Irrigation

Running Inline Dripline Through a Planted Bed

A drip grid cannot be watched, so its schedule is computed: emitter discharge over the grid area gives depth per hour, and the mulch goes over the tube.
  • 17 minReading time
  • 8Sections
  • 4Calculators inline
  • Last reviewed

A Planted Bed, a Coil of Tube and a Delivery Booked for Thursday

The border runs fourteen metres along the fence, averages a little over two wide, and the shrubs went in last week. There is a coil of sixteen millimetre inline dripline in the van with the labels still on it, a spare station on a four-zone manifold that otherwise drives lawn rotors, and a load of bark arriving Thursday morning. None of that is hard work. What holds the job up is that two of the decisions are arithmetic and neither of them can be made by looking at the bed: how many minutes the controller should hold that station open, and how many cubic yards to have tipped on the drive.

Everything else on an irrigation job announces itself. Stand a rotor zone up and you can see the throw, see where the arcs miss, see the fence getting wet. A drip grid gives you a dark ring of damp around each emitter, a few minutes after it starts, and then nothing further to look at — the interesting half of what it is doing is a hundred and fifty millimetres down. Turn it on for the client at handover and they will watch a bed that appears to be doing very little, which is exactly what a correctly running grid looks like.

So the schedule has to be derived rather than observed, and the derivation is short: what one emitter discharges, spread over the patch of ground the grid gives it, is a depth of water per hour, and a depth per hour is the only language a controller understands. The mulch order follows from the same tape work that set out the laterals, and it follows it in the correct order — tube first, bark over the top, never the reverse.

The Spacing You Choose and the Spacing the Factory Already Chose

Inline dripline arrives with its emitters welded into the wall at a fixed interval, and that interval is part of the part number, not a site decision. Three hundred millimetres is the common landscape pitch in metric markets, three hundred and thirty and five hundred sit either side of it, and twelve, eighteen and twenty-four inches do the same job in North America. Buying the tube commits the spacing along the run. Nothing you do on the bed changes it.

The spacing between adjacent runs across the bed is yours, and it is the only lever on the grid that is. Set the laterals at the same interval as the emitters and you get a square grid, the most even wetting the product can give, and the highest application rate it can produce. Open the laterals out and the rate falls in direct proportion, which sounds like a free saving until you notice what else falls with it: the strips between the runs stop overlapping and the bed develops dry ribbons the planting will find before you do.

Where that limit sits is a soil question. Water leaving a point source spreads sideways and downward at the same time, and the ratio between the two is close to the ratio of the soil's fine fraction — a heavy silt or clay pushes a wide, shallow bulb that meets its neighbour easily, and a sand takes the water almost straight down and leaves the halfway point dry. ASABE/ASAE EP405.1, Design and Installation of Microirrigation Systems, is the document that governs how a microirrigation layout is designed and installed; what it will not do is tell you the bulb width in this bed, because nobody can from a distance. The field answer takes an hour: lay a trial run, open the valve, dig a small pit across the tube afterwards and look at where the wet stops.

Two layout habits are worth keeping whatever the spacing turns out to be. Hold the outermost lateral a good hundred and fifty to two hundred millimetres inside the bed edge, because the edge is where a spade re-cuts the line every spring and where a strimmer works, and run the laterals along the bed's long axis so the fitting count stays low — every barb is a joint, a pressure loss and something to find later. On a bed of any size, feeding the laterals from a manifold at both ends rather than dead-ending them costs a few metres of tube and takes the far-end pressure loss out of the argument entirely.

Litres an Hour Over a Square Metre Is Millimetres an Hour

The conversion that makes drip schedulable is a definition rather than a formula. A litre poured evenly over a square metre stands one millimetre deep. So an emitter rated in litres per hour, divided by the area of bed that emitter is responsible for — its spacing along the tube multiplied by the spacing between laterals — is a depth per hour, in exactly the units a rotor or a spray head is rated in and exactly the units a controller schedule is written in. In imperial the same identity reads one gallon per square foot equals 1.6 inches of depth, which is where the awkward-looking inch-per-hour figures on the right of the table below come from.

The table is arithmetic, not test data. It is worth reading for the shape of it rather than the individual rows: a drip grid lands somewhere in the low teens of millimetres per hour across most sensible product choices, and the choices that look very different on paper — a lighter emitter on a tight grid, a heavier one spread out — land close together. That is the useful property. It means the schedule is not especially sensitive to which of two similar products the wholesaler has in stock, and it means a grid that comes out at double or half the band is telling you the spacing has drifted from what was intended.

One caution about which area the rate belongs to. The figure is the depth applied over the ground the grid actually covers, which is the rectangle bounded by the outermost laterals and the outermost emitters — not the bed outline on the plan. Six runs at four hundred millimetres put their outermost laterals two metres apart on a two and a half metre bed, and the five hundred millimetres left over at the margins receives whatever the bulbs spread into it and nothing else. Work the run time against the gridded area and treat the margins as planting positions to keep away from, not as ground the valve is watering.

It also settles the question of whether this bed can share a station with anything else. It cannot. The grid above applies water several times more slowly than a fixed spray zone in the same garden — compare it against the precipitation rate on the head manufacturer's performance chart rather than against a remembered figure — and it applies it in a different pattern, so a valve carrying both is being asked to run two schedules at once and will be set to whichever half complains first.

Applied depth for common inline dripline configurations, from emitter discharge divided by the area of bed each emitter serves
Emitter dischargeEmitters along the tubeLaterals apartApplied depth
1.6 L/hr300 mm300 mm17.8 mm/hr
1.6 L/hr300 mm400 mm13.3 mm/hr
1.6 L/hr300 mm500 mm10.7 mm/hr
2.0 L/hr330 mm450 mm13.5 mm/hr
2.3 L/hr400 mm500 mm11.5 mm/hr
0.6 gal/hr12 in18 in0.64 in/hr
Applied depth for common inline dripline configurations, from emitter discharge divided by the area of bed each emitter serves

Put the discharge printed on the box and the two spacings the bed will actually be set out at through the division, and the grid stops being a product and becomes a rate the controller can be programmed against.

The rated discharge of a single emitter at the design pressure.

The distance between emitters moulded into the tube.

The distance between adjacent runs of dripline across the planting.

Application rate

0.415 in/h

Medium confidence

This is the rate the grid applies over the area it covers, which is the number a controller needs. It is not a statement about what reaches the root zone: on a slope, on a crusted soil, or with an emitter that has begun to plug, the applied depth and the infiltrated depth part company.

Area served by each emitter
1.63 ft²
Discharge per unit length of lateral
0.43 gal/h/ft
Depth applied in a thirty-minute run
0.21 in

Add the equipment this sizes

This result is a specification — 0.415 in/h — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

What this calculation does not cover

  • Assumes every emitter on the zone is discharging at its rated figure, which requires the filtration and pressure regulation a drip valve should have at its head.
  • Says nothing about run length. A lateral longer than the manufacturer's maximum loses pressure along its length, and the far end applies less than this figure whatever the label says.
  • Ignores evaporation from the surface between emitters, which for surface-laid dripline in an exposed bed is not negligible.

Turning a Depth per Hour Into Minutes on the Station

A rate is half the schedule. The other half is the depth the planting needs replacing in a week at the height of the season, and that number does not come from the tube — it comes from the site. Reference evapotranspiration for the location, computed the way FAO Irrigation and Drainage Paper 56 sets out, is the base figure, and a mixed shrub or perennial bed uses a fraction of it. WUCOLS IV, the University of California classification of landscape species by water use, is where that fraction is looked up honestly rather than guessed, and it is worth noticing that the answer for an established, moderate-use shrub planting under mulch is a good deal less than for the lawn on the other side of the path. Divide the weekly depth by the grid's depth per hour and you have weekly minutes.

Splitting those minutes into cycles is a soil-storage question rather than a rate question. The bed can only hold so much water in the depth the roots occupy, which for shrubs and perennials is the top three to four hundred millimetres of profile; the available water a soil holds per metre of depth is tabulated in FAO 56, and the practical shape of it is that a sand holds roughly half what a silt loam does over the same depth. Apply more than the store in one visit and the surplus drains past the roots — invisible on drip, because there is no runoff to see. A soil with a small store therefore wants the same weekly minutes delivered in more, shorter visits, and a soil with a large one prefers a single long soak that pushes the wetting front deep enough to be worth having.

Cycle-and-soak, the habit that spray zones on slopes are built around, mostly does not apply here. A drip grid discharges below a mulch blanket at a rate an undisturbed bed soil absorbs without complaint, and the exception is narrow: a bed on a real fall, or one whose surface has crusted where the mulch has thinned, where the emitter output tracks downhill before it soaks. On those, split the run.

None of this survives contact with the bed unchecked, and the check costs one hour. Run the completed zone for the calculated time, come back the next day, and dig a narrow slot across a lateral with a trowel. The wetted band should be continuous along the run and it should be damp at the depth the root balls were planted to. If it is wet at the surface and dry at two hundred millimetres, the run is too short and too frequent; if the slot is wet to the bottom of the trowel and the plants are still tired, the interval is wrong rather than the duration. The Irrigation Association's Landscape Irrigation Scheduling and Water Management guidance is the reference for the method behind that adjustment, but the trowel is what settles this bed.

  1. Take reference evapotranspiration for the site at peak season from the local published figure, not from a national average.
  2. Apply a landscape coefficient for the planting from WUCOLS IV, allowing for the fact that a mulched shrub bed shades and shelters its own soil.
  3. Divide that weekly depth by the grid rate the calculator returned to get weekly run minutes on the station.
  4. Split the weekly minutes into visits the soil's root-zone store can accept in one go, then round to a whole number of minutes the controller will actually hold.
  5. Programme the peak-season schedule and leave the seasonal adjust percentage to carry spring and autumn, rather than rewriting the programme four times a year.
  6. Dig a slot across a lateral the day after the first full cycle and correct duration or interval on what the soil profile shows.

How Much Tube One Valve Will Carry

Drip flow accumulates by the metre, which is the one hydraulic habit that separates it from everything else on the manifold. Emitter discharge divided by emitter spacing gives litres per hour for every metre of tube on the bed — 1.6 litre emitters at three hundred millimetres draw 5.3 litres per hour per metre — and the zone total is that figure times the metres laid. Seventy-two metres of tube across a thirty square metre border comes to something near 380 litres per hour, or a little over six litres a minute, which is a small enough number that installers stop checking it and then group four beds onto one station without ever adding them up.

Two limits bind before the flow does. The first is the maximum run length for the product, which every inline dripline data sheet publishes as a table against emitter spacing and inlet pressure — the technical literature for Netafim Techline, Rain Bird XFS, Toro DL2000 and Rivulis inline products all carry one, and the numbers differ enough between them that a habit formed on one brand will overrun another. Pressure-compensating tube holds its rated discharge across a working band and so tolerates a long lateral and a fall along it; non-compensating tube does not, and on a sloping bed its bottom emitters simply discharge more than its top ones. The second limit is the head assembly, which on a drip station is not optional: filtration at the mesh the data sheet calls for, a fixed-outlet pressure regulator chosen at the pressure the product's discharge chart is drawn at, and air relief at the high point so the tube does not draw soil and fines back through the emitters as it drains.

Protection of the supply is a separate matter decided by somebody else, and it should be settled before the trench is opened rather than at handover. The International Plumbing Code deals with it in Section 608, Protection of Potable Water Supply, and in the United Kingdom the Water Supply (Water Fittings) Regulations 1999 and the accompanying Water Regulations Guide treat a garden irrigation system as a high-category risk that a check valve does not answer. The assembly type is the purveyor's call in both cases; the installer's job is to have asked.

This divides an available flow by the flow of one outlet, and on a drip station the outlet worth counting is a whole lateral run rather than a single emitter — an emitter draws far too little to be the unit a valve fails on, and the run is what you would remove to bring the zone back inside its supply.

Your water supply's available flow rate, in the unit shown.

The rated flow rate of the sprinkler head you're using.

Maximum heads per zone

5 heads per zone

Medium confidence

This is a flow-based estimate only — also check that your zone valve and pipe sizing can handle the combined flow, and that static water pressure is sufficient for the specific heads chosen.

Add the equipment this sizes

This result is a specification — 5 heads per zone — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

What this calculation does not cover

  • One flow rate is divided into the supply, so the count only holds for a zone whose heads all pass the same amount; a run that mixes rotors with sprays, or two nozzle sizes on the same valve, has no single divisor and has to be added up head by head instead.
  • Nothing here looks at the ground — this is a ceiling set by the water supply, not a head count for the area being watered, and a lawn needing more heads than this figure allows is a lawn that has to be split across further zones.
  • The remainder is dropped rather than reported: the division is floored to whole heads, and the leftover flow, which can be almost a full head's worth, is not shown, so the answer gives no sense of how much spare capacity the zone is left running on.
  • The smallest head flow the box accepts is 0.1 L/min (0.03 gal/min), which is well above what a single drip emitter passes even though the input's own note points at drip — a drip zone has to be entered as the flow of a whole lateral, not one emitter.
  • There is no time anywhere in the arithmetic. It answers how many heads can run at once, not how long the valve must stay open, so it settles nothing about the depth of water the planting actually receives.

The Eleven Litres Already Inside the Tube

A nominal sixteen millimetre dripline has a bore somewhere near thirteen and a half to fourteen millimetres, which the data sheet gives exactly and which works out at roughly a sixth of a litre for every metre of tube. The seventy-two metre bed above therefore holds about eleven litres standing in it, and that volume has to be pushed out to the far end before the last emitter on the run discharges anything at all. On a fifteen-minute cycle it is a rounding error. On a five-minute daily cycle — the schedule an anxious client tends to arrive at — a meaningful fraction of the run is spent filling tube, and the end of the bed is systematically drier than the start for reasons no amount of digging near the valve will reveal.

The same volume leaves again when the valve closes, unless the tube carries integral check valves, and on a bed with any fall it leaves through the lowest emitters. That is the origin of the wet patch at the bottom of a sloping border and of the plant that drowns while the rest of the bed is fine. It is also why the tube gets flushed rather than simply capped: dripline is commissioned by running every lateral open-ended until what comes out is as clean as what goes in, before the end closures go on, and it is flushed again on the annual visit. The microirrigation design literature puts a minimum flushing velocity at the tail of a lateral near a third of a metre per second; on a garden bed, opening the ends in turn and watching the water clear is the same instruction in a form you can carry out on your knees.

Enter the bore from the data sheet and the total metres of lateral on the station to see the volume that has to move before the far emitters run, and that drains back out of the low end every time the valve shuts.

The pipe's inside diameter, not the nominal or outside size.

The total length of pipe run.

Estimated pipe volume needed

0.7573 gallons

High confidence
Volume (liters)
2.87 liters
Volume (cubic in)
174.95 cubic in

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

0.75 in
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • The figure is the contents of a straight bore and nothing else. Fittings, valve bodies, meters, strainers and any water standing in a cylinder or tank at the end of the run are not counted, and the pipe wall is excluded — so this is not the volume of pipe material, and not the space the pipe occupies in a chase or trench.
  • Volume scales with the square of the bore, so an inside diameter that is 9 per cent out produces a volume 19 per cent out. Published inside diameters differ by material, schedule and class for the same nominal size, and the calculator takes whatever figure you type at face value — it has no way of knowing that a half-inch pipe was entered at half an inch.
  • It assumes the run is completely full of liquid over its whole length. Gravity drains, waste stacks and sewers are designed to flow part full, and a system that has not been purged holds air at its high points, so both contain less than this number says.
  • It answers how much the run holds, not how long the wait is. Turning that volume into a hot-water delay needs the fixture's flow rate as well, and the real delay runs longer because the first hot water gives up heat to the pipe wall and to whatever surrounds it. No time calculation happens on this page.
  • Nothing here is a sizing or a support check. Velocity, friction loss and pressure drop are separate calculations, and a long run that holds a comfortable volume can still be too small to deliver flow. The contents also weigh whatever that volume of water weighs, which bears on hanger spacing and is not assessed.

Mulch Goes Over the Tube, and Barely Changes the Order

The sequence is fixed and it is the part that gets reversed on busy sites: plant, set out and pin the grid, pressure-test it, flush it, photograph it, and then mulch. Pushing tube underneath an existing mulch blanket is slower, leaves the laterals wandering at whatever depth the fork found, and puts the emitters discharging into bark rather than into soil. The tube belongs on the soil surface, pinned every metre or so and closer on the curves, with the mulch laid over the top of it.

That position is worth defending against the two shortcuts either side of it. Buried in the soil, standard dripline is exposed to root intrusion and needs the root-inhibiting product made for subsurface use rather than the one on the shelf. Laid on top of the finished mulch, it bakes in ultraviolet, lifts as the tube warms and curls, gets dragged out by a rake and is chewed by anything with teeth. Under fifty to seventy-five millimetres of bark it is dark, cool, held down by the weight above it and out of the way of everything except a spade.

The mulch quantity is measured from the soil surface, not from the top of the tube, and the tube takes almost nothing out of it. At laterals four hundred millimetres apart there are two and a half metres of tube on every square metre of bed; sixteen millimetre tube has a cross-sectional area near two hundred square millimetres, so the tube displaces around half a millimetre of depth across the bed. Against a seventy-five millimetre spread that is well under one per cent, and a fifteenth of what a ten per cent settling allowance already carries. Do not deduct it, and do not let anybody spend the afternoon working out how to.

So the order is simply the bed: thirty square metres at seventy-five millimetres is two and a quarter cubic metres, near enough three cubic yards once the settling allowance is on, and the practical question left is what depth the client is buying rather than what the tube did to it. There is one genuine drip-specific argument for going to the deeper end of the mulch band here. Under a spray zone, a dry bark blanket intercepts the first few millimetres of every cycle and the plants get what is left; under drip, the water is discharged at the soil surface beneath the mulch and moves straight into the profile, so the blanket costs nothing and pays back the evaporation it suppresses. Keep it pulled clear of stems and trunk flares as ANSI A300 (Part 2) directs, specify the material against AS 4454 where mulch quality is being written into a contract, and take BS 8545 as the reference for establishment planting where trees are in the bed.

Stone over a drip grid deserves one flag before it is agreed. The grid is retrievable from under bark with a gloved hand; from under fifty millimetres of slate chipping over a barrier it is an afternoon's excavation, and every repair for the life of the bed pays that cost again. If the client wants stone, lay the tube on the soil, fix it properly, cut the barrier over it rather than under it, and photograph the layout with a tape in shot before anything covers it.

Where the tube sits in a mulched bed

A planting bed cut across its width in four courses: a buried sub-main and its riser feeding the bed from below, the prepared planting soil above that, inline dripline laterals lying on the soil surface, and the mulch blanket covering the tube from the sun and the rake.
  1. Mulch blanket — fifty to seventy-five millimetres over the tube, ordered against the bed area and the soil surface rather than the top of the laterals Mulch & Gravel Calculator
  2. Inline dripline laterals — pinned to the soil at the spacing that sets the application rate, emitters discharging into soil and not into bark Dripline Precipitation Rate Calculator
  3. Prepared planting soil — the store the schedule is written against; its texture decides how far each emitter bulb spreads sideways before it drains Garden Soil Calculator
  4. Buried sub-main and riser — the only part of the zone below spade depth, carrying the whole station flow to the point where the laterals begin Pipe Volume Calculator

The bed area and the spread depth are the whole order; put them in as measured, leave the tube out of the deduction, and let the settling allowance rather than an inflated depth carry the difference between the load and the finished surface.

SettingsSettings for this calculation
Who is doing the work?

The standard allowance most suppliers and estimating guides assume for ordinary work.

The length of the bed or area to cover.

The width of the bed or area to cover.

How deep a layer to spread.

Mulch settles and beds are rarely perfectly level.

Estimated mulch & gravel needed

0.662 cubic yards

High confidence
Area
65 ft²
Depth
3 in
Volume (no extra)
0.6 yd³

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

Plan of the slab, 10′ by 6′ 6″.10′6′ 6″

What this calculation does not cover

  • The covered area is one rectangle: `areaLength * areaWidth` and nothing else, so a curved border, a kidney-shaped bed, a circular tree ring or a path that turns a corner has to be broken into rectangles and each piece run separately before you add the yardages up. Each of those two fields also stops at 50 m (about 164 ft), and a longer run is clamped back to that bound rather than calculated.
  • The depth you enter is spread flat across the whole measured area. Nothing thins the layer back from stems and trunks, dishes it around a drain cover or manhole, crowns a gravel path so it sheds water, or subtracts the mulch already sitting in the bed — the answer is a full new layer at the stated depth over the whole rectangle, and the depth field itself is capped at 12 inches (30.5 cm), so a deeper gravel fill is not what this describes.
  • No material is named anywhere in the arithmetic, so shredded bark, wood chip, pea gravel, crushed stone and screened topsoil all come back as exactly the same volume. Bulk aggregate is normally sold and delivered by weight while mulch is sold by volume, and turning this volume into a weight for a gravel order needs a density figure the page never asks for.
  • The "Extra for Settling" percentage is a single flat multiplier on the finished volume, capped at 25 per cent, and settling is what it is named for: mulch sinking and an uneven base. It is not a compaction allowance, so gravel that will be raked and plate-compacted to a finished depth needs more loose material delivered than the area-by-depth figure suggests, and nothing in the formula adds it.
  • The figure comes back unrounded, at whatever fraction of a bulk unit the geometry gives. Bulk suppliers deliver in whole units of their own measure, by weight or in bulk bags and bagged mulch comes in fixed bag sizes, so this is the amount needed to cover the bed rather than the amount you can actually order — round up to the next unit your yard sells.
  • Cost, where you switch it on, is applied through one installed-mulch rate per cubic yard for every result. Gravel, decorative stone and topsoil are priced at that same mulch rate, so the money figure tracks the volume correctly but not the material.

What the Bed Should Be Handed Over With

The photograph taken before the mulch went on is the most valuable thing produced all day, and it takes ten seconds: the whole grid in frame with a tape laid across it, and a second shot of the manifold end with the filter and regulator visible. Two years on, when a fence post has to go in or a shrub is being lifted, that photograph is the difference between a careful dig and a repair coupling. Write the zone card alongside it — product and emitter spacing, lateral spacing, metres of tube on the station, the depth per hour the grid works out at, the filter mesh, the regulator pressure and the peak-season programme — and the next person to stand in front of that controller inherits a system rather than a mystery.

Then book the first-season revisit rather than waiting for the call. Flush the laterals, pull and rinse the filter element, dig the trowel slot again now the planting has grown into the bed, and move the seasonal adjust rather than rewriting the programme. A drip bed that is checked once in its first summer tends to be a drip bed nobody phones about, which is the whole point of putting the arithmetic in before the tube came off the roll.

Settled before the tube comes off the roll

Six things decide both the schedule and the delivery, and five of them are cheaper to establish standing in the bed with a tape than to correct once the bark is spread over the top.

  • Emitter discharge and pitch, read off the box — Both are fixed by the part number. Confirm them against the product data sheet at the pressure the regulator will actually deliver, not at the top of the discharge table.
  • Lateral spacing chosen against the soil, not the price — Tight on sand where the bulb runs straight down, wider on a heavy soil that spreads. A trial run and one trowel pit answers it for this bed in an hour.
  • Gridded area, kept separate from the bed outline — The rate applies between the outermost laterals and emitters. The margin outside them is planting position, not watered ground.
  • Metres of tube on the station, added up before grouping — Discharge divided by pitch gives litres per hour per metre. Multiply by the metres, then check it against the run-length table and the supply, in that order.
  • Head assembly specified: filter, regulator, air relief — Mesh and outlet pressure both come from the dripline data sheet. Backflow protection is the water purveyor's call and belongs in the conversation before the trench.
  • Mulch volume against the soil surface, with no deduction for tube — Sixteen millimetre laterals displace around half a millimetre of depth across the bed. A ten per cent settling allowance on a seventy-five millimetre spread is fifteen times that on its own.
Open this as a workspace →

Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.

Drawn from

  • ASABE/ICC 802, Landscape Irrigation Sprinkler and Emitter Standard
  • ASABE/ASAE EP405.1, Design and Installation of Microirrigation Systems
  • ISO 9261, Agricultural irrigation equipment — Emitters and emitting pipe — Specification and test methods
  • FAO Irrigation and Drainage Paper 56, Crop Evapotranspiration — Guidelines for Computing Crop Water Requirements
  • WUCOLS IV, Water Use Classification of Landscape Species, University of California Cooperative Extension
  • Irrigation Association, Landscape Irrigation Scheduling and Water Management
  • USDA NRCS National Engineering Handbook, Part 623, Chapter 2, Irrigation Water Requirements
  • International Plumbing Code, Section 608, Protection of Potable Water Supply
  • The Water Supply (Water Fittings) Regulations 1999, with the Water Regulations Guide's treatment of garden irrigation risk
  • ANSI A300 (Part 2), Soil Management — Standard Practices for Tree, Shrub, and Other Woody Plant Management
  • AS 4454, Composts, Soil Conditioners and Mulches
  • BS 8545, Trees: from nursery to independence in the landscape — Recommendations
  • Manufacturer design literature for inline dripline — Netafim Techline, Rain Bird XFS, Toro DL2000 and Rivulis — for maximum run length, filtration and regulator pressure

Guidance, not a specification. Local codes, the engineer of record and the product manufacturer’s instructions govern where they differ from anything written here.