat the sheltered elevation as unsurveyed rather than as sound.

There is a crude way to remove both variables at once. Shut every external door and window, close the trickle vents, open the internal doors so the whole volume behaves as one space, and run the kitchen and bathroom extract fans together. The house goes slightly negative, every opening leaks inward at the same time, and the round becomes repeatable enough to compare against itself afterwards. Use a smoke pencil or an incense stick rather than a flame — it reads a fraction of the movement a candle needs — and keep any naked flame away from curtains, away from the meter cupboard, and out of any room where a gas smell has ever been reported. Shut down every open-flued appliance in the house before the fans go on, and leave it shut down for the round: pulling a house negative is exactly the condition that drags combustion products back down a flue, which is the hazard the section on combustion air below is about.

The instrumented version of that trick is a blower door, and the methods are written down: ASTM E1827 for orifice blower doors, ANSI/RESNET/ICC 380 and BS EN ISO 9972 for the test procedure, ATTMA Technical Standard L1 for dwellings in the UK. The openings themselves have their own tests — ASTM E283 and BS EN 1026 measure air leakage through a window or doorset and BS EN 12207 classifies what comes out — but those numbers describe a new unit clamped into a rig. None of it survives eighty years of paint, seasonal movement and a jamb that has been eased twice by different people.

Where to hold the smoke on a depressurised house, and what a steady pull means
Where the smoke goes sidewaysWhat is actually happeningWhat the line on the sheet becomes
Hinge side of a door, at mid heightNo seal in the rebate, or a foam strip crushed flat years agoJamb and head length, and a profile chosen against the measured gap
Under a door, at one corner before the otherThe leaf is out of parallel with the floor, not merely unsealedA sweep sized by leaf width, and hinge or threshold work before it
Meeting rail of a sash, worst at the endsSashes no longer pulling together; parting bead worn thinBrush pile in a routed groove, or a new parting bead first
The line where architrave meets plasterAir arriving from the frame-to-masonry gap behind the trimA sealant run, or lifted architrave and a packed void behind it
Skirting and floorboard junction below a windowThe suspended floor void. The window is innocentMetres of sealant along the junction; no product on the window helps
Letterplate, keyhole, cat flap, old extract grilleA designed hole doing exactly what it was made to doPurpose-made closures, counted as items and never cut off a roll
Where to hold the smoke on a depressurised house, and what a steady pull means

One closed opening, six separate gaps

Stand at a single sash and count the ways air gets past it. There is the moving joint, where the sash meets the frame. There is the fixed joint, where the frame meets the masonry, hidden behind the architrave and usually the larger of the two. There is the glass, which does not leak at all but is cold enough to start a convection loop the occupant will describe as a draught. There is the sill and its underside. There is the hardware — the sash lift, the keyhole, the letterplate on the door in the next room. And there are the routes that only look like the window: the floorboard line beneath it, the void behind boxed-in shutters, the plaster gap at a boxed pipe.

Only the first of those takes weatherstrip. Everything else takes sealant, tape, a fitted item, joinery, or nothing at all, and the discipline that keeps an order sheet honest is refusing to write strip against a gap that is never going to move. A compression seal squeezed into a static joint does the job a tube would have done for a tenth of the money and comes away with the paint in two years.

Read the opening as a stack from the weather inward and each line on the sheet has a place in it, along with the reason it is measured the way it is.

The air joint at a closed opening

One closed opening in section, weather side uppermost: the mastic joint at the reveal, the packed gap behind the frame, the frame itself, the compression seal sitting in the rebate, the leaf that closes against it, and the film stretched across the room face.
  1. Perimeter mastic at the reveal — the outside face of the frame-to-masonry joint, bought as tubes against a bead length rather than by the metre of anything Caulk & Sealant Calculator
  2. Packed gap behind the frame — the void the frame was shimmed into, closed with backing and tape; often the largest single leak at the opening Air Barrier Sealant Tape Linear Footage Calculator
  3. Frame or lining with its rebate — carries the seal and sets what profile will fit, since the rebate depth decides whether the leaf still closes on it
  4. Compression seal in the rebate — the only layer here bought by the running metre, measured as the full perimeter of every opening it goes round Weatherstripping Calculator
  5. Door leaf or sash — the part that moves, so its squareness and its swing decide whether any seal at all will work here
  6. Film across the room face — an added still-air layer over single glazing, measured to the tape line on the frame and not to the glass Window Film Calculator

Sorting the doors into three piles

Doors divide into three groups and the sheet is worth ruling into three columns before the round starts. The first pile takes a seal in the rebate and nothing else: the leaf is sound, it closes on its stops evenly, and the gap is consistent enough that one profile will cover it. The second pile needs joinery before any seal is bought, because a leaf that has dropped on its hinges, bowed away from the frame at the lock side, or been painted until the rebate is full will defeat every profile on the rack. The third pile needs a threshold rather than a strip, because the gap under it is not a tolerance, it is a clearance over a carpet somebody laid in 1994.

Measure the moving joint as the full perimeter of the opening, all four sides. Air sealing is not casing: casing skips the bottom of a door because the bottom has no architrave, and air does not care about that. But the bottom is a different product — a sweep, a brush strip or a drop-down seal, sized by the width of the leaf and bought as an item — so it comes off the roll figure and goes on its own line. Count the same way at every opening and the two lines never get confused at the counter.

Take gap widths while you are there, at three heights on each jamb and at both ends of the head. Record the largest and the smallest, not an average, because the profile you buy has to seal the widest point without binding at the narrowest. A folded card, a coin, a feeler set, anything with a known thickness works; what does not work is holding the door and saying it feels about right, since a seal is asked to bridge that gap for the life of the door with no further adjustment.

Then group the openings by size before touching the arithmetic. Six identical bedroom doors are one calculation multiplied out; a front door, a back door and a pair of French doors are three separate ones. Seal comes in whole rolls with a waste allowance built in, so a run of small openings does not consume small amounts of anything — it consumes a whole roll per profile per gap band, and the leftover ends are what you go back for.

  1. Walk the ground floor first with the extract fans running, since that is where the largest and most reachable leaks in an old house sit.
  2. At each door, close it on a strip of paper at four points and note where the paper pulls out with no resistance.
  3. Check the leaf against the frame with a straightedge before writing any product against it.
  4. Write perimeter, leaf width, largest gap and smallest gap on one line per opening.
  5. Mark which openings are fire doors or escape routes; those take intumescent and smoke seals to their own specification, not a draught profile off a rack.
  6. Total the perimeters by size group, not by room, because the merchant sells against the group and not against the room.

Run the perimeter of each size group through this and it comes back as whole rolls with the waste already in, which is the number the counter needs — the sweeps and threshold seals stay on a separate line, sized by leaf width.

The height of the door or window opening.

The width of the door or window opening.

How many identical openings you're sealing.

The length weatherstripping is sold in at your supplier.

Weatherstripping needed

3 x 10 ft rolls

High confidence
Weatherstripping needed (with waste)
20.9 linear ft

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

3 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • Gap width is not part of this. The perimeter comes out the same whether the door closes on a hairline gap or one you can see daylight through, and gap width is what decides the profile and thickness you buy. Measure it at the head, at the latch and at the hinge, because a door that has dropped will give three different numbers.
  • Door sweeps and thresholds are not sized here, and neither are kerf-in or screw-on seals, which are sold in door-length pieces rather than on a roll. The count treats the whole opening perimeter as roll material.
  • Waste is a flat 10 percent on the total, not a cutting plan. It does not model the offcut left when a roll will not yield another full jamb length, corner overlaps or mitred returns, or a job that runs two strips on the same jamb.
  • Every opening is treated as a plain rectangle of one size. Out-of-square or racked frames, arched and round-top heads, and the extra run at the meeting stile of a pair of doors are all outside the model.
  • This is a materials take-off, not an air-leakage or energy figure. It does not estimate the infiltration you will remove or what it saves, and it is not a ventilation assessment: tightening a house that has atmospherically vented combustion appliances is work that has to be checked against those appliances.

A profile chosen against the gap you measured

The rack holds half a dozen families and they are not interchangeable. Self-adhesive foam is cheap, forgiving of a rough surface and finished in a couple of seasons, because it takes a set and stays crushed. Extruded EPDM in E, P or D section is a compression seal that recovers, and the letter is a shape, not a size — each maker bands its own profiles by the gap they suit. Tension or V-strip springs open against the leaf and is at its best in a joint that slides, which is why it survives on a sash where foam does not. Brush pile handles a sliding joint with a wide and variable gap and is what a sash meeting rail and most patio doors want. Silicone bubble and blade seals set into a routed groove are the joiner-fitted version, cost an operation per opening, and are still there in twenty years.

Two failures account for most of the strip that ends up in the bin. Too thick, and the leaf will not latch: the occupant leans on it, the seal takes a permanent set within a month, or somebody simply pulls it off, and either way the gap is back. Too thin, and nothing was ever bridged. The second failure is surface, not size — self-adhesive tape wants clean, dry, sound, non-greasy substrate above the temperature its maker states, and an October hallway with old gloss paint, condensation on the frame and dust in the rebate is below every one of those conditions. Wipe, dry, and warm the frame if the sticking has to happen that evening.

Seal families against the joint they are being asked to close
FamilyThe joint it suitsHow the gap presentsHow it is sold
Self-adhesive foamA hinged rebate on a sound frame, as a first passAnything from hairline up, but it stops recovering earlyRoll, by length
Extruded EPDM, E/P/D sectionA hinged rebate expected to lastRead the maker's own band for the section; they do not agree with each otherRoll, by length
Tension or V-stripSliding joints and sash stiles, where a leaf rubs pastNarrow and consistent; it springs rather than squashesRoll, by length
Brush pileSash meeting rails, sliding doors, under-door stripsWide and variable, the case compression cannot handleRoll or carrier length
Routed bubble or blade sealDoors being rehung or repainted anywaySet by the groove, so the gap is made to suit the sealCoil, plus a routing operation
Sweep, brush strip, drop-down sealThe threshold, on every pile of doorA clearance over a floor finish, not a toleranceItem, by leaf width
Seal families against the joint they are being asked to close

The sashes, and what a film can honestly do

Single glazing loses heat two ways that feel identical from an armchair. Air comes through the joints, and the glass runs cold enough to chill the air against it, which then falls down the face of the window and crosses the floor. The second is not a draught in any measurable sense and no amount of weatherstrip touches it. It is the one that makes a sealed room with a big window still feel unpleasant to sit in.

Shrink film answers the second problem by adding a still-air layer in front of the glass, and it answers it well enough on a genuinely cold single-glazed sash that people notice within a day. It goes on the room side, taped to the frame or the bead rather than the glass, because the trapped layer is the whole mechanism and a film stuck to the pane traps nothing. Tape to a clean dry surface, tension it with a hairdryer until the wrinkles pull out, and test the tape on a hidden inch first — on old distemper, flaking gloss or bare timber it will take the finish with it when it comes off in March.

Measure to the tape line, not the glass. The film has to cover the opening plus the band of frame it sticks to, and rolls come in fixed widths that do not tile neatly onto a bay of odd Georgian sashes, so the waste is real and worth carrying in the number rather than discovering it two windows from the end. Roll dimensions come off the product's own packaging: there is no standard governing shrink film coverage, and the sizes differ between insulating kits, static cling and solar control films that solve an entirely different problem.

Then be honest about the limits, because they are what the guide is for. A filmed sash cannot be opened until spring, so no window serving as an emergency escape opening — governed by IRC Section R310 in North America and by Approved Document B in England — gets filmed, and neither does one whose trickle vent would end up behind the sheet. On a modern sealed unit the gain is small enough to be inside the noise. And if the room is genuinely damp, moving the cold surface from the glass to the film moves the condensation with it rather than removing it. Where the window is worth keeping and the improvement has to last, Historic England's advice note on secondary glazing describes the durable version of the same idea, and it is joinery rather than a kit.

Total the areas you measured to the tape line, not to the glass, and this returns rolls with a trim allowance in them — the roll size varies by brand, so check the packet against the number before the trip.

The combined area of all windows to be filmed.

Window film rolls needed

3 rolls

Medium confidence

Roll size varies by brand and film type (insulating shrink film, static cling, solar/UV-blocking) — check your specific product's roll dimensions.

Area to cover (with trim allowance)
121 sq ft

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

What this calculation does not cover

  • The count assumes every roll is the standard 3 ft (0.91 m) x 15 ft (4.5 m), 45 sq ft (4.2 m²) footprint. There is no input for roll size, so shrink-film kits, static cling packs and wide architectural rolls all have to be rescaled by hand against the coverage printed on the box.
  • The 10% allowance is a flat margin on total area, not a cut plan. Film comes off a roll of fixed width, so a pane wider than the roll needs a seam or a wider product, and offcuts left by mismatched pane widths rarely nest across windows. Arched, bay and divided-light glazing routinely wastes far more than the allowance carries.
  • This is a take-off, not a performance figure. It says nothing about U-value, solar heat gain coefficient, R-value or energy saved, and nothing about whether film is the right fix for the glass you already have.
  • The area asked for is glass area. Interior shrink film is taped to the frame or surround rather than to the pane, so the area it actually covers is larger than the glass; measure the surround for that product or the roll count runs short.
  • Glass compatibility is not checked. An applied film raises the risk of thermal stress cracking on some glazing, particularly tinted, thick, annealed or already coated units, and many sealed-unit warranties exclude glass carrying an applied film. Confirm the film against the glass type and the warranty before ordering.

The joints that never move

The fixed joints are where an old house usually loses more air than the moving ones, and they are invisible because the trim covers them. A frame was shimmed into a rough opening, packed with whatever came to hand, and the architrave went on over a void that runs the full height of both jambs and along the head. Behind skirting there is often a continuous gap onto a floor void, and under a window it is that gap, not the sash, that puts cold air across your ankles. Loft hatches, boxed pipework, the plaster around a soil stack and the hole a cable was pulled through all belong on the same list.

Sealant selection is a specification job even at this scale. ASTM C920 classifies elastomeric sealants by movement capability and by the substrates they are tested against, and ASTM C1193 is the guide to using them: joint width to depth ratio, backer rod, and the rule that a joint bonded on three sides tears itself apart the first time it moves. On the outside of an old building the substrate is the problem — friable brick, soft lime render and chalky paint give nothing to stick to, so rake the joint back to something sound, and where the reveal is genuinely powdery accept that a compressible backing and a bead is a maintenance item, not a permanent seal.

Quantify these as bead length and convert to tubes, and buy more than the count says. Every tube has an end that hardens in the nozzle overnight, a gun-load worth of waste at each changeover, and the runs that get found once the architrave is off are always longer than the ones measured with it on.

Put the openings you are sealing round through this to convert perimeter bead into tubes, then add the internal runs — the skirting line, the loft hatch surround, the boxing — as extra openings of equivalent length.

SettingsSettings for this calculation
Who is doing the work?

The standard allowance most suppliers and estimating guides assume for ordinary work.

The height of the door or window opening being sealed.

The width of the door or window opening.

How many identical openings you're caulking.

Extra bead length on top of the openings' perimeter, for the sealant lost at the ends of tubes and in tooling.

Caulk tubes needed

1 tube

High confidence
Caulk bead length (with waste)
20.9 linear ft

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

3 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • The whole estimate is locked to one figure — a 1/4 in (6 mm) bead at 25 linear ft (7.6 m) per 10.1 oz tube — and there is no field for gap width or joint depth, so the answer never moves when the joint does. Widening the bead to 3/8 in (9.5 mm) at the same depth uses about half as much caulk again per unit length, and a gap that is both wider and deeper can take more than double. Size the bead against the actual gap before ordering to this number.
  • It measures the opening, not the bead path. The exterior bead runs around the outside of the casing where trim meets siding, which is longer than the opening perimeter by roughly eight times the casing width, and most exterior details also take a second bead on the inner edge where casing meets the frame. The waste allowance on the result, 10% as the page opens, does not stand in for either.
  • The formula takes the full perimeter, 2 x (height + width), so it charges caulk along the bottom of every opening. Standard practice on many window and door details is to leave the sill joint and any weep openings deliberately open so water that gets behind the trim can drain out. If you follow that, the real bead is shorter than the figure here.
  • Nothing here addresses the sealant itself: substrate compatibility, the movement the joint has to survive, whether a backer rod is needed to set depth and break the third-side bond, primer, or the temperature and surface-moisture limits printed on the cartridge. A correct tube count applied to a joint bonded on three sides still tears through its own middle.
  • This is a material take-off, not an air-sealing assessment. It does not identify where the leaks are, and it is not a blower-door result or evidence of compliance with any air-leakage or energy-code requirement — trim caulk is one small part of a wall's air barrier.

The appliance that had been breathing through those gaps

There is one way this work kills people and it is worth reading before the first roll goes on. An open-flued gas fire, a back boiler, a solid fuel stove, an open fire or a gas range takes its combustion air from the room it sits in, and in a house that leaks through every door and sash, that air arrived through the gaps you are about to close. Seal the ground floor properly, then run a powerful kitchen extract, and the path of least resistance for replacement air can become the flue, pulling combustion products back down into the room.

What governs it depends on where you are. In North America the indoor air method in NFPA 54 and the International Fuel Gas Code sizes combustion air openings by appliance input, requiring two openings — one near the ceiling, one near the floor — each with the stated minimum free area; the outdoor air methods use different factors and an unconfined space may need no dedicated opening at all. In England, Approved Document J covers combustion appliances and BS 5440-2 sets the ventilation provision for gas appliances up to 70 kW net. Neither is a calculation to settle by yourself on somebody's stove.

So write every open-flued appliance inside the sealed volume onto the survey sheet before any product is bought, keep the permanent air vents that serve them, and have a spillage test done by a registered engineer after the work rather than before it. Carbon monoxide alarms in the affected rooms are a five-minute purchase on the same trip. A sealed room with a working alarm is a good outcome; a sealed room with a bricked-up air brick and a cheerful new draught excluder is the other one.

This screens the indoor air method against an appliance nameplate so you can see whether the vents in the room are anywhere near the free area the code asks for — it is one method of several, and the full section governs the installation.

The fuel-burning appliance's total rated input, from its nameplate.

Minimum free area per opening

100 in²

Medium confidence

This is the NFPA 54/IFGC indoor air method for a confined space, requiring TWO openings of this minimum free area each (one high, one low). Outdoor air methods use different (typically smaller) sizing factors, and unconfined spaces may not require dedicated combustion air openings at all — confirm which method and space classification applies to your installation with the full code section before finalizing opening size, as this is a single-method screening calculation, not a complete combustion air analysis.

Free area before the 100 in² floor is applied
100 in²

Add the equipment this sizes

This result is a specification — 100 in² — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

What this calculation does not cover

  • Free area is not the size of the hole you cut. A grille or louver passes only its open fraction — roughly three-quarters for metal, as little as a quarter for wood — and an insect screen behind it takes more again, so a 100 in² (645 cm²) free-area requirement can need an opening of 130 to 400 in² (840 to 2,580 cm²) depending on what covers it. Size from the louver's published free area, or the appliance is starved through an opening that measures correctly.
  • The openings only work if the space on the other side is large enough. This method assumes the adjoining room, plus everything freely communicating with it, holds at least 50 ft³ (1.4 m³) per 1,000 BTU/hr (0.3 kW) of combined appliance input; cutting two grilles into the partition of a small closet does not create combustion air, it shares one shortage between two rooms.
  • Nothing here accounts for air being pulled out of the space. A kitchen hood, a clothes dryer or a bath fan can drop the room below atmospheric pressure and reverse an atmospheric flue no matter how generous the openings are, which is how a correctly sized opening still ends with a CO alarm — a house with substantial mechanical exhaust needs the appliance's air supply looked at as a pressure balance, not as an area.

Proving it, and what a tighter house does next

Repeat the depressurised round with the same fans running, the same doors open and the same smoke source, ideally in similar weather. That comparison is worth more than any single reading, because it uses the house as its own reference and finds what you missed rather than scoring what you did. The openings that still pull will mostly be the ones where a profile was chosen against a remembered gap instead of a measured one.

The measured version puts a number on it. A blower door reports flow at fifty pascals, and that flow taken over an hour, divided by the volume of the house, gives air changes per hour at the same pressure, which is the currency every standard and target is written in. Watch the unit the fan reports in before dividing anything: a reading in cubic metres per hour divides straight into a volume in cubic metres, while one in cubic feet per minute is a per-minute figure and has to be put on an hourly footing first. The direction of travel matters more than the absolute figure in an old building: new-build thresholds under the adopted energy code, such as the air leakage provisions at Section R402.4 of the IECC, are written for construction that was detailed for airtightness from the drawings up, and no amount of strip round a Victorian sash is going to reach them.

Tightening the envelope also removes ventilation nobody had specified. Uncontrolled infiltration is a bad way to ventilate a house — it happens most on the coldest, windiest days and least in still humid weather, which is exactly backwards — but it was doing something, and the moisture from cooking, washing and breathing left through it. ASHRAE Standard 62.2 and Approved Document F both make the same point from opposite sides of the Atlantic: the answer to a tighter house is deliberate ventilation, in the wet rooms first, not a return of the gaps.

Watch the first winter for where that moisture goes instead. It condenses on the coldest surface in the room, which in an old house is a window reveal, an uninsulated lintel, an external corner or the wall behind a wardrobe on the north side. Mould appearing on a reveal a month after draught-proofing is not a coincidence and not a reason to undo the work; it is the humidity that used to leave through the sash telling you the extract fan runs for four minutes and the bathroom door is shut too soon.

Keep the trickle vents open. They are the controlled version of what you removed, they are the cheapest ventilation in the building, and taping them shut on a cold night is the single most common way a good draught-proofing job turns into a damp complaint by February.

Enter the floor area, the ceiling height and the airtightness you are aiming at, and this returns the flow the fan should read at fifty pascals — a target to set before the work, so the retest has something to be measured against.

The total conditioned (heated/cooled) floor area of the building.

The average ceiling height across the conditioned space.

Your airtightness goal, e.g. from an energy code requirement or certification program.

Target CFM50

432 CFM50 (target maximum)

High confidence

Your actual blower door test result should come in at or below this target — this is the inverse of the Air Changes Per Hour Calculator, useful for setting a goal before construction or air sealing work rather than evaluating a completed test.

Building volume
8,640 ft³

Add the equipment this sizes

This result is a specification — 432 CFM50 (target maximum) — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

8 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • Building volume here is nothing more than floor area multiplied by average ceiling height. That ignores the thickness of intermediate floor assemblies, flattens stairwells and double-height spaces into an average, and omits any conditioned basement or attic whose area you did not enter. The target moves in direct proportion to the volume, so a volume measured ten per cent differently from the tester's gives a CFM50 limit ten per cent different — agree the volume basis with whoever will run the test before you build to this number.
  • Nothing here defines the tested envelope: whether an attached garage, an unheated basement, a conditioned crawl space or a plant room sits inside or outside it. That single decision changes both the volume in the denominator and the leakage the fan has to move. Two people can test the same building to two different ACH50 figures purely by drawing the boundary in two different places.
  • ACH50 normalises leakage against volume. UK and much European testing, and some North American programmes, instead specify air permeability or leakage per unit of envelope area. This page never asks for envelope area, so a target handed to you in those terms cannot be met by hitting this CFM50 figure.
  • The number assumes a properly conducted test at 50 Pa. It carries no correction for wind, stack effect or baseline pressure, no averaging of a depressurisation result against a pressurisation one, and no allowance for how the building is prepared — which trickle vents, flues, extract fans and drain traps get sealed and which are left as found. Those are the usual reasons two tests of the same building disagree.
  • This is a target airflow, not a ventilation or combustion-air check. A building tightened towards a low ACH50 needs mechanical ventilation sized and commissioned for it, and any open-flued or naturally aspirated appliance inside the envelope needs its own combustion air and spillage assessment. Hitting this figure says nothing about either, and those are the parts that carry a safety consequence.

One order, four units of sale

The whole round collapses into four units. Metres on a roll, for the moving joints, grouped by profile and by gap band. Items by leaf width, for the sweeps and threshold seals. Area in a fixed-width roll, for the film. Tubes, for every joint that will never move again. Nothing on the sheet is bought in any other way, and a list that does not resolve into those four is a list with a guess still in it.

Buy whole rolls, keep the offcuts labelled with the room they came from, and expect the second visit to the merchant anyway — it will be for the letterplate closure, the keyhole cover and the sealant colour that did not match, which is the cheap trip rather than the expensive one. The expensive trip is the one where the profile turned out to be a size too thick and every door in the house has to be stripped back and done again.

What the round has to hand the merchant

Six columns on one sheet, filled in as you walk. Anything missing from them turns into a guess at the counter, and the guesses are what bring you back.

  • Perimeter length per opening, grouped by size — All four sides, since air sealing does not skip the threshold the way casing does. Identical openings are one calculation multiplied out.
  • Leaf width for every door in the survey — Sweeps, brush strips and drop-down seals are items sized by width, so they never come off the roll figure and belong on their own line.
  • Largest and smallest gap on each jamb — The profile has to seal the widest point without binding at the narrowest, and the maker's own band for that section is what decides it.
  • Glazed area measured to the tape line — Film covers the opening plus the band of frame it sticks to, and fixed roll widths do not tile onto a bay of odd sashes.
  • Metres of fixed joint, for the tubes — Frame perimeters, architrave lines, skirting under windows, loft hatch surrounds and boxed services. Rake back anything friable first.
  • Every open-flued appliance in the sealed volume — Recorded before the first roll is bought, with its air vents kept and a spillage test booked for after the work rather than before.
Open this as a workspace →

Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.

Drawn from

  • ASTM E283 Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
  • ASTM E1827 Standard Test Methods for Determining Airtightness of Buildings Using an Orifice Blower Door
  • ANSI/RESNET/ICC 380 Standard for Testing Airtightness of Building, Dwelling Unit, and Sleeping Unit Enclosures
  • BS EN 1026 Windows and doors. Air permeability. Test method
  • BS EN 12207 Windows and doors. Air permeability. Classification
  • BS EN ISO 9972 Thermal performance of buildings. Determination of air permeability of buildings. Fan pressurization method
  • ATTMA Technical Standard L1: Measuring Air Permeability in the Envelopes of Dwellings
  • ASTM C920 Standard Specification for Elastomeric Joint Sealants
  • ASTM C1193 Standard Guide for Use of Joint Sealants
  • ANSI/ASHRAE Standard 62.2, Ventilation and Acceptable Indoor Air Quality in Residential Buildings
  • International Energy Conservation Code, Section R402.4 Air Leakage (as adopted and amended locally)
  • International Residential Code, Section R310 Emergency Escape and Rescue Openings (as adopted and amended locally)
  • NFPA 54 National Fuel Gas Code, combustion air provisions
  • International Fuel Gas Code, combustion air provisions (as adopted and amended locally)
  • Approved Document B (Fire safety), Volume 1: Dwellings, Building Regulations for England — escape windows
  • Approved Document F (Ventilation), Building Regulations for England
  • Approved Document J (Combustion appliances and fuel storage systems), Building Regulations for England
  • BS 5440-2 Flueing and ventilation for gas appliances of rated input not exceeding 70 kW net. Specification for the installation and maintenance of ventilation provision for gas appliances
  • BS 8213-4 Windows and doors. Code of practice for the survey and installation of windows and external doorsets
  • Historic England, Energy Efficiency and Historic Buildings: Draught-proofing Windows and Doors
  • Historic England, Energy Efficiency and Historic Buildings: Secondary Glazing for Windows

Guidance, not a specification. Local codes, the engineer of record and the product manufacturer’s instructions govern where they differ from anything written here.