Chalk Before Screws
The warehouse is 46 m by 122, single storey, steel deck at nine metres to the top of the parapet. By seven in the morning there are four hundred boards banded on the deck and nobody has driven a screw. Two of the crew are walking the perimeter with a tape and a chalk box, snapping one line 3.6 m in from every edge and a second at 7.2 m, then squaring off the corners so each one carries a small box of its own. Nothing about the material changes across those lines. The same polyiso, the same cover board and the same 3 m sheet goes down inside them and outside them. What changes is how many times each of those things is attached to the building.
The reason is aerodynamic and visible on any smoke test of a building model. Wind arriving at a low parapet does not flow over the roof; it separates at the edge and reattaches somewhere out in the field, and the separated shear layer above the leading strip pulls hard on everything under it. At a windward corner the separation organises into a pair of conical vortices trailing back along the two adjacent edges, and the suction under those cores is the largest negative pressure anywhere on the building — which is why a corner is its own zone rather than the place two edge strips happen to meet.
Work out what that costs in area before deciding it is a nuisance. On this roof the interior field measures 38.8 by 114.8 m, which is 4,454 m² out of a total 5,612. The perimeter strip and the four corner boxes between them account for 1,158 m² — a little over a fifth of the roof, carrying a schedule that will not be the field schedule. Fasten the lot to the field pattern and a fifth of the roof is under-attached at exactly the places wind starts a peel; fasten the lot to the corner pattern and you have bought four fifths of a roof's worth of unnecessary screws and paid a labourer to drive every one.
The Only Dimension the Whole Layout Hangs On
Zone width has one symbol, a, from the same rule in every edition that uses it: the smaller of a tenth of the least horizontal building dimension and four tenths of the mean roof height, with a floor of four percent of the least dimension and an absolute floor of three feet. Here a tenth of 46 m is 4.6 m and four tenths of nine metres is 3.6 m, so height governed and a is 3.6 m — just under twelve feet. Put the deck at six metres instead and a drops to 2.4 m, moving the whole chalk layout.
The word least is the one that gets misread. It is the SHORTER plan dimension that sets a, so a long narrow building carries narrow zones running its entire length rather than the generous ones its footprint suggests. On an L-shaped or stepped plan take the least dimension of the rectangle enclosing the roof under consideration, and treat a roof at a different level as a separate roof with its own height and its own a — the step between two levels is an edge for the upper one and an obstruction for the lower.
Pressure comes next and the arithmetic is short. Velocity pressure at mean roof height is 0.00256 × Kz × Kzt × Kd × Ke × V² in psf, with V the mapped basic wind speed in mph at the building's risk category. For components and cladding the directionality factor Kd is 0.85, and an enclosed building carries an internal pressure coefficient of plus or minus 0.18 added to whatever external coefficient you read. On this roof — 115 mph, Exposure C, nine metres to the deck — Kz works out near 0.98 and the velocity pressure near 28 psf, about 1.35 kPa, the same everywhere on the roof.
What is not the same everywhere is GCp, and this site does not supply it. It is read from the components-and-cladding figure in the code edition your jurisdiction has actually adopted, against roof form, slope, zone, and the effective wind area of the thing being held down — which for a single fastener and its plate is a small area and therefore a large coefficient. Editions differ in how finely the low-slope figure is cut: older ones give three zones, newer ones subdivide the edge and the corner further and add an interior zone for very large roofs. Read the figure you are held to, not the one you memorised. The corner coefficient on any of them is a multiple of the field value, not a few percent above it.
One more conversion decides whether the schedule is right or off by a factor. Wind pressures from ASCE 7-10 onward are strength-level, and the 0.6 in the allowable-stress load combinations is what brings them down to the level a service-load capacity is compared against; mixing the two silently halves or doubles a fastener count. Kzt is the other quiet one — taking it as 1.0 is correct on flat ground and wrong on a hill, a ridge or an escarpment, where speed-up is a separate calculation.
- Establish mean roof height and the least plan dimension from the drawings, then confirm both on site — a re-roof that has already gained 150 mm of build-up is taller than the record set.
- Compute a, and double it; those are the two offsets you will chalk.
- Snap the a line continuously around the whole perimeter, inside the base flashing, before any board is placed.
- Square the corner boxes off both adjacent edges rather than mitring them, and mark each with a paint dot the boards will not hide.
- Mark every curb, hatch, skylight and equipment stand in the field — each is a local edge in its own right.
- Photograph the chalked roof from each corner — once insulation covers the lines, those frames are the only record.
Height, least dimension and exposure resolve into the zone width you are about to chalk and the velocity pressure the coefficient multiplies — run it before the tape comes off the reel, not after the boards are placed.
The mapped basic wind speed for the site, at the risk category of the building.
The terrain roughness upwind of the building, over the distances the code specifies.
Average of eave height and ridge height, measured from grade.
The shorter of the building's two plan dimensions.
The pitch of the roof plane being checked, in degrees.
Read from the components-and-cladding figure in your adopted code, for this zone and effective area.
Design uplift pressure in the selected zone
30.5 psf
The external pressure coefficient is the value you entered, not one this page supplies, so the answer is only as good as the figure you read off. This is a low-slope roof, so the low-slope coefficient figure applies and the corner zone wraps the full perimeter corner. The topographic factor is taken as 1.0, which is wrong on a hill, a ridge or an escarpment.
- Velocity pressure at mean roof height
- 25.82 psf
- Velocity pressure exposure coefficient
- 0.9 (Kz)
- Internal pressure component included
- 4.65 psf
- Corner and edge zone width, measured in from each roof edge
- 3.9 ft
- Corner zone plan area at each corner
- 15.21 ft²
They open the calculator with your figures already in it
Roof Uplift Zone Pressure and Zone Width Calculator: 30.46 psf — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 30.5 psf — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- Enclosed building assumed. A partially enclosed building carries a much larger internal pressure coefficient and a building with a large dominant opening larger still.
- Kzt = 1.0 assumed. Speed-up over a hill or an escarpment can raise the pressure by half again, and that is a separate calculation.
- Gives pressure, not fastener spacing. Turning pressure into a clip or fastener layout needs the tested assembly's own rated resistance and its safety factor.
What the Wind Is Actually Pulling Apart
Uplift does not act on a roof; it acts on a chain of connections, and the chain is only as strong as the interface that lets go first. Suction on the membrane is carried across the sheet to the nearest row of stress plates, out of the plate into the screw head, down to its threads, and out of the threads into the top flute of the steel deck. Then it goes on — deck to joist, joist to beam, beam to column, column to foundation. A roofing contractor owns four of those links and inherits the rest.
Each link fails in its own way and the modes look nothing alike. A screw pulls out of a thin deck flute. A plate pulls through the membrane and leaves a neat torn ring. A sheet tears between two plates when the row spacing was widened past what the seam supports. An adhered board debonds cleanly from its primer. On a torn-off roof the mode tells you which link was weakest, and it is worth reading before the tear-off crew loses the evidence: a roof that lost plates through the sheet needs a different fix from one where every screw still stands proud of a deck it stripped out of.
The chain a stress plate sits in the middle of
- Single-ply membrane sheet — sheet width is the row spacing, so narrowing sheets in the perimeter and corner changes the roll count as well as the fastener count EPDM Single-Ply Roofing Roll Calculator
- Screws and stress plates — the link that carries every square metre of suction between two rows into a single point of steel deck
- Cover board — spreads the plate load, keeps hail and traffic from printing every insulation joint, and is what the membrane is bonded or fastened to Roof Insulation Cover Board Calculator
- Roof insulation boards — carries the thermal duty and nothing structural; a board that has taken water has lost the compressive strength the plate needs under it Foam Board Insulation Calculator
- Fluted steel deck — gauge and flute width decide what a screw can hold and how much freedom the layout has to land plates where the pattern wants them Steel Deck Support Beam Spacing Calculator
A Rating Belongs to an Assembly, Never to a Screw
There is no such thing as a fastener rated for a wind pressure. There are assemblies rated for one, and a fastener is a component of an assembly along with the deck it goes into, the board it goes through, the plate on top of it, the sheet over that, and the spacing of every one of those. FM Approvals Standard 4470 is the approval standard that puts single-ply, modified bitumen, built-up and liquid-applied assemblies through that test; UL 580, Tests for Uplift Resistance of Roof Assemblies, and UL 1897, Uplift Tests for Roof Covering Systems, are the other two names that appear on submittals. ASTM E907 covers field uplift testing of adhered membrane systems on a roof that already exists.
Read the listing itself rather than the marketing sheet quoting it. It names the deck type and minimum gauge, the fastener and plate by model, the board type and thickness, the adhesive or fastening density, and the maximum spacing at which the whole thing held. Substitute any one and the number on the submittal no longer describes what is on the roof. The commonest substitution is the deck: an assembly listed over 22-gauge is not the one you built over 24-gauge, and a plate landing in a narrower flute has less steel around the thread than the test gave it.
The relationship between what an assembly held in a laboratory and the pressure it is rated for is set by the approval standard, not by the contractor and not by the specifier. Do not derive it — look the assembly up in the listing database the approval body publishes. Where the project is insured to a particular carrier's standards, look it up there instead: FM Global Property Loss Prevention Data Sheet 1-28, Wind Design, and Data Sheet 1-29, Roof Deck Securement and Above-Deck Roof Components, decide what an FM-insured warehouse is allowed to have on it, and they are stricter than the building code in places where a loss history taught them to be. ANSI/SPRI WD-1, Wind Design Standard Practice for Roofing, is the corresponding trade standard where no carrier is imposing one.
Rows, Not a Grid
A mechanically attached single-ply roof is not fastened on a grid, and picturing it as one leads to the wrong takeoff every time. The fasteners live in the seam. A sheet is rolled out, its edge is fastened in a straight row through the lap, and the next sheet is laid over that row and welded or taped to it, which means the plates are buried under the weld and the exposed field of every sheet carries no fasteners at all. Row spacing and sheet width are therefore the same number, and choosing one has chosen the other.
That is what makes zone enhancement a layout decision rather than a fastening decision. To tighten the pattern in the perimeter you do not add screws to a 3 m sheet; you cut the sheet down — to two metres, or to half width, or to whatever the manufacturer's wind table names for the pressure you computed — and you get more rows because you have more seams. Fasteners within the row are spaced at the table's figure as well, and the two together give the density the assembly was listed at. Set the corner sheets out first, while the roof is still empty; they are the fiddliest on the job and the ones a tired crew fudges.
Cutting sheets changes the material order in two directions at once. Narrower sheets mean more linear metres of seam for the same area — more weld time or more tape, and offcuts unless the sheet is a stock half-width — and they mean the roll count for the perimeter strip is not the roll count for the same area of field. Work the layout against the real roof geometry, the curbs and drains and equipment stands, rather than against a bare area figure.
Two habits sit behind most mechanically attached failures that are not design failures. The first is the screw set at the wrong depth: overdriven, the plate dishes and cuts the sheet at its rim; underdriven, it stands proud and telegraphs, and every foot that lands on it works the fastener loose. Set the gun's depth on a test board each morning and again when the deck warms. The second is a row that drifts off the flute — a line that wanders half a flute over twenty metres has a run of fasteners hanging in a void with a satisfying driven torque and nothing holding them.
Sheet width is the row spacing, so the roll count and the fastener pattern are one decision — settle it here against the roof you actually measured, then read the perimeter and corner strips as separate areas with their own sheet width.
The total roof area to be covered with EPDM membrane.
The area a single roll of EPDM membrane covers.
EPDM rolls needed
5 rolls
They open the calculator with your figures already in it
EPDM Single-Ply Roofing Roll Calculator: 5 rolls — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- The same roll count buys any thickness. EPDM is stocked at 45, 60 and 90 mil, reinforced and unreinforced, and thickness is what the warranty term and the hail and foot-traffic tolerance key off. The area arithmetic is identical for all of them, so this figure cannot tell you the wrong sheet came off the truck.
- Says nothing about what holds it down. Fully adhered, mechanically attached and ballasted roofs need different quantities of bonding adhesive, plates and fasteners or ballast, and that density rises sharply in the perimeter and corner zones set by wind uplift on the particular building. Those lines are usually the larger part of the order and none of them follow from area.
- Roll width decides how much seam the roof has. Covering the same area in wider sheets roughly halves the length of field seam, and seams are where single-ply roofs leak — entering a bare coverage area hides that trade-off completely.
The Boards Under the Sheet Keep Their Own Schedule
Insulation and cover board have a fastening density of their own, and it is not the membrane's. It is expressed as fasteners per board, and it steps up in the perimeter and corner exactly as the membrane's does — a fact that gets lost because the boards go down first, before anyone is thinking about wind, and because the person placing them is not the person who read the wind table. Give the board crew the same chalk lines and the three patterns drawn on a board offcut nailed to the parapet, in pictures rather than numbers.
Board layout interacts with the zone lines in a way the membrane's does not. A 1.2 by 2.4 m board straddling the a line is in two zones, and there is no such thing as fastening half a board to one pattern: take the higher pattern for any board crossing a line, or set the layout out so joints fall on the line. Where the assembly is two layers, keep joints in the upper layer off the joints in the lower — a coincident joint through both is a hinge running straight down to the deck, and it is where a corner starts to lift.
Where the insulation is adhered rather than fastened, ribbon spacing is the equivalent variable and it closes up in the same zones. Adhesives bring constraints fasteners do not: a minimum substrate temperature, a maximum open time, a flatness tolerance on the deck, and a requirement that the board is walked in while the adhesive grabs. A ribbon layout applied to a dusty or damp board is the one attachment method that can look perfect and hold nothing, because there is no torque reading and no plate to inspect — which is the case ASTM E907 exists to settle on a finished roof.
Board count is what the per-board fastening pattern multiplies into a plate order, so it is worth having the sheet count for the field, the perimeter and the corner as three separate figures rather than one.
The total roof area to be covered with cover board.
The coverage area of a single cover board sheet.
Cover board sheets needed
51 sheets
They open the calculator with your figures already in it
Roof Insulation Cover Board Calculator: 51 sheets — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- Counts boards and nothing that holds them down. In many assemblies one screw and plate passes through the cover board AND the insulation beneath it in a single shot, so the fastener length is set by board thickness plus the whole insulation stack plus the embedment the deck needs, and that fastener quantity belongs to the stack rather than to this layer. A board count on its own will not tell you whether you are buying one set of fasteners or two.
- Board thickness and type are not asked, and the sheet count comes out identical whichever you pick. What the board has to be — gypsum, HD polyiso, cement board, mineral — is set by the assembly's fire and hail classification and by what the membrane above it has to bond to, and those are the decisions carrying the cost difference between two roofs of the same area.
- An adhered installation is not ordered by sheet count at all. Adhesive goes on by coverage rate — a volume per unit of area, or ribbon spacing across each board, tightened at the perimeter and corners — so the pail count follows that rate and the zone layout, and it does not track the number of boards.
The Deck That Breathes Underneath It
Watch a mechanically attached roof in a gale and it billows between the rows, lifting into a series of long pillows and dropping back. Some of that is unavoidable and the assembly is tested with it. What makes it worse than it should be is air moving up through the building into the space under the membrane, because every unsealed deck side lap, every open flute end at a wall, and every un-firestopped penetration is a path for interior air to pressurise the underside of the sheet. Internal pressure adds to external suction; it does not average with it.
So the air barrier is part of the uplift design, not part of the energy package. Seal the deck laps and the flute ends at every perimeter and interior wall, tie the vapour retarder to the wall air barrier, and keep the roof's air seal continuous around every curb and pipe. FM Global Data Sheet 1-29 treats deck air leakage explicitly for this reason, and on a warehouse with tall stack effect and roll-up doors on one elevation the effect is not marginal. The building is a pressure vessel with a flexible lid; the tighter the vessel, the less the lid has to hold.
Where the Field Stops Being the Field
Almost every membrane blow-off begins at an edge and almost none in the middle of a field. The mechanism is peel: once wind gets under a free edge it lifts a strip, and the strip acts as a lever on the next row of fasteners, so each row unzips at a fraction of the pressure the assembly resists in tension. Everything at the perimeter is doing one job — denying the wind an edge to start on — so treat the base flashing, the termination bar, the nailer and the edge metal as one detail with four parts.
At a parapet the membrane turns up the wall and terminates on a bar, the last mechanical hold before the flashing becomes a free edge. Manufacturers publish a bar spacing in their own schedule, commonly 300 mm on centre and closer where the wind table calls for it. Count honestly: the run needs one fastener at each end as well as one per interval, splices between bar lengths need their own pair, and corners need fasteners either side of the break rather than one at the mitre. Type follows the wall — masonry anchors into block, self-drillers into steel, a lag into the nailer where the detail lands on timber.
Where there is no parapet, the membrane wraps over the edge onto a nailer under fascia or a gravel stop, and the assembly falls under ANSI/SPRI ES-1, Wind Design Standard for Edge Systems Used with Low Slope Roofing Systems. The model building code adopts ES-1 for perimeter edge securement on low-slope roofs, with the local amendment deciding the edition. A tested edge system is a fascia and a continuous cleat together, sized for the face height in front of them — so a re-roof that thickened the build-up has a taller face than the old metal was tested at, and that metal does not come back on however sound it looks from the ground.
The nailer is the part nobody checks and the part that fails quietly. It has to be anchored for the same uplift the metal above it resists, its fastening has to reach the wall or the deck's supporting member rather than the deck sheet, and its withdrawal capacity in timber is what the whole edge hangs from. Where the roof gained thickness the nailer gained courses, and stacked boards need fastening to each other as well as to the wall: a three-course nailer lagged only through its bottom board is an edge detail waiting to leave in one piece.
Bar spacing is the manufacturer's number and the count is arithmetic on it, but the arithmetic is where the ends, the splices and the corners get forgotten — put the measured run in and add those three by hand.
The total length of termination bar to be fastened.
The on-center spacing between fasteners along the bar.
Fasteners needed
170 fasteners
They open the calculator with your figures already in it
Roof Membrane Termination Bar Fastener Calculator: 170 fasteners — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- Assumes one continuous run. The +1 end fastener is added once, so a perimeter broken into separate runs by corners, upstands or penetrations needs one extra fastener per additional run — six runs are five fasteners short of this figure.
- The spacing is the figure you entered, not the figure the membrane system requires. Most manufacturers tighten fastener spacing in the corner and perimeter zones, where wind uplift is highest and where a bar pulling away starts the failure.
- Nothing about the fixing itself. The count does not say whether the fastener suits a concrete, timber or metal deck, nor whether it develops the pull-out value the assembly needs.
- No allowance for a re-drill. A hole that misses the deck or lands in a joint costs a fastener and is normal on a real roof.
Held Down by Weight Instead of Thread
Not everything on this roof resists uplift with a fastener. A ballasted single-ply system holds the sheet down with stone or pavers, pedestal pavers sit loose on the membrane, and a ballasted photovoltaic array is held entirely by its own mass and its friction on the roof surface. ANSI/SPRI RP-4, Wind Design Standard for Ballasted Single-ply Roofing Systems, governs the first of those, and it does what the fastening tables do: it increases the ballast at the perimeter and again at the corners, and it sets a height and an exposure above which ballast is not acceptable at all.
Scour is the failure mode, and it is why the corner increase is not optional. Wind crossing gravel at the edge lifts the smallest stones first, and once a patch is bare the sheet under it is exposed and the surrounding ballast has lost its edge restraint. On a paver roof the equivalent is one lifted paver that becomes a missile with a whole warehouse of run-up. Any loose-laid system needs its perimeter courses heavier, larger or mechanically restrained, and the roof needs a maintenance instruction saying so — the person redistributing ballast around a new curb in five years will not have read RP-4.
A rooftop array adds a question the roofing scope does not usually own. Ballast holding an array down is dead load the deck and joists have to carry, concentrated at the array feet rather than spread, and it lands in the same corner zone where the roof already needed its heaviest attachment. Wind on an array is not the same load case as wind on a bare roof either — ASCE 7 carries its own provisions for rooftop solar panels, and tilt, row spacing and setback from the edge all change the answer. Settle the ballast figure and the structural check together, before anything is craned up.
Ballast mass follows the uplift pressure and the array area with a safety factor on top, and the number it returns is a dead load somebody has to sign off as well as a wind restraint.
The design wind uplift pressure acting on the array, from your wind load analysis.
The total plan area covered by the solar panel array.
A multiplier applied to the calculated uplift force to account for uncertainty in wind loading and ballast performance.
Required ballast mass
20,300 lb
This is a simplified whole-array tributary calculation — actual ballast distribution requires a location-specific wind uplift analysis per ASCE 7 (uplift varies significantly by roof zone: field, perimeter, and corner), typically performed by the racking manufacturer's engineer for the final layout.
- Total wind uplift force
- 13,533.76 lbf
They open the calculator with your figures already in it
Solar Panel Roof Mount Wind Uplift Ballast Calculator: 20,294 lb — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
What this calculation does not cover
- The uplift pressure is applied uniformly across the whole array footprint and the answer comes back as one total mass. It carries no distribution: corner and perimeter modules see far higher uplift than modules in the field of the roof, so spreading this total evenly leaves the edges light and the middle heavy.
- No credit is taken for the weight of the modules, rails and racking, which already resist uplift. A real ballast schedule subtracts that self-weight before sizing blocks, so this figure is the mass required as if the array weighed nothing rather than the mass of concrete to add on top of the hardware.
- Only vertical lift-off is checked. Wind also drives the array sideways and can rotate a row about its downwind edge, and both depend on friction between the ballast pads and the roof surface and on how well the array is tied together as one block — none of which is entered here.
- The roof structure is not checked. Ballast is permanent dead load concentrated under the trays, and nothing here confirms the deck can carry it alongside snow and the array's own weight, or that the point loads stay within the deck's capacity.
- The uplift pressure is an input, not a result — nothing derives it from wind speed, exposure, building height, parapet, roof zone or module tilt, and the answer scales directly with whatever figure you type. The safety factor is a plain multiplier, not a code load combination, so this is a sizing check and not the stamped ballast design a ballasted array normally requires.
What Gets Written Down Before the Sheet Covers It
The deck is the one variable nobody can verify from a drawing, and it is the one the whole schedule rests on. Test it. ANSI/SPRI FX-1, Standard Field Test Procedure for Determining the Withdrawal Resistance of Roofing Fasteners, is the field pull test for exactly this, and a set of pulls across the roof at the start of the job is the only way to find out that a 1970s deck is thinner than the record drawings claim, that a section over the old office has a different gauge, or that a bay has corroded from a leak nobody reported. Pull in the corners as well as the field — that is where the answer matters most and where the deck has usually had the worst of the weather.
Then record what was built, zone by zone: the chalked roof, each zone's fastener layout with a tape in frame, the fastener and plate model numbers off the carton, the depth setting on the gun, the FX-1 results, and the listing number of the assembly the submittal claimed. That file is what an insurer asks for after a storm and what a warranty claim turns on, and it takes one person twenty minutes a day.
Work the perimeter safely while doing all of it, because the zone needing the most attention is the strip nearest the drop. OSHA 29 CFR 1926 Subpart M covers fall protection on this work, and the corner boxes are chalked, boarded, fastened and flashed with a crew within a few metres of an unprotected edge throughout. Set the warning lines or the guarding out before the tape comes off the reel, not once the material is on the roof and there is nowhere left to stand.
| Zone | Where it is | What the schedule changes |
|---|---|---|
| Field | Inboard of the a line on all four sides | Baseline sheet width, baseline row and in-row spacing, baseline board pattern |
| Perimeter | The strip a wide around the whole roof edge | Narrower sheets giving more rows, tighter in-row spacing, higher per-board pattern |
| Corner | A box of side a at each corner of the enclosing rectangle | The tightest of the three layouts, set out first while the roof is empty |
| Around curbs and units | Locally at every raised obstruction in the field | Local edge treatment regardless of which zone the curb stands in |
| The edge itself | Base flashing, termination bar, nailer, fascia or coping | Tested edge system, not a fastener count — sized to the finished fascia face height |
| The deck below all of it | Everywhere, and unverifiable from the drawings | Nothing, until a field pull test says the assumed withdrawal value is real |
Pricing a roof that is fastened three different ways
Take the roof off as three areas and one perimeter, not as one number. Everything below is quantified separately for the field, the perimeter strip and the corner boxes, because that is how it will be installed and how it will be inspected.
- Zone width a, and the three areas it produces — Least plan dimension and mean roof height give a; the interior field is the plan less 2a on every side, and what is left is the perimeter and the four corner boxes.
- Membrane rolls at three different sheet widths — Sheet width is the row spacing, so the perimeter and corner strips consume rolls at a different rate per square metre than the field does — and generate more seam with them.
- Seam length by zone, in linear metres — More rows means more weld or more tape; the increase lands as labour hours on the same days the corner sheets are being set out.
- Insulation and cover board fasteners at three per-board patterns — Board count times the pattern for the zone that board sits in, with any board crossing a chalk line taking the higher pattern.
- Termination bar and its fasteners around the whole perimeter — Bar by the measured run plus waste; fasteners at the manufacturer's spacing plus the ends, the splices and both sides of every corner break.
- Edge metal as a tested system, and the nailer under it — Fascia and continuous cleat sized to the finished face height, with nailer courses and their anchorage counted separately from the metal.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.
