Facade

Stopping Condensation on a Curtain Wall

The glass can be bone dry while the mullion beside it runs with water. Condensation finds the coldest room-side surface, and that is nearly always the frame.
  • 20 minReading time
  • 12Sections
  • 4Calculators inline
  • Last reviewed

Dry Glass, Wet Aluminium

First hard frost after handover, seventh floor, north-west corner. Facilities has folded a paper towel onto the window board beneath the corner mullion because water has been tracking down the aluminium since about six in the morning, and by nine there is a stain on the carpet tile. The glass on both sides of that mullion is perfectly clear. Somebody has already taken a photograph, because glass is what you photograph when you believe you have a condensation problem, and the photograph shows nothing worth looking at.

The complaint will nonetheless be logged as sweating windows, and the first document anybody pulls will be the glass certificate. That is the wrong half of the wall. The vision glass and the frame holding it are two separate surfaces facing the same room, exposed to the same outdoor temperature, and separated by a factor of two or more in thermal transmittance. Each has its own room-side surface temperature, and moisture leaves the air at whichever of them is colder. On a framed facade that is the frame: at the mullion face, at the transom, along the perimeter and hardest of all in a corner, where two cold members meet and the air moves least.

So a first-rate insulating unit in a second-rate frame is a bay that runs with water while every certificate in the file passes. Sorting it out means treating the frame as a component with its own number, finding where the room's dew point actually sits, and knowing which of several quite different waters is on the wall — because some of them are not room-side condensation at all.

The Number in the Energy Submission Is an Average

Fenestration is rated as a whole product. NFRC 100 combines the centre-of-glass, edge-of-glass and frame contributions into one area-weighted U-factor for the assembly, and that single value is what the energy submission needs, what ASHRAE Standard 90.1 sets a limit against, and what appears on the drawing schedule. It is a perfectly good number doing a perfectly good job, and it is the wrong number for this page. An average describes no surface in the bay. Condensation is a local minimum problem, and averaging a good component with a poor one produces a figure that flatters the poor one and slanders the good one in a single stroke.

The composite is still worth working out, because what you want from it is the split rather than the total. A bay coming out a little over 1.8 watts per square metre kelvin might be glass at 1.4 across four-fifths of its area and frame at 3.5 across the rest. Nothing about the 1.8 says condensation is coming; the 3.5 says it immediately, and it is the number the surface check further down this page needs. Take the frame area off the shop drawings rather than the elevation — the opaque width at a mullion includes the pressure plate and the cap.

Feed it the two component U-factors and the two areas and it returns the assembly figure the energy model wants — but read it backwards for this job, because the interesting output is how far apart the two inputs were and which one is carrying the bay.

The center-of-glass (or whole-glass) U-factor for the glazing component.

The total visible glass area in the window wall assembly.

The U-factor for the frame/mullion component, typically higher (less insulating) than glass.

The total opaque frame/mullion area in the window wall assembly.

Composite area-weighted U-factor

0.3769 BTU/(hr·ft²·°F)

High confidence

Add the equipment this sizes

This result is a specification — 0.3769 BTU/(hr·ft²·°F) — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

What this calculation does not cover

  • The assembly is split into two areas here, glass and frame, while the NFRC method the source names uses three: centre-of-glass, a 63.5 mm (2.5 in) edge-of-glass band where the spacer and sealant conduct around the perimeter of each lite, and frame. Entering a centre-of-glass U-factor across the whole glass area therefore averages that colder band in as though it were centre glass, and the composite lands lower — better — than the rated whole-window U-factor for the same product.
  • Nothing checks that the glass area and the frame area actually tile the opening. Taking the frame area from the outside frame footprint while the glass area comes from the daylight opening double-counts the overlap and pushes the composite up; missing a mullion, a transom or a stack joint leaves that area out and pulls it down. Neither mistake raises an error, because the two figures are only ever used as weights against their own sum.
  • Area weighting does not capture thermal bridging. The anchors, brackets and the slab-edge and head-and-sill details that tie a window wall back to the structure conduct around both of the areas entered here, and they are quantified by a linear psi-value or a two-dimensional thermal model rather than by an average of two U-factors.
  • The output is a conduction rating, not a heat loss and not an energy performance figure. It is computed in W/m²K and restated as BTU/(hr·ft²·°F) when the page is set to US units, while the two U-factor boxes above stay in W/m²K whichever way that switch is set. Multiply it by the assembly area and the design temperature difference to get watts, and handle solar separately, since gain is governed by SHGC and shading — a low composite U-factor says nothing about overheating on a west elevation. Air leakage through the perimeter seal and the joint to the slab is outside the rating as well.
  • An area-weighted average is a mean, and condensation is a local event. The sight line, the spacer and the frame itself all run colder than the composite figure implies, so an assembly that meets a U-factor target can still run wet at the glass edge; that question needs the manufacturer's condensation resistance figure or a thermal model of the actual profile.

Run the Surface Check Twice, Once Per Component

The steady-state check behind AAMA 1503 and NFRC 500 is short enough to do on the back of a drawing. The room-side surface temperature is the interior air temperature less the heat crossing the assembly divided by the interior air film conductance: Ts = Ti − U × (Ti − To) ÷ hi. Three of those four inputs are conditions rather than products. Only U belongs to the thing on the wall, which is exactly why the calculation has to be run once with the glass U-factor and once with the frame U-factor rather than once with a blend of the two.

Take a winter design condition of minus ten outside, twenty-one inside, and the conventional interior film conductance of 8 W/m²K. A double unit with a soft coat and argon, whole-glass U around 1.4, lands its room-side surface at about 15.6 degrees. The thermally broken aluminium mullion beside it at 3.5 lands at about 7.4. Those two surfaces are eight degrees apart in the same bay under the same weather. If the room is sitting at fifty per cent relative humidity its dew point is a little over ten degrees, which puts the glass five degrees clear and the frame three degrees under. That is the paper towel on the window board, predicted a year before anyone laid it there.

Two published indices describe the same behaviour and they are not interchangeable. AAMA 1503 measures a condensation resistance factor in a test chamber and reports the frame and the glass separately, precisely because the two do not behave alike — the lower of the pair is the one that governs the bay. NFRC 500 produces a single simulated condensation resistance index for the whole product on a scale of one to a hundred, computed under ISO 15099 with tools such as LBNL THERM and WINDOW. Both are useful for ranking products against each other. Neither is a temperature, neither can be compared across the two scales, and neither answers the question of whether this bay in this room at this humidity will be wet on Tuesday. For that you need the surface temperature and the dew point in the same units.

One boundary worth noticing: the checker below stops at a U-factor of four. That ceiling is a statement rather than a limitation. A frame with no thermal break at all runs somewhere between five and seven, its room-side face lands within a degree or two of the outdoor air, and it does not need a calculation — it needs replacing, or it needs the interior conditions changed around it. Nothing in a steady-state check will rescue a raw aluminium extrusion running from outside to inside.

  1. Pull the frame U-factor and the glass U-factor as two separate figures from the system supplier's simulated or tested data, not the single assembly number off the schedule.
  2. Take the outdoor design temperature from climatic design information for the site — the 99 per cent or 99.6 per cent winter condition — rather than a record low.
  3. Fix the interior design temperature from the mechanical brief, and then fix it again for whatever the space actually does overnight and at weekends.
  4. Establish the dew point of the interior air from its temperature and relative humidity, using measured humidity if the building is occupied and the design intent if it is not.
  5. Run the check on the glass, then run it again on the frame, and compare both against that dew point.
  6. Repeat the frame run with a reduced film conductance for any bay that will spend its winter behind a blind, behind a screen or under a sill unit that gets switched off.

Put the frame U-factor in first rather than the glass one — the pass it gives you on the glass is the pass everybody already assumes — and treat the result as a temperature to be compared, not a verdict to be filed.

The interior air design temperature used for the winter condensation check.

The exterior winter design temperature for the project location, typically a 97.5% or 99% design condition.

The overall U-factor of the spandrel/vision glass assembly being checked.

The interior air film coefficient, commonly taken as 8 W/m²K per standard convention.

The dew point of the interior air, based on its temperature and relative humidity.

Interior glass surface temperature

57.2 °F

ComparisonA comparison, not a check — no result here is an approval.

The calculated interior glass surface temperature stays above the interior air's dew point shown below, so condensation is not predicted under these steady-state design conditions. This checks room-side vision/spandrel glass surface condensation risk only, per NFRC 500/AAMA 1503 steady-state methodology. Shadowbox CAVITY condensation — a distinct, common failure mode driven by trapped cavity moisture and solar vapor drive behind the spandrel panel — is NOT covered here and needs separate ventilation/vapor analysis per GANA/NGA guidance. No risk predicted under these conditions is not the same as none. The conditions are the ones you entered, and one surface is not the assembly.

Interior air dew point
50 °F

What this calculation does not cover

  • Models conduction only. Warm indoor air pushed out through an imperfect air seal — a splice joint, an anchor pocket, a gasket that has taken a set — carries far more moisture into the assembly than diffusion does, and it condenses wherever it cools rather than on the face being checked. A wall that passes on paper can still run with water, or ice, inside the mullion, and the first sign of it is usually a stain at the head of the panel below.
  • Uses the exterior air temperature, and the outer surface does not sit at it. On a clear, calm night the glass radiates to the sky and settles several degrees below the surrounding air, which drags the interior surface down with it — and those are exactly the nights condensation forms. A result that clears the dew point by a degree or two at the design air temperature has no margin left for the sky.

The Dew Point Belongs to the Occupants

Everything above the line in that calculation is fixed by the facade and the weather. The line itself is fixed by the people inside, and it moves without anybody telling the facade team. Dew point is a function of the air's moisture content alone: raise the temperature of a room and the dew point does not follow, but add moisture — from occupants, from a humidifier commissioned to protect a timber floor or a server room, from a kitchen, from a pool, from a wet trade still drying out on the floor above — and it climbs immediately. The psychrometrics chapter of the ASHRAE Handbook — Fundamentals is where the relationship is set out properly, and CIBSE Guide A carries the equivalent design conditions in British practice.

The table below runs the arithmetic in the direction that is actually useful on a facade job. Start with the humidity somebody wants to hold in the space, read across to the dew point that implies, and read across again to the highest frame U-factor that keeps a room-side face above it on a minus-ten morning. It is an uncomfortable table for anyone who has been told that a humidified building and a standard commercial framing system can share an elevation. The two right-hand columns are the whole argument between the facade consultant and the mechanical engineer, written out before it happens.

Interior humidity at 21 °C, and the frame it demands at a −10 °C design condition
Relative humidity held in the spaceDew point of that airHighest frame U-factor that stays above itWhat that means to specify
30%about 2.8 °Cabout 4.7 W/m²KAlmost any thermally broken frame clears it. This is a dry winter office with no added humidification.
40%about 6.9 °Cabout 3.6 W/m²KA modest polyamide break is enough. Corners and transom junctions still want checking individually.
50%about 10.2 °Cabout 2.8 W/m²KA good break, a warm-edge spacer and a glazing pocket detailed to match. Blinds start to matter here.
60%about 12.9 °Cabout 2.1 W/m²KHigh-performance framing, verified by simulation for the actual profile rather than taken from a catalogue range.
70%about 15.3 °Cabout 1.5 W/m²KNot a frame U-factor a standard commercial system reaches. The humidity comes down, or the surface gets warmed deliberately.
Interior humidity at 21 °C, and the frame it demands at a −10 °C design condition

One Number That Travels Between Jobs

There is a tidier way to carry a frame's condensation behaviour around than a surface temperature, because a surface temperature is only true for the pair of design temperatures it was worked out at. Rearrange the same equation and the design temperatures cancel: the temperature factor at the internal surface is f = (Ts − To) ÷ (Ti − To), which reduces to f = 1 − U × Rsi, where Rsi is the interior surface resistance — the reciprocal of that film conductance. The frame at 3.5 with a film conductance of 8 has a temperature factor of 0.56 whatever the weather does. The glass at 1.4 has 0.83. Those two numbers describe the components rather than the day, which is why they are the ones worth writing on a drawing.

BS EN ISO 13788 is the document that formalises this, and it is the route most European specifications take to a condensation requirement: it sets out how to derive the internal surface temperature needed to avoid critical surface humidity, and for OPAQUE surfaces it deliberately assumes a more onerous interior surface resistance than the value used for heat loss calculations — 0.25 m²K/W (1.42 hr·ft²·°F/BTU) against the 0.13 (0.74) of BS EN ISO 6946 — to stand for the still air behind furniture and curtains and in corners. For windows and doors, frames included, it keeps the ordinary 0.13, so a frame is assessed close to the 0.56 above. The onerous film belongs to an opaque element such as a spandrel panel, where 0.8 W/m²K (0.14 BTU/hr·ft²·°F) is a factor of 0.90 with the ordinary film and 0.80 with the onerous one. BRE Information Paper IP 1/06 sets threshold factors by building type, dwellings more demanding than offices and retail and pool halls more demanding again; take the threshold from the document for the building in front of you, because the values differ by more than the margin most frames have.

The factor this section describes, from a component's U-value and the surface resistance it is assessed with — the frame at 3.5 W/m²K (0.62 BTU/hr·ft²·°F) with a film conductance of 8 (1.4) comes back at 0.56 — or from a surface temperature read on the wall, with BRE IP 1/06's critical factor for the building type beside it.

A flat wall or roof away from junctions follows from its U-value; a junction needs a surface temperature from a model or a measurement.

The element's thermal transmittance, surface resistances included.

The surface film the factor is worked with — larger than the one used for heat loss, on purpose.

The room's temperature — strictly the operative temperature, the mean of the air and the surrounding surfaces.

The outdoor air temperature for the day or month being assessed.

BRE IP 1/06 sets a critical factor by the humidity the building's use generates.

Temperature factor fRsi

0.925 ratio

High confidence

For a plane element the factor is 1 − U × Rsi, whatever the weather: the temperatures only place the surface temperature on the day. The factor is at or above the 0.75 BRE IP 1/06 gives for dwellings, residential buildings and schools.

Surface temperature at these air temperatures
65.3 °F
Critical factor for this building type (BRE IP 1/06)
0.75
Surface temperature the critical factor corresponds to
59 °F

What this calculation does not cover

  • From a U-value the factor holds for a plane element only. Junctions, lintels, window reveals and corners conduct in two or three dimensions and need a model to BS EN ISO 10211, or a measured surface temperature.
  • The critical factors are BRE's, derived for the internal humidity each building type is expected to generate; a building used more humidly than its type needs its own assessment to BS EN ISO 13788.
  • The factor is about the surface: it says nothing about condensation between the layers of the construction, which BS EN ISO 13788's interstitial method assesses separately.

Blinds, Diffusers and a Coefficient Nobody Checks

The interior film conductance is the input in that equation that looks like a constant and behaves like a variable. The conventional 8 W/m²K represents a vertical surface with room air circulating freely against it. Close a blackout blind against the glass and the strip of air between blind and facade stops being room air: it cools, it stratifies, and its dew point stays where the room's is because moisture diffuses through the gaps at the head and sill perfectly well even when heat does not. Push a run of storage units along the perimeter, hang a heavy curtain, install a bench seat that boxes in the trench heating, and the same thing happens over a longer stretch of wall.

Halve that conductance and watch the arithmetic. The frame at 3.5, twenty-one inside and minus ten outside, sat at 7.4 degrees with the film conductance at 8. At 4 it falls to about minus six — four degrees off the outdoor air, and a surface that collects water at anything above roughly sixteen per cent relative humidity, which is to say at every humidity a building ever holds. A good frame at 2.4 W/m²K is not exempt either: comfortable at 11.7 degrees in open air, it drops to about 2.4 degrees behind the same blind, which is the dew point of a room held at thirty per cent, and thirty per cent is a dry office in a cold snap rather than a design target. This is why a facade that was dry for two winters starts weeping the season after a fit-out, and why the bays that fail are so often the ones a tenant has furnished hardest.

The counter-measure is the oldest in the trade and it is a mechanical decision rather than a facade one: wash the interior surface with supply air. A perimeter slot or a sill unit throwing warm air up the inside face keeps the boundary layer moving and the effective film conductance high, which is why the ASHRAE Handbook treats fenestration surface temperature as a reason perimeter air distribution is arranged the way it is. Balancing that zone is therefore a condensation measure and not only a comfort one — and a diffuser taped over by an occupant who finds it draughty is a facade defect waiting to be reported as one.

The Wettest Hour Follows the Setback

Buildings that run a night setback have a specific and reliably misdiagnosed failure. Drop the interior air from twenty-one to sixteen overnight and the room's moisture content does not drop with it — the vapour is still there, so the dew point is unchanged. The surface temperature, however, falls: differentiate the check and each degree lost from the interior air costs the surface (1 − U ÷ hi) of a degree. On that 3.5 frame the factor is 0.56, so five degrees off the room takes nearly three off the frame. The mullion that sat at 7.4 in the evening is at about 4.6 at five in the morning, against an unmoved dew point.

So the wall is at its wettest in the hour before anybody arrives, and by half past nine, with the heating recovered and the sun on the elevation, the evidence has evaporated. What survives is a tide mark on a window board, a soft patch of plasterboard at a jamb, a spot of corrosion on a fixing, and an occupant nobody believes. A weekend shutdown does the same thing over sixty hours instead of eight, which is why so many facade condensation reports are dated on a Monday.

Spandrel and Shadow Box: Water Nobody Sees

The spandrel zone runs across the floor edge and it works to a different set of rules from the vision area, even though it hangs in the same frame. Behind an opaque or ceramic-fritted panel there is a cavity, then a back pan, then insulation, then the room. Every one of those interfaces is a place a temperature and a vapour pressure meet, and the check that governs the vision glass says nothing at all about them. The condensation checker on this page is explicit about that boundary: it evaluates the room-side surface, and shadow box cavity condensation is a separate mode with separate causes.

That cavity is the awkward part. It is not outdoor air and it is not room air, and where the back pan is sealed and the outer panel is not ventilated, whatever moisture is in there when the panel is glazed stays in there. Sunlight on the panel then drives vapour off any damp surface inside — an unprotected mineral wool face, a wet back pan, sealant still curing — and the following clear night drops the inside of the panel below the cavity's dew point, so it rains inside the box. Because the water is behind glass and appears in sun rather than in frost, it gets reported as a leak and a hose test is arranged that finds nothing. The National Glass Association's guidance on spandrel and shadow box glazing is where the ventilation and vapour options belong, and sealed-versus-vented is a design-stage decision because it changes the back pan detail.

The back pan itself is doing two jobs that get confused. It is the air and vapour barrier of the wall at that level, which means its perimeter seal onto the mullion and transom is a continuity detail and not a tidiness one. And it is the warm boundary of the insulation behind it, which means the temperature at its plane is what decides whether moisture arriving from the room condenses on the back of it. Work the gradient through the insulated depth and you find out where in that thickness the dew point falls — inside the mineral wool, which is survivable, or on the metal itself, which is not.

One detail causes more spandrel failures than the rest together: insulation packed against a back pan whose perimeter seal was never completed, in a bay where a bracket or a firestop pierces the pan. Room air at fifty per cent humidity needs no great gap — only a pressure difference, and at a floor edge in winter there is one all day.

A spandrel zone, taken apart from the weather face inward

A curtain wall spandrel in section, outside face inward: the outer spandrel panel across two bays, the shadow box cavity behind it, the sealed back pan with its upturned edges, the insulation packed against the pan, and the mullion beneath — outboard aluminium, the thermal break, and the room-side face that the condensation check is about.
  1. Outer spandrel panel — sits at close to outdoor temperature all winter, which makes its inner face the cold wall of the cavity behind it Curtain Wall Panel Count Calculator
  2. Shadow box cavity — neither room air nor outside air, and whatever moisture is sealed into it at glazing stays in it
  3. Back pan and its perimeter seal — the air and vapour line of the wall at floor level, so a seal left short is a hole in the barrier
  4. Insulation behind the pan — carries the temperature gradient, and where the dew point falls within its depth decides the outcome Insulation Batt Calculator
  5. Mullion, thermal break and room-side face — the coldest surface the room can touch, and the one the whole steady-state check is written about Curtain Wall Spandrel Condensation Risk Checker

Give it the total resistance of the spandrel build-up and the portion of it that sits between the room and the plane you are worried about, and it puts a temperature on that plane — which is the way to find out whether the back pan is inside the warm side or on the wrong edge of it.

The assumed indoor air temperature.

The outdoor winter design temperature for the site's climate zone.

The full wall assembly's total thermal resistance, interior surface to exterior surface.

The portion of the total R-value between the interior face and where the vapor barrier sits.

The dew point temperature of the interior air, based on its temperature and relative humidity.

Temperature at vapor barrier location

55.9 °F

ComparisonA comparison, not a check — no result here is an approval.

The temperature at this location stays above the interior dew point shown below, so condensation is not predicted under the design conditions entered. No risk predicted under these conditions is not the same as none. The conditions are the ones you entered, and one surface is not the assembly.

Interior air dew point
50 °F

What this calculation does not cover

  • Air leakage, not diffusion, is what usually wets a wall, and there is nothing about it here. The gradient gives the temperature at the plane; it cannot say how much moisture arrives there. A wall that passes this check and leaks warm interior air through a top plate, a service penetration or an unsealed electrical box deposits far more water at that plane than vapor diffusion through an intact assembly ever could.
  • The R-values entered describe the clear field of the wall, between the framing. The path through every stud, plate and header is colder than this straight line says, and at a steel stud or an uninsulated slab edge much colder — so an assembly that passes in the middle of a bay can be sitting below dew point on the back of the sheathing at every framing member, which is exactly where mold turns up.
  • It is one snapshot at one pair of temperatures, and it totals nothing. What damages an assembly is how many hours a year it spends below dew point and whether it dries out in between. A wall that dips below on a few cold nights and recovers is not the same wall as one that stays below for a month, and this returns the identical verdict for both.
  • The obvious fix for a failing result can produce a wall that cannot dry. Moving the barrier inboard is right only if the outboard side is open to vapor. Where a low-perm layer already sits outside — exterior foam, a self-adhered membrane, an impermeable sheathing — a second one inside traps whatever gets past either of them, and the assembly then passes this temperature check with no drying path in either direction.

Air Carries the Water; Diffusion Only Trickles

Vapour diffusion through a sealed spandrel build-up moves a small and calculable quantity of moisture. Air leakage through a gap in the same build-up moves an amount that is not in the same league, because the air is carrying its moisture with it rather than letting it find its own way through a material. This is why the sequence of failures on a wet facade so often runs the other way round from the investigation: the wall is not failing because the vapour control layer has the wrong permeability, it is failing because there is a route for humid room air to reach a cold surface, and that route is usually at a junction rather than in a panel.

The floor edge is where the routes are: a back pan seal stopped short at a bracket, a smoke seal installed as a fire measure and assumed to be an air seal, a perimeter joint sealed to the slab in one bay and to the mullion in the next, a service penetration cut after sign-off. Stack effect then supplies the pressure difference for free — in winter the upper floors of a tall building push warm humid air outward through every gap in the envelope, all day, which is exactly the direction that lands room moisture on cold facade components. The lower floors pull the other way and stay dry, and the report arrives describing a problem confined to the top three levels.

Testing tells the two apart. ASTM E283 measures air leakage through the assembly in the laboratory and ASTM E783 does the same on a wall already standing; ASTM E1105 is the water penetration test that the same wall usually passes, because water penetration and air leakage are different failures and a wall can be watertight and leaky at once. Field air leakage testing on a mock-up is the cheapest hour anybody spends on a facade, and on a humidified building it is not optional — AAMA CW-DG-1 and the CWCT Standard for Systemised Building Envelopes both set out what that programme covers.

Three Waters, Told Apart Before Anyone Is Blamed

Almost every facade moisture complaint resolves into one of a small number of conditions, and they are distinguishable on a single site visit if you know what you are looking at. The distinguishing evidence is where the water sits, whether it wipes away, and what the weather was doing in the hours beforehand. Getting this right early matters because the three have different owners: one belongs to the mechanical brief, one to the facade contractor's detailing, and one to the glass processor's warranty.

What the water is, read from where it sits and when it appears
What you findWhen it shows upWhat it actually isWhere the remedy sits
Water on the room-side frame face, glass beside it clearCold mornings, worst before the heating recoversSurface condensation on the coldest component in the bayInterior humidity, perimeter air distribution, then the frame itself
A band of water along the bottom sightline of the glassSame conditions, a degree or two colder outsideSurface condensation in the edge-of-glass zone, over the spacerWarm-edge spacer on any replacement unit; check the glazing pocket detail
Mist between the panes that cannot be wiped offAny time; often first noticed in low sunA failed insulating unit edge seal — nothing to do with the roomUnit replacement under the processor's warranty, against ASTM E2190 or BS EN 1279
Water inside a shadow box, or dripping from a transomSunny days after a cold night, not during rainCavity condensation behind the spandrel panelBack pan seal continuity and the cavity's ventilation strategy
Damp plasterboard at a jamb or over the ceiling linePersistent through winter, worse on upper floorsExfiltrating room air condensing out of sight at a junctionAir seal continuity at the floor edge, proven by test rather than by inspection
What the water is, read from where it sits and when it appears

What Is Left to Change Once the Wall Is Standing

The levers are unequal in cost and in effect, and they come in an order. Interior humidity is first because it is the only one that moves the dew point rather than the surface temperature, and where humidification was specified for a reason — an archive, a data hall, a pool — that conversation belongs to the mechanical engineer and the client rather than the facade contractor alone. Ten percentage points off the set point buys three or four degrees of dew point, more than most remedial work to a standing facade will ever buy.

Air distribution is second, and often the cheapest genuine fix: recommissioning a perimeter zone, reopening a diffuser somebody taped over, changing a throw so the supply reaches the glass line, cutting a blind pocket back so the blind stops sealing the boundary layer against the frame. Third comes the interior surface itself — trench heating, a warmed sill, or in extreme cases a secondary internal glazing line putting a new, warmer surface in front of the cold one. Fourth, and by a distance the most expensive, is the frame, because retrofitting thermal isolators into a standing wall is not generally available and this becomes a replacement conversation.

On a new project the whole list collapses into one early decision: the frame's thermal performance is chosen against the interior humidity the building will actually hold, verified for the real profile by simulation to ISO 15099 or BS EN ISO 10077-2 rather than taken from a system's headline figure. The polyamide isolators that do the work in a thermally broken extrusion — Ensinger's insulbar and Technoform's profiles are the ones most often named in system literature — are tested structurally as well as thermally, under AAMA TIR-A8 and AAMA 505, and the depth and geometry of the isolator moves the frame U-factor far more than the product family name suggests. Two profiles from one range can be a full watt per square metre kelvin apart.

Log It Rather Than Argue About It

The whole dispute turns on two readings taken at the same moment, and neither is usually available when it is needed. Put a combined temperature and humidity logger in the occupied zone at the perimeter — not on a column mid-floorplate and not above the ceiling, because the air at the facade is colder and stratified and it is the only air touching the wall — and let it record through a cold spell at fifteen-minute intervals. Pair it with a surface probe taped to the mullion face and a note of the outdoor temperature from the nearest station.

What the three traces show is a dew point line and a surface line crossing somewhere around dawn, and the gap between them is the answer: how many degrees short the frame is, and therefore how much humidity reduction, air movement or better component would close it. Hand that record on with the operation and maintenance information. The alternative, in year three, is a specialist at an occupied elevation with a cover plate and a screwdriver, reconstructing from a stain what a cheap logger would have recorded at the time.

What to settle before the frame is ordered

None of this is a material take-off in the usual sense — it is five numbers that have to be agreed between the facade package and the mechanical brief, and they are far cheaper to agree on paper than on an elevation with a paper towel taped to it.

  • The interior relative humidity the building will actually hold — Not the comfort range in the specification — the set point the humidifier will run to, including any space with its own brief such as an archive, a pool or a server room.
  • The frame U-factor as a separate figure from the glass — Simulated for the actual profile and the actual glazing pocket to ISO 15099 or BS EN ISO 10077-2. A system family's headline number covers profiles that differ by a full watt.
  • The outdoor winter design temperature for the site — The 99 or 99.6 per cent condition from climatic design information, taken for this location rather than for the country.
  • The interior surface resistance the check will be run at — The conventional value for an open surface, and a second, more onerous run for every bay that will live behind a blind, a screen, joinery or a switched-off sill unit.
  • The spandrel build-up, layer by layer, with the back pan located in it — Total resistance and the portion of it inboard of the pan, so the temperature at the pan can be worked out rather than assumed to be warm.
  • An air leakage test on the mock-up, booked before the first bay is glazed — Exfiltration at the floor edge moves more moisture than diffusion through anything, and it is the one failure that an inspection of a finished wall cannot find.
Open this as a workspace →

Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.

Drawn from

  • AAMA 1503 Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections (FGIA)
  • NFRC 500 Procedure for Determining Fenestration Product Condensation Resistance Values
  • NFRC 100 Procedure for Determining Fenestration Product U-factors
  • ISO 15099 Thermal Performance of Windows, Doors and Shading Devices — Detailed Calculations
  • BS EN ISO 10077-2 Thermal Performance of Windows, Doors and Shutters — Calculation of Thermal Transmittance — Part 2: Numerical Method for Frames
  • BS EN ISO 13788 Hygrothermal Performance of Building Components and Building Elements — Internal Surface Temperature to Avoid Critical Surface Humidity and Interstitial Condensation — Calculation Methods
  • BS EN ISO 6946 Building Components and Building Elements — Thermal Resistance and Thermal Transmittance — Calculation Methods
  • BRE Information Paper IP 1/06 Assessing the Effects of Thermal Bridging at Junctions and Around Openings
  • ASHRAE Handbook — Fundamentals: Psychrometrics, Climatic Design Information and Fenestration chapters
  • ASHRAE Handbook — HVAC Applications, on perimeter air distribution against fenestration
  • ASHRAE Standard 90.1 Energy Standard for Buildings Except Low-Rise Residential Buildings
  • CIBSE Guide A Environmental Design
  • ASTM E283 Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors
  • ASTM E783 Standard Test Method for Field Measurement of Air Leakage Through Installed Exterior Windows and Doors
  • ASTM E1105 Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Difference
  • ASTM E2190 Standard Specification for Insulating Glass Unit Performance and Evaluation
  • BS EN 1279 Glass in Building — Insulating Glass Units
  • AAMA 505 Dry Shrinkage and Composite Performance Thermal Cycling Test Procedure (FGIA)
  • AAMA TIR-A8 Structural Performance of Composite Thermal Barrier Framing (FGIA)
  • AAMA CW-DG-1 Aluminum Curtain Wall Design Guide Manual (FGIA)
  • CWCT Standard for Systemised Building Envelopes
  • National Glass Association (formerly GANA) Glazing Manual and its technical guidance on spandrel and shadow box glazing
  • LBNL THERM and WINDOW documentation, Lawrence Berkeley National Laboratory
  • Manufacturer literature for polyamide thermal isolators: Ensinger insulbar and Technoform profile data

Guidance, not a specification. Local codes, the engineer of record and the product manufacturer’s instructions govern where they differ from anything written here.