Read the Assembly Before You Touch It
Walk the space with a psychrometer and an infrared thermometer before a single roll of liner comes off the truck. Log dry-bulb and relative humidity at mid-span, convert to dew point, then shoot surfaces: foundation wall at mid-height and again at the footing, underside of the subfloor, exposed duct, cold water lines, pier faces, bare soil. Anything colder than that dew point is wetting right now, visible or not.
Two visits beat one. A December reading tells you where the heat is leaving; a July reading tells you where the moisture is landing, and those are rarely the same square foot. Note the gap between soil surface temperature and crawl air temperature — a wide spread in summer predicts exactly which joist bays will grow something before the encapsulation is finished.
Pin meters settle the argument. Drive probes into joists, girders, sill plate and subfloor sheathing at several depths, following the direct measurement methods of ASTM D4442; readings that hold near or above twenty percent point to an active source rather than a bad season. Mark those bays on a sketch — they become the punch list you check against next summer.
Summer Air on Cool Masonry
Foundation vents were drawn for a drying problem that only exists in a heating climate. Outdoor air at 80°F (27°C) and 80 percent relative humidity carries a dew point near 73°F (23°C). Below-grade masonry and the soil beneath it track closer to the annual mean air temperature, commonly in the fifties or sixties (10 to 20°C) across much of the temperate United States. Open a vent to that air and the wall becomes a condenser.
Damage reads like a map once you know what drew it. Staining and cupping concentrate downstream of vent openings; duct seams rust nearest the outside air; cold supply lines run wet from spring through September; fungal growth blooms on the joist faces that see the most air movement and the least warmth. Winter, by contrast, usually leaves the same crawlspace dry.
Model codes have followed the physics. The unvented, conditioned crawl space provisions of the International Residential Code allow a sealed space where a continuous ground vapor retarder is paired with an approved means of conditioning the air. Which edition applies, and what local amendments do to it, is set by the adopting jurisdiction — confirm with the building official before you spec the closure of a single vent.
Bulk Water Sets the Floor
No membrane outruns a downspout dumping at the foundation. Before anything gets sealed, chase the surface water: extend leaders well clear of the wall, restore positive grade away from the house, clear window wells, and cut any planting bed that traps runoff against the block. Liquid water under a liner holds the soil at saturation and pins the space's dew point to ground temperature.
Where the water table rises into the space, drainage comes before encapsulation. An interior perimeter drain tied to a sealed, lidded sump with a check valve and a dedicated circuit handles what grading cannot. Route the discharge far enough out that it does not return; a pump recycling its own water runs constantly and tells the owner nothing is working.
Efflorescence and a persistently damp block face signal capillary rise through the footing. Coatings applied to the inside of that wall rarely last, because the drive is coming from behind them. Plan to insulate and drain rather than to seal the masonry face, and let the liner and the dehumidifier carry the residual load.
The Ground Plane
Bare soil is the largest continuous vapor source in the assembly, and covering it is the single change that moves the whole space's dew point downward. Specify a reinforced polyethylene sheet meeting ASTM E1745, Standard Specification for Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs; the classes in that standard separate products by tensile strength, puncture resistance and water vapor permeance, and puncture resistance matters more than nominal thickness on a rocky floor.
Prep earns the warranty. Rake out rubble, remove sharp stone, fill low spots that will pond under the sheet, and cut back debris around piers. Lap seams generously and tape the full run rather than spot-sealing; ASTM E1643, Standard Practice for Selection, Design, Installation, and Inspection of Water Vapor Retarders Used in Contact with Earth or Granular Fill under Concrete Slabs, is installation discipline worth borrowing here even though the concrete never arrives.
Terminate the liner up the wall and hold it with a termination bar bedded in sealant, not tape alone — tape on damp block releases in a season. Wrap piers and tape the collar. Where termite inspection is required, leave the exposed band the local code demands rather than covering it and arguing about it at final.
Between the joists and the dirt
- Floor system overhead — the surface the whole exercise is protecting; left uninsulated once the crawl is brought inside the thermal boundary, which is why nothing below it may stay cold
- Rim and sill band — the coldest wood in the box, bought by the sheet against perimeter length rather than floor area Rim Joist Insulation Calculator
- Foundation wall foam — board or closed-cell applied tight to masonry so the cold face becomes foam; thickness follows the locally adopted energy code, continuity beats the last half-inch of R-value Foam Board Insulation Calculator
- Ground liner — reinforced sheet over the whole floor and up the wall to a termination bar, sized on floor area plus run-up plus lap rather than on the plan dimension Crawlspace Encapsulation Liner Calculator
- Raked soil — rubble pulled out, sharp stone removed and ponding hollows filled, because puncture resistance is worth more here than nominal sheet thickness
Sheet quantity, not sheet spec, is what stalls this stage on site — settle the roll count against the real floor area, wall run-up and lap allowance before the crew is standing on raked dirt.
SettingsSettings for this calculation
The standard allowance most suppliers and estimating guides assume for ordinary work.
The total floor area of the crawlspace to be lined.
The total perimeter of the crawlspace walls being lined.
The height the liner extends up the crawlspace walls.
Extra liner material to allow for overlaps, seams, and cut waste.
Liner needed
800.2 sq ft
- Wall area
- 297.5 sq ft
They open the calculator with your figures already in it
Crawlspace Encapsulation Liner Calculator: 800 sq ft — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- Piers, columns and interior footings carry no term in the arithmetic: the total is the floor footprint plus perimeter times wall height, so liner wrapped around a masonry pier or carried up an interior support is extra material this figure does not contain.
- A single wall height is applied around the entire perimeter, so a stepped footing, a sloping site, or a run that drops into a full-height basement wall has to be split and estimated in sections — and the height field caps at 2.5 m (about 8 ft), short of a true basement lift.
- Floor area and perimeter are read as two independent numbers and never reconciled, so nothing objects when the perimeter you enter could not physically enclose the floor area you enter, and a transposed digit in either still returns a plausible-looking total.
- The waste allowance is one multiplier on the combined floor-and-wall total rather than a separate overlap on each surface, it is already folded into the headline number with only the wall area broken out beneath it, and it stops at 20% — below what a crawlspace crowded with ducts, plumbing drops and pier blocks can actually consume.
- The perimeter you enter serves only to generate wall area and is never returned as a linear run, so the seam tape, adhesive and top-of-wall termination that make an encapsulation airtight — quantities that follow seam length rather than area — sit outside this answer.
Moving the Condensing Plane Into the Foam
Fiberglass hung against a foundation wall does nothing to relocate the dew point. Air-permeable insulation lets crawlspace air reach the cold concrete behind it, so the condensing surface stays exactly where it always was — on masonry, under a wet batt, out of sight. Board foam or closed-cell spray applied tight to the wall changes the geometry: the cold face is now foam, and the interior face runs warm enough to stay above the space's dew point.
Thickness is a climate-zone decision. Minimum R-values for below-grade walls come from the International Energy Conservation Code and the energy provisions of the International Residential Code as adopted and amended locally, so the number governing your job is whatever the authority having jurisdiction enforces. Run the assembly continuous from sill down to the liner, seal every board edge, and avoid leaving a thin lap at the top of the wall.
Resist adding an interior Class I vapor retarder over the foam in most climates. Foundation walls dry inward; a second low-perm layer on the warm side leaves incidental moisture no exit. The foam already sits low on the permeance scale measured by ASTM E96/E96M, Standard Test Methods for Water Vapor Transmission of Materials, and that is enough.
Wall foam earns its place only if the interior face lands above crawlspace dew point at design conditions, and that is a number to settle before the boards are cut, not after the batts are already wet.
The assumed indoor air temperature.
The outdoor winter design temperature for the site's climate zone.
The full wall assembly's total thermal resistance, interior surface to exterior surface.
The portion of the total R-value between the interior face and where the vapor barrier sits.
The dew point temperature of the interior air, based on its temperature and relative humidity.
Temperature at vapor barrier location
55.9 °F
The temperature at this location stays above the interior dew point shown below, so condensation is not predicted under the design conditions entered. No risk predicted under these conditions is not the same as none. The conditions are the ones you entered, and one surface is not the assembly.
- Interior air dew point
- 50 °F
They open the calculator with your figures already in it
Vapor Barrier Dew-Point Condensation Risk Calculator: 55.85 °F — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
What this calculation does not cover
- Air leakage, not diffusion, is what usually wets a wall, and there is nothing about it here. The gradient gives the temperature at the plane; it cannot say how much moisture arrives there. A wall that passes this check and leaks warm interior air through a top plate, a service penetration or an unsealed electrical box deposits far more water at that plane than vapor diffusion through an intact assembly ever could.
- The R-values entered describe the clear field of the wall, between the framing. The path through every stud, plate and header is colder than this straight line says, and at a steel stud or an uninsulated slab edge much colder — so an assembly that passes in the middle of a bay can be sitting below dew point on the back of the sheathing at every framing member, which is exactly where mold turns up.
- It is one snapshot at one pair of temperatures, and it totals nothing. What damages an assembly is how many hours a year it spends below dew point and whether it dries out in between. A wall that dips below on a few cold nights and recovers is not the same wall as one that stays below for a month, and this returns the identical verdict for both.
- The obvious fix for a failing result can produce a wall that cannot dry. Moving the barrier inboard is right only if the outboard side is open to vapor. Where a low-perm layer already sits outside — exterior foam, a self-adhered membrane, an impermeable sheathing — a second one inside traps whatever gets past either of them, and the assembly then passes this temperature check with no drying path in either direction.
Rim Joist and Sill: the Coldest Wood in the Box
The rim joist and sill sit at the top of the wall where warm interior air meets an uninsulated wood band with siding on the far side. Colder than the foundation below it during the heating season and rarely conditioned, that band collects condensation from indoor air pushing outward through the floor system, and it is usually the first framing to rot in an otherwise dry crawlspace.
Detail it with closed-cell spray foam or cut rigid board sealed on all four edges, bearing hard on the sill and lapping the top of the wall insulation. Thin foam with a batt stuffed over it recreates the original failure: the batt keeps interior heat off the wood while the foam is too thin to hold that face above dew point. Continuity beats nominal R-value at this joint.
Check two things before foam goes in — that the sill plate is dry and not already in decay, and that nothing gets buried that must stay accessible. Junction boxes, cleanouts, gas line unions and any required termite inspection band all need to remain visible after the crew leaves.
The band runs the entire perimeter and is bought by the sheet, so take the count off the wall lengths rather than discovering the shortfall two bays from the end.
The total exterior perimeter at the rim joist band (typically between the foundation and first floor framing).
The depth of the floor joists, which sets the height of the rim joist band.
Foam board sheets needed
4 sheets (4x8 ft)
- Rim joist band area
- 100.21 sq ft
They open the calculator with your figures already in it
Rim Joist Insulation Calculator: 4 sheets (4x8 ft) — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- Board thickness is not an input, so the count is the same for a 25 mm board as for a 100 mm one, and it covers a single layer. Nothing here tests the resulting R-value against what the rim joist is expected to achieve, and building up two layers to reach a target doubles the sheet count.
- Thickness is also what keeps the rim board dry, and that is not checked either. Foam too thin for the climate leaves the inner face of the rim board cold enough for indoor air to condense against it, so the penalty for getting thickness wrong here is damp timber rather than a slightly higher heating bill, and the thickness needed to hold that face above the dew point depends on the climate zone.
- The 10% allowance covers ordinary offcuts, not the yield lost to cutting a whole sheet down into bay-sized pieces. A 4x8 ft sheet cut into 9.25 in by 14.5 in rectangles — 2x10 joists, the default here, at 16 in centres — gives 30 pieces, about 87% of the sheet, with the rip and end strips discarded, so a long band worked out from area alone can come up a sheet short.
- Only the boards are counted. The canned foam that seals the perimeter of every cut piece, the sealant at the sill plate, and any covering the foam needs where it is left exposed are all outside the number — foam plastic inside a dwelling normally has to sit behind a thermal or ignition barrier, and whether the rim joist band is granted an exception is jurisdictional.
- Perimeter times joist height treats the band as an unbroken rectangle. Nothing is deducted for basement windows, walkout doors or beam pockets, and nothing is added where a cantilever, bay window or bump-out carries the band past the foundation line that the help text asks you to measure.
- The band is assumed to be exactly as tall as the joist. Many rim joist details are insulated from the underside of the subfloor down over the sill plate to the top of the foundation wall, which is taller than the joist depth entered here.
Air Leakage Carries the Water
Diffusion through materials moves a trickle; air carrying vapor through a hole moves a flood. A crawlspace connected to outdoors by open vents, a loose hatch and an unsealed band imports summer dew point faster than any dehumidifier can strip it. Tightening the enclosure is what makes conditioning affordable instead of a permanent line on the power bill.
Order matters on site. Close vents with cut rigid foam bedded in sealant or with masonry infill, gasket and latch the access hatch, seal plumbing and wiring penetrations through the subfloor, then chase duct seams and boot connections. Leave the hatch itself for last so the crew keeps a working opening while the messy sealing happens.
Verify rather than assume. A blower door run under ASTM E779, Standard Test Method for Determining Air Leakage Rate by Fan Pressurization, or ASTM E1827 confirms the enclosure actually tightened; a digital manometer reading between crawl and living space confirms the crawlspace now sits inside the pressure boundary instead of acting as a supply plenum for the house above it.
Tightening is a claim until a fan says otherwise, and this turns the airtightness you promised into the reading the gauge has to show while the crew is still on site to chase it.
The total conditioned (heated/cooled) floor area of the building.
The average ceiling height across the conditioned space.
Your airtightness goal, e.g. from an energy code requirement or certification program.
Target CFM50
432 CFM50 (target maximum)
Your actual blower door test result should come in at or below this target — this is the inverse of the Air Changes Per Hour Calculator, useful for setting a goal before construction or air sealing work rather than evaluating a completed test.
- Building volume
- 8,640 ft³
They open the calculator with your figures already in it
Blower Door CFM50 Target Calculator: 432 CFM50 (target maximum) — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 432 CFM50 (target maximum) — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- Building volume here is nothing more than floor area multiplied by average ceiling height. That ignores the thickness of intermediate floor assemblies, flattens stairwells and double-height spaces into an average, and omits any conditioned basement or attic whose area you did not enter. The target moves in direct proportion to the volume, so a volume measured ten per cent differently from the tester's gives a CFM50 limit ten per cent different — agree the volume basis with whoever will run the test before you build to this number.
- Nothing here defines the tested envelope: whether an attached garage, an unheated basement, a conditioned crawl space or a plant room sits inside or outside it. That single decision changes both the volume in the denominator and the leakage the fan has to move. Two people can test the same building to two different ACH50 figures purely by drawing the boundary in two different places.
- ACH50 normalises leakage against volume. UK and much European testing, and some North American programmes, instead specify air permeability or leakage per unit of envelope area. This page never asks for envelope area, so a target handed to you in those terms cannot be met by hitting this CFM50 figure.
- The number assumes a properly conducted test at 50 Pa. It carries no correction for wind, stack effect or baseline pressure, no averaging of a depressurisation result against a pressurisation one, and no allowance for how the building is prepared — which trickle vents, flues, extract fans and drain traps get sealed and which are left as found. Those are the usual reasons two tests of the same building disagree.
- This is a target airflow, not a ventilation or combustion-air check. A building tightened towards a low ACH50 needs mechanical ventilation sized and commissioned for it, and any open-flued or naturally aspirated appliance inside the envelope needs its own combustion air and spillage assessment. Hitting this figure says nothing about either, and those are the parts that carry a safety consequence.
Holding Dew Point Under the Coldest Surface
One target governs the mechanical design: crawlspace air dew point must stay below the coldest surface in the space, in every season. That goal moves — the coldest surface is the rim joist in January and the foundation wall in August — so the control strategy has to hold year-round, not merely during the months the owner notices an odor.
Three approaches appear in code-recognised practice: continuously operating exhaust to outdoors, supply air delivered from the conditioning system with a path back to the house, or a dedicated dehumidifier. Exhaust works in dry climates and backfires in humid ones by drawing in the very air causing the trouble. Supply air needs a real return path, not a gap around a duct. Across mixed and humid climates the dehumidifier usually does the actual work.
Set the humidistat to hold in the low fifties percent relative humidity, then confirm the resulting dew point sits under your measured minimum surface temperature. Drain condensate by gravity where grade allows and by pump where it does not, run the line to daylight or a trapped fixture drain, stand the unit off the liner with filter access, and label the service interval on the housing. Whole-house ventilation rates remain governed by ANSI/ASHRAE Standard 62.2.
Pick the capacity against the floor area and the dampness you logged on the first visit, not against whichever machine fitted through the hatch on the last job.
The floor area of the basement or room.
How consistently damp the space feels, especially in humid weather.
Recommended dehumidifier capacity
13 pints/day
This sizing chart assumes typical conditions — extra factors like an attached laundry area, frequent door traffic to outdoors, or a large uninsulated space can push actual needs higher.
- Room area
- 540 sq ft
They open the calculator with your figures already in it
Dehumidifier Sizing Calculator: 12.96 pints/day — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 13 pints/day — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- The calculation takes floor area and nothing else. Moisture sits in the air volume, not on the floor plate, so a basement with a 3.5 m (11.5 ft) ceiling and a 1 m (3.3 ft) crawl space of the same footprint return the same answer, and neither the extra air nor the extra wall and slab surface behind it is in the number.
- The dampness level is a description of how the space feels, not a measured moisture load. Nothing here counts the actual sources - an unvented dryer, a bare-earth crawl space floor, an open sump, an adjoining laundry or shower, occupants, or humid outside air leaking in at the rim joist and the stair door. Two rooms of the same area carrying the same rating can differ several times over in the water they give up in a day.
- The per-500-sq-ft rate is applied strictly linearly, so 2,000 sq ft (186 m²) returns exactly four times the 500 sq ft (46 m²) figure. Published sizing tables do not scale that way - pints needed per unit of floor area falls as the space grows - so the further past 500 sq ft (46 m²) you go, the more this overstates the machine. At the largest area it accepts, on the wettest setting, it returns over 200 pints a day, far beyond any single residential unit.
- Air temperature is not an input. A refrigerant dehumidifier's plate rating is measured in warm air and its real extraction falls off sharply as the space gets colder, to the point where the coil frosts and the machine spends part of its cycle defrosting rather than pulling water; a basement, crawl space or garage that stays cold usually wants a low-temperature or desiccant unit, not a bigger conventional one. The pint figures here are also not tied to any stated test standard, and the standard changed - older ratings were taken in warmer air than current ones - so a 12-pint recommendation and a machine plated at 12 pints are not necessarily the same amount of water.
- This is a capacity figure only. It does not set a humidity target, estimate run hours or condensate volume, choose a drain route, or check the circuit will carry the machine, and it does not size drainage, a sump, grading or a vapour barrier. Where the 'extremely wet' level applies - standing water or active seepage - water is arriving faster than a dehumidifier is built to remove it, and the water path is the job before any capacity number means anything.
Soil Gas, Combustion Air, and Fire Protection
Sealing an enclosure changes the combustion picture. An atmospherically vented water heater or furnace sitting in a crawlspace loses its dilution and makeup air the moment the vents close, and a backdrafting appliance in a space directly connected to the floor above is a life-safety failure, not a callback. Test worst-case depressurization in the combustion appliance zone; where the appliance cannot be converted to sealed combustion or relocated, the encapsulation scope has to change.
Soil gas concentrates under a continuous membrane. Test for radon after the work as well as before, because the pre-existing number describes a space that no longer exists. Where results exceed the 4 pCi/L (148 Bq/m³) action level used by the U.S. EPA, a sub-membrane depressurization system installed to ASTM E2121, Standard Practice for Installing Radon Mitigation Systems in Existing Low-Rise Residential Buildings, is the remedy — and roughing in the suction pit while the liner is open beats cutting it open later.
Foam plastics generally require a thermal or ignition barrier unless the specific product carries an approval for exposed installation, with surface burning characteristics established by ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials. Both the limits and the acceptable coverings come from the adopted building code and the local inspector, so confirm the detail before the wall gets closed in.
If an atmospherically vented appliance is staying down there, the free area feeding it has to be worked out before the last foundation vent gets foamed shut, not after the draft test fails.
The fuel-burning appliance's total rated input, from its nameplate.
Minimum free area per opening
100 in²
This is the NFPA 54/IFGC indoor air method for a confined space, requiring TWO openings of this minimum free area each (one high, one low). Outdoor air methods use different (typically smaller) sizing factors, and unconfined spaces may not require dedicated combustion air openings at all — confirm which method and space classification applies to your installation with the full code section before finalizing opening size, as this is a single-method screening calculation, not a complete combustion air analysis.
- Free area before the code's minimum is applied
- 100 in²
They open the calculator with your figures already in it
Appliance Combustion Air Free Area Calculator (Indoor Air Method): 100 in² — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 100 in² — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- Free area is not the size of the hole you cut. A grille or louver passes only its open fraction — roughly three-quarters for metal, as little as a quarter for wood — and an insect screen behind it takes more again, so a 100 in² (645 cm²) free-area requirement can need an opening of 130 to 400 in² (840 to 2,580 cm²) depending on what covers it. Size from the louver's published free area, or the appliance is starved through an opening that measures correctly.
- The openings only work if the space on the other side is large enough. This method assumes the adjoining room, plus everything freely communicating with it, holds at least 50 ft³ (1.4 m³) per 1,000 BTU/hr (0.3 kW) of combined appliance input; cutting two grilles into the partition of a small closet does not create combustion air, it shares one shortage between two rooms.
- Nothing here accounts for air being pulled out of the space. A kitchen hood, a clothes dryer or a bath fan can drop the room below atmospheric pressure and reverse an atmospheric flue no matter how generous the openings are, which is how a correctly sized opening still ends with a CO alarm — a house with substantial mechanical exhaust needs the appliance's air supply looked at as a pressure balance, not as an area.
Commissioning and the First Cooling Season
Leave instrumentation behind. A logging thermo-hygrometer in the middle of the space plus a second sensor taped to the coldest surface identified on day one turns the next twelve months into evidence rather than opinion. Baseline the wood moisture readings at the same joist bays marked during the survey and hand the owner that sketch with the closeout package.
Return during the first humid stretch, not in the fall. Pull the log, compare recorded dew point against surface temperatures, and read the signatures of an incomplete job: a wet band along one wall means a liner termination let go; condensation on ductwork means the duct is uninsulated or leaking cold air into a space still running humid; a dehumidifier that never cycles means the enclosure is still open somewhere.
Documentation belongs in the deliverable. Photograph the liner before terminations are covered, record foam product and thickness, note the humidistat setpoint and condensate route, and write down which vents were sealed and by what method. The next trade into that space — plumber, pest inspector, HVAC tech — will cut the liner if nobody tells them what it does.
Crawlspace Encapsulation Takeoff
Quantities and checks to settle before the truck is loaded, each one tied to a surface whose temperature you already measured.
- Liner area: floor, wall run-up, pier wraps — Add lap allowance at every seam and the vertical run to the termination bar; piers and stub walls eat more sheet than the floor plan suggests.
- Seam tape, termination bar, sealant — Tape alone fails on damp block — mechanical termination bedded in sealant is the joint that survives.
- Rigid or closed-cell foam, wall and rim band — Thickness follows the locally adopted energy code; continuity from sill to liner matters more than the last half-inch of R-value.
- Vent and hatch closures — Count openings including crawl-to-garage and old coal doors; the hatch needs a gasket and a latch, not a leaned panel.
- Dehumidifier, stand and condensate route — Confirm a gravity drain or pump path and a serviceable filter before the unit is set; verify setpoint dew point against the coldest measured surface.
- Combustion and radon checks — Worst-case depressurization test on any atmospheric appliance, and a post-encapsulation radon test with the suction pit roughed in while the liner is open.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.
