Fourteen windows, and a column on the survey nobody filled in
The survey sheet has a line per opening and about nine columns: reference, tight size, configuration, handing, restrictor, glass specification, colour inside, colour outside, and a notes box. On most sheets the ventilator is a tick in that notes box or it is nothing at all, and the fabricator's order form then fills the gap with whatever the account default is — usually vents on, occasionally vents off, and on a mixed order sometimes both without anyone noticing. Six weeks later a lorry arrives with fourteen welded frames whose heads either have a slot in them or do not, and a decision that was never consciously taken has already been manufactured.
Nothing else on that sheet is as final. A colour is a foil the fabricator can re-run. A handing is one sash remade. A glass specification is a sealed unit swapped through the bead the following week, which is its own job with its own arithmetic. A ventilator is a machined aperture through a structural member of a welded frame, cut before the corners were fused, and it cannot be added afterwards without either sending the frame back to a machine or drilling it in the opening — a different operation, with a different result, and on most systems a different warranty position.
The consequence lands on the installer rather than on the homeowner who chose the colour. Replacement windows in a dwelling in England and Wales are controlled work under the Building Regulations 2010, discharged either by a building notice to the local authority or through a competent person scheme — FENSA, Certass or Assure — whose certificate is issued to the address and produced again years later by a conveyancer. Ventilation is one of the things that certificate covers. A house re-glazed without background ventilators in rooms that had them holds a certificate asserting something untrue about the building, and the person who signed it is the person holding it.
The test is what each room had, not what the house averages
The governing principle for replacement windows in England sits in Approved Document F, Ventilation, Volume 1: Dwellings, and it is comparative rather than absolute. Provision after the work should be no worse than provision before it. Where the window coming out carried a background ventilator, the window going in should carry one of at least the same equivalent area. Where the old window had none, the current Volume 1 does not leave it to judgement: it says the provision has to be shown to be no worse than before, and sets out figures that demonstrate it — 8,000 mm² equivalent area in a habitable room, 8,000 mm² in a kitchen, and 4,000 mm² in a bathroom with or without a WC. The kitchen is the one that catches people, because it sits on the same figure as the habitable rooms rather than with the wet rooms, and a schedule that groups it with the bathroom orders half the area the room needs. Read the paragraph in the edition in force where the work is being carried out rather than the one you memorised — the older figures were 5,000 mm² and 2,500 mm², and they did group the kitchen with the bathroom, which is how a house re-glazed in two phases ends up with two different provisions across one elevation.
The comparison is per room, and that is the part that gets lost. A whole-house total is meaningless here, because a ventilator only ventilates the room it is in: two vents on a landing do nothing for a bedroom with none. So the audit has to happen while the old windows are still in the wall, room by room, counting what is actually there rather than what the house is thought to have.
It also has to count ventilators that are not in a window. Plenty of houses have their provision in an over-frame unit above the head, in a hit-and-miss wall vent, or in an airbrick left over from a chimney that has since been removed, and each of those is provision the comparison recognises. Watch for the ones that have been defeated: a ventilator screwed shut and painted over by a previous occupant is still, for the purposes of the test, a ventilator that was there. Deleting it from the schedule because it was not working is exactly how provision drops without anybody deciding to drop it.
Position is prescribed too, in one line that settles the whole detail. Approved Document F expects background ventilators to be controllable, to sit at least 1.7 m above floor level, and still to be easy for the occupant to reach, which is why they end up in the window head rather than the sill — air arriving at head height entrains room air before it reaches anyone sitting down, and air arriving at knee height is a draught complaint that ends with the vent taped over by February. That height convention is also what makes the frame head the only practical location, and the frame head is the member that has to be machined.
What the cutter actually goes through
On a PVC-U system the aperture is cut through the outer frame head before the corners are welded, and it passes through more than one wall of the extrusion: the external face, the chamber behind it and the internal face, with the airway formed between them. The head of a large frame is usually reinforced, so the steel or aluminium insert has to be notched, stopped short, or avoided by shifting the vent along the head — a fabrication decision taken against the profile system's own manual, and precisely why a vent drilled in situ later meets that reinforcement instead of a designed clearance. Aluminium is less forgiving again: a thermally broken section is two shells held apart by polyamide struts, a bore driven through the head crosses the break, and systems that offer a head ventilator publish the position and the machining for it while systems that do not, do not. Timber and composite take a routed slot more readily, but the bore exposes end grain along the whole airway, and a slot cut into a factory-finished frame needs sealing and priming through it before the body goes in — fifteen minutes in a workshop, an awkward half hour on a scaffold in November.
There is a certification consequence as well. A window's weathertightness classification under BS 6375-1, with the air permeability and watertightness classes measured to BS EN 12207 and BS EN 12208, and any security rating held under PAS 24, are all properties of a tested configuration. That configuration either included a ventilator or it did not. Cutting one in afterwards produces a window that no longer matches the specimen the certificate was issued against, and the manufacturer will say so in writing. Thermal performance is the exception that catches people out in the other direction: whole-window U-values calculated to BS EN ISO 10077-1 account for frame and glazing and not for a ventilator, so a vented unit and an unvented one carry the same declared figure — which is not the same as losing the same amount of heat.
What a vented window head is made of
- External hood and insect mesh — clips to the weather face, keeps driven rain and insects out of the airway, and takes its own share of the declared equivalent area before any air reaches the room
- Outer frame head, slotted — the member the aperture is machined through, on a welded system before the corners are fused and clear of whatever reinforcement runs the length of the head
- Ventilator body and baffle — the airway itself; on an acoustic unit it is a labyrinth, which is why it passes far less air than a straight hole of the same cross-section CFM Ventilation Calculator
- Internal controller and flap — the only part the occupant ever touches, and the part that has to be reachable from the floor if it is going to be left open through a cold January
- Sash head, seals and sealed unit — hangs below the vented head and carries the declared thermal performance, which is calculated as though the ventilator above it were not there Window Wall Area-Weighted U-Factor Calculator
Equivalent area is a test result; free area is a measurement of a hole
Three different areas get quoted for the same ventilator, and only one of them is the number the regulation is written in. Equivalent area is defined by test: the product is measured to BS EN 13141-1, and the result is expressed as the area of a sharp-edged orifice that would pass the same airflow at the same pressure difference. It has already absorbed everything between the weather and the room — the tortuosity of the airway, the insect mesh, the external hood, whatever baffle sits inside the body. Free area, by contrast, is the unobstructed opening through the finished assembly, and geometric slot area is what a tape measure finds on the profile. Both are larger than the equivalent area of the same product, sometimes by a lot, and the gap widens on exactly the products working hardest, because an acoustic ventilator is a labyrinth and a labyrinth passes less air than a hole of the same size. Ordering against a slot dimension because it is the number visible on the fabrication drawing is the commonest way a schedule that looks compliant comes up short.
Ventilator manufacturers — Titon, Glazpart and Renson among them — publish declared equivalent area by model and by length, so the schedule should quote a model and a figure rather than a length of slot. Equivalent areas add, which gives you room to manoeuvre: two ventilators in one room sum, and a room with two windows can carry its whole provision on one of them provided somebody has decided which one. A room with a single window and a large requirement needs a longer vent or a higher-performance one, and that is a product decision taken at order time because the slot length is machined at order time.
| Figure | What it measures | Where it comes from | What it is good for |
|---|---|---|---|
| Geometric slot area | The rectangle the cutter takes out of the frame head | A tape on the profile, or the fabrication drawing | Nothing on its own — the airway narrows behind it |
| Free area | The unobstructed opening through the finished assembly | Measured, or declared by the maker | Combustion air provisions and some non-domestic work; not the Part F comparison |
| Equivalent area | The sharp-edged orifice that would pass the same air at the same pressure | A test to BS EN 13141-1 | The figure Approved Document F is written in, and the one that belongs on the order |
| Declared airflow | Litres per second through the unit at a stated pressure difference | The same test, reported the other way round | Comparing two products, and relating a vent to a whole-dwelling rate |
The extract fans are the demand, and the vents are the supply
Background ventilators and wet-room extract are one circuit, not two separate provisions that happen to appear in the same document. A bathroom fan does not create air. It moves air that has to arrive from somewhere, and in a dwelling ventilated the traditional way that air arrives through the background ventilators in the habitable rooms, crosses the landing under the doors, and leaves through the fan. Delete the vents and the fan pulls against the envelope instead — which it will do, at a fraction of its plate rating, through whatever gaps remain, and on a bad day down a flue.
The transfer path is the half nobody prices. Door undercuts are the usual provision and they are usually the first thing a new carpet removes. A fan that hit its rated flow at commissioning with the door standing open will measure far less with the door shut against a deep pile, and the same fan in the same house after a vent-free re-glaze has no supply path at all. When a homeowner reports that the new windows made the bathroom mouldy, this is nearly always the mechanism, and it is a supply failure being blamed on the extract.
So establish the demand first and then look at what is left to feed it. The extract rates themselves are tabulated figures rather than calculations — Approved Document F sets them by room in litres per second for England, and ANSI/ASHRAE Standard 62.2 does the equivalent job in North America — but knowing what volume of air each wet room is trying to turn over puts the vent schedule in proportion. A single busy wet room can be asking for more air per hour than every background ventilator in the house will pass.
Take the wet rooms one at a time and read the airflow each is trying to shift; what comes back is an air-change estimate rather than the code minimum, so use it as the size of the appetite that every ventilator you are about to delete was quietly feeding.
Different rooms have different recommended ventilation rates.
The length of the room.
The width of the room.
Floor-to-ceiling height.
Recommended airflow (CFM)
85.3 CFM
Based on general air-changes-per-hour targets, not a code-mandated minimum for your specific jurisdiction — check local building code for required bathroom/kitchen exhaust minimums.
- Room volume
- 640 cu ft
- Target air changes/hour
- 8 ACH
They open the calculator with your figures already in it
CFM Ventilation Calculator: 85.33 CFM — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 85.3 CFM — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- This sizes the airflow the room needs, not the fan you buy. Manufacturer CFM ratings are measured against a static pressure far lower than a real installation imposes, and duct length, elbows, flexible duct, the interior grille and the exterior cap all cut delivered flow. None of that is modelled here.
- This is not a code compliance check. Codes commonly set a flat minimum exhaust rate for bathrooms and kitchens, plus separate whole-dwelling ventilation rates driven by floor area and occupancy, and a small bathroom or WC will compute below those minimums. Size on whichever figure is larger and confirm it against the code your work is inspected under.
- Makeup air is not accounted for. Air pulled out has to be replaced, so a fan sized from this figure with no door undercut, transfer grille or trickle vent will move less than the number says, and in a sealed room it can depressurise the space enough to backdraft an open-flued gas or solid-fuel appliance. Combustion safety is a separate check, not something this result covers.
- The air change rate is one fixed value per room type, and only four room types exist. It does not move for the number of occupants, shower versus bath use, gas versus electric cooking, cooktop or hood width, an openable window already in the room, local humidity, or whether the fan runs continuously or on a timer.
- Room volume is length x width x height and nothing else. A sloped or vaulted ceiling, an L-shaped room, a dropped bulkhead, or a space open to an adjoining one such as an ensuite off a bedroom or a kitchen open to the dining area has no honest set of three numbers to enter, and the volume has to be worked out separately.
The airtightness test is run with every vent shut
Anyone who has watched a blower door go in knows the crew tapes things up first, and one of the things they close is every trickle vent in the building. That is not a shortcut for a faster result. The test method — BS EN ISO 9972, applied to dwellings in the United Kingdom through ATTMA Technical Standard L1, and ASTM E779 and ASTM E1827 in North America — sets out to measure the leakage of the envelope, so intentional openings are closed, and where they cannot be closed they are temporarily sealed. Extract terminals get taped over. Ventilators get shut.
State the consequence plainly, because it decides how much weight the number deserves on a window job: the airtightness result a house is handed says nothing whatever about whether it can breathe. A dwelling can test tight, satisfy whatever leakage target applies to it, and still be unventilated, because the provision that was supposed to ventilate it was excluded from the measurement by the method. Two houses at the same result can be in entirely different trouble, and only one of them has vents to open. What a genuinely tightened house then needs, and what goes wrong in it over the following winter, is the subject of the damp guide linked below rather than of this one.
Where a re-glaze is large enough to be worth measuring — a whole house, or windows bundled with insulation — a before-and-after pair is the cheapest evidence available of what the contract actually did to the fabric. Take a reading with the old windows still in, take another once the last frame is sealed and made good, normalise both against the same internal volume so they are comparable, and keep the ventilators closed on both so the comparison is like for like. A step change of several air changes at fifty pascals across one contract is unremarkable for a re-glaze, and it is exactly the size of the change that has to be handed back deliberately.
Turn each fan reading and the dwelling's volume into ACH50 so the before and the after are the same kind of number — then remember both were measured with the ventilators closed, which is why neither of them is a statement about ventilation.
The total conditioned (heated/cooled) floor area of the building.
The average ceiling height across the conditioned space.
The airflow reading from a blower door test at 50 Pascals of pressure difference.
ACH50 (air changes per hour at 50 Pa)
10.42 ACH50
Fairly leaky — typical of an older, un-air-sealed home; many energy codes target under 3-5 ACH50 for new construction.
- Building volume
- 8,640 ft³
They open the calculator with your figures already in it
Air Changes Per Hour (ACH50) Calculator: 10.42 ACH50 — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 10.42 ACH50 — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- ACH50 is leakage measured while a fan holds the building at 50 Pa, not the rate at which air actually changes in service. Real infiltration is a fraction of this figure and varies with wind, stack effect, exposure, shielding and building height, so this result is not a ventilation rate and not a number to feed straight into a heat-loss or plant-sizing calculation.
- The test behind the reading is run with trickle vents, extract terminals and other intentional openings closed or sealed, so a low result is not evidence the building is ventilated. A dwelling driven down towards the tight end without mechanical ventilation added at the same time has been sealed, not improved.
- The calculation divides whatever CFM50 you type; it does not check the reading. Temperature and wind correction on the day, a single-point reading versus a multi-point fit, pressurisation versus depressurisation, and how thoroughly the crew sealed intentional openings all move the flow figure, and none of them are visible here.
- Volume is taken as floor area times average ceiling height, and the fields only reach dwelling scale — a floor area above 1,000 m² (about 10,760 sq ft) or a ceiling above 6 m (about 20 ft) is replaced with the limit. Whether a conditioned basement, a room in the roof or the space between storeys belongs inside the tested volume is settled by the test protocol and by the two numbers you enter, so the ACH50 on a certificate for the same house can differ from this one.
- This is not a compliance check. It applies no code target, no climate zone and no certification scheme's pass mark, and it does not produce air permeability in m3/(h.m2) of envelope area, which is the figure a UK or European air-leakage test is judged against. The flow field is CFM only, so a certificate quoting m3/h at 50 Pa has to be converted before it goes in the box.
Rooms that lose their provision without anybody deciding to
The rooms that end up short are rarely the ones anyone was thinking about. A bedroom with two windows where only the rotten one is being replaced keeps the vent in the window that is staying, and is fine. The same bedroom where both go, and where the fabricator put a vent on one of the pair because the order said vents without saying how many, ends up with half the equivalent area it started with. A box room whose only opening is being changed from a side-hung casement to a fixed light for the sake of the view loses everything at once — background provision, purge, and if it was the escape window, that too.
The other reliable failure is the room that is not in the contract. A rear extension re-glazed on its own, or a front elevation done for appearance, changes some rooms and not others; the comparison is still per room, so untouched rooms simply keep what they had, and the temptation to average across the house is the error. Run the audit against the room schedule rather than against the window schedule, because the two do not have the same number of lines and it is the difference between them that hides the shortfall.
- Walk the house with the old windows still in and record, per room, every ventilator there is: window head, over-frame, wall vent, airbrick — including any that has been screwed shut or painted over.
- Mark which of those openings sits in a window being replaced and which sits in one that is staying, because only the first group is yours to lose.
- Read the declared equivalent area for each existing ventilator where the model can be identified; where it cannot, record the physical type and treat the figure as unknown rather than as zero.
- Set the required provision per room against whichever document applies in that jurisdiction, then subtract what is being kept.
- Decide which specific sash in each room carries the shortfall and put that sash's reference on the order, rather than a general instruction at the foot of it.
- Check the same rooms for purge provision and, where it applies, for escape opening, since both are decided on the same hardware schedule as the vent.
- Confirm the transfer path to the wet rooms — door undercuts measured against the finished floor level, not the screed — before the fans are recommissioned.
Purge is a separate provision and it dies on the hardware schedule
Background ventilation and purge ventilation are two different requirements met by two different parts of the same window, and a replacement can satisfy one while quietly destroying the other. Purge is the ability to clear a room quickly — after painting, after a spill, after a crowd — and in England it is normally provided by an openable window sized as a proportion of the room's floor area. The convention in Approved Document F ties that proportion to how far the window opens: a window opening 30 degrees or more is credited against a smaller fraction of the floor than one opening between 15 and 30 degrees, which has to be roughly twice as generous to do the same job.
Which makes the opening angle a ventilation input that lives on the hardware schedule rather than on the ventilation schedule. Restricted hinges, child-safety restrictors, egress hinges, and the swap from a side-hung casement to a top-hung one all change the angle or the geometry of the opening, and every one of them is normally specified for a reason that has nothing to do with air. A window ordered with restrictors to answer a safety concern at first-floor level, in a room whose purge provision was already marginal, has taken that room below provision without a single line of the ventilation schedule changing.
Escape windows are the third thing decided on the same form by the same person on the same afternoon, and they are governed elsewhere — Approved Document B for dwellings in England, Section R310 of the International Residential Code in the United States. A room can only afford to lose so many of the three, and the sash somebody wants to make fixed is frequently the one carrying the escape duty.
Same window, four different rulebooks
England, Wales, Scotland, Northern Ireland and the Republic of Ireland do not share a document here, and a fitter working across a border is working to a different rule the moment the van crosses it. England's provisions are in Approved Document F, Volume 1: Dwellings. Wales applies its own Approved Document F, which has not tracked the English revisions, so the recommended figures differ. Scotland has no Approved Document at all: the Technical Handbook — Domestic sets the ventilation standards there, and trickle ventilation in replacement windows has been an explicit expectation for longer than it has been south of the border. Northern Ireland works to Technical Booklet K, and the Republic of Ireland to Technical Guidance Document F. Get the edition as well as the jurisdiction: a merchant's standard vent, a fabricator's default and an installer's habit all lag the current document by however long it has been since anybody re-read it, and the date the work is carried out fixes which edition applies, not the date the quotation was written.
In North America the physical question is identical and the legal one is not. There is no trickle-ventilator tradition and no equivalent-area provision to match it; natural ventilation is credited through openable window area under Section R303 of the International Residential Code, and the whole-dwelling requirement, where it is imposed at all, is a mechanical one drawn from ANSI/ASHRAE Standard 62.2 and the mechanical provisions of the IRC. A window replacement there does not usually carry a ventilation obligation attached to the window — but it carries the same physics, and a house re-glazed from single-pane sashes to modern sealed units has lost the same leakage whether or not a document told anybody to give it back.
When a vent in every sash is the wrong answer
Background ventilators are the default for a naturally ventilated dwelling, not the only compliant route. A house served by continuous mechanical extract, or by a heat recovery unit supplying and extracting throughout, has a designed ventilation strategy that does not depend on apertures in the window heads, and Approved Document F recognises those strategies on their own terms. On a deep retrofit where windows, insulation and airtightness are all being done in one programme, specifying a vent in every sash and then installing a recovery unit is paying twice and letting the first purchase undermine the second — the guide on installing a heat recovery ventilator covers what that alternative actually involves.
Where the provision has to go somewhere other than the window, there are two ordinary alternatives, and both are survey decisions rather than delivery decisions. Over-frame ventilators sit in the head detail above the frame, through the cavity closer, and suit a profile system with no machining option — but they need a head detail with room in it, and that room either exists when the surveyor is standing there or it does not.
Through-wall ventilators are core-drilled, and they bring consequences the window contract does not usually price. A bore across a cavity needs a sleeve and a fall to the outside, and on a wall with a filled cavity the core is going through insulation that will afterwards be missing along the line of the sleeve.
Noise is the case where the product choice stops being a formality. Where a planning condition or a road frontage sets an internal noise target, an acoustic ventilator is specified on its rated element-normalised level difference, measured to BS EN ISO 10140-2 and rated to BS EN ISO 717-1, and it is longer, bulkier and lower in equivalent area per unit length than a standard vent. Making the area up then means a longer head or a second vent, both of which are frame decisions with a lead time. BS 8233 is where the internal targets those planning conditions are usually written against come from, and it is worth reading the condition before the window schedule rather than after.
The order line, and the certificate at the end of it
Put the ventilator on the order the way the fabricator's system reads it: against the individual window reference, naming the model and its declared equivalent area, the colour, the face it controls from, and its position along the head where reinforcement or a mullion forces it off centre. A note at the foot of the order reading all windows to have trickle vents produces the fabricator's default product at the fabricator's default length, which may be exactly right and may be half the area the schedule needed, with nothing in the paperwork to tell those two apart. Then count vented heads against the schedule while the frames are still stacked, because a frame with the wrong head is a remake and a frame already sealed into a wall is an argument — and keep the evidence afterwards, because the vent schedule, the declared areas and the room-by-room comparison are what the competent person certificate is actually asserting, and the only thing that answers the question years later when a surveyor stands in a bedroom and asks where the ventilation went.
Settle these before the cutting list is released
In the order the fabricator needs them, and all of it while the old windows are still in the wall. The workspace opens on the airtightness normalisation, seeded for a 110 m² dwelling with 2.5 m ceilings measured at 2,400 CFM50 before the work — put the post-installation reading through the same fields to see what one contract did to the envelope.
- A ventilator count per room, not per window — The comparison Approved Document F sets is room by room. Count what exists in each room, including wall vents and anything painted shut, before a single frame is measured.
- A model and a declared equivalent area, never a slot length — Equivalent area is a BS EN 13141-1 test result and it is smaller than the hole. Quote the product and the figure so the schedule can be added up.
- The sash that carries the shortfall, named on the order — Where a room has two windows, one of them takes the provision. Say which reference, or the fabricator's default decides it for you.
- Opening angle and restrictors checked against purge — Purge lives on the hardware schedule. A restrictor added for safety at height can put a marginal room below provision with no ventilation line changing.
- A blower door reading before the old windows come out — The only chance at a genuine before figure, and it costs a morning. Normalise it against the internal volume so the after reading compares.
- The transfer path to every wet room — Door undercuts against the finished floor, and the extract flow measured at the grille. Vents supply what the fans remove, and the circuit fails at either end.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.
