A strip along the eaves against ice dams, or a lining down every valley.
Both are the same self-adhering membrane, worked differently: the eave strip is a width up the slope from the drip edge, measured from the wall line; a valley lining is a width laid centred down each valley, along its whole sloping length, under the shingles or the metal.
The combined length of all eaves requiring ice barrier protection.
Add every eave that needs protecting, on every plane, measured along the eave in plan. A simple gable has two; a hip has four; a roof with dormers has an eave under each one. Gable ends are rakes and are not eaves — they shed rather than collect, and including them buys membrane for the two edges least likely to dam. Valleys need their own treatment and are not covered by this.
The horizontal distance the roof overhangs beyond the exterior wall line.
The plan distance from the outside face of the exterior wall to the edge of the roof. This matters here more than it looks: the code requires the barrier to reach a set distance INSIDE the wall line, so the overhang is added to that distance, and every extra 100 mm of overhang is another 100 mm of membrane along the whole eave. Measure to the wall's outer face, not to the fascia.
How far the membrane must extend past the interior face of the exterior wall line, per IRC R905.1.2.
IRC R905.1.2 sets this minimum at 24in for most cold climates; check your local jurisdiction's amendments.
The roof's slope, expressed as rise per 12 units of run — used to convert horizontal coverage distance to along-slope distance.
Pitch is what turns the code's horizontal distance into the material you actually buy: the steeper the roof, the more slope length it takes to cover the same horizontal distance. A 4/12 roof needs about 5% more membrane than the plan distance; a 12/12 roof needs 41% more. On a roof with planes at different pitches, work each plane separately rather than averaging. The field starts at 1 in 12 because a flat roof has no slope to convert. A roof covered in a membrane system rather than shingles or tiles is sealed whole rather than in a strip at the eaves, so this page does not apply to it.
Ice dam membrane area needed
246 sq ft
- Membrane width (along slope)
- 3.73 ft
They open the calculator with your figures already in it
Roof Eave Ice Dam Protection Membrane Footprint (and Valley Lining): 246 sq ft — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- IRC R905.1.2: self-adhering ice barrier membrane must extend from the eave edge to at least 24in inside the building's exterior wall line, measured along the roof slope
- IRC R905.2.8.2, valleys under asphalt shingles: a closed valley lined with one ply of smooth roll roofing at least 36 in (914 mm) wide, an open valley lined with metal at least 24 in (610 mm) wide; self-adhering polymer-modified bitumen underlayment (ASTM D1970) is permitted in place of the lining
Inputs used
- Membrane For
- The eaves (an ice barrier strip)
- Total Eave Length
- 66 ft
- Roof Overhang
- 16 in
- Required Coverage Inside Wall Line
- 24 in
- Roof Pitch (rise per 12)
- 6
- Total Valley Length (along the slope)
- 30 ft
- Valley Lining Width
- 36 in
Intermediate steps
- Membrane width (along slope)
- 3.73 ft
What this calculation does not cover
- The two horizontal distances above are added at "the wall line", and a wall has thickness. R905.1.2 measures its 24in from the INSIDE face of the exterior wall, while an overhang is normally dimensioned from the OUTSIDE face of the framing or sheathing — so the 150 to 300 mm between those two faces belongs in the membrane width and is in neither box. On a thick wall, or one with exterior insulation, the membrane stops short of the point the code actually names.
- Gives a flat area, and the membrane is bought in rolls of fixed width — commonly 900 mm — that overlap at every side and end lap. The default inputs need a 1.13 m width, which is wider than one roll, so it goes on as two courses with a lap between them, and the sheet area to order runs above this figure by the lap on every seam plus the cut-off at each end of a run.
- Eaves only. The same membrane is normally run up every valley, behind sidewalls and dormer cheeks, around chimneys and skylights, and across any section shallow enough to need it — none of that is in this number, and on a cut-up roof it is often more area than the eaves themselves.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
Part of bigger jobs
This trade is one line of several job takeoffs. Run the whole job and every other trade comes back with it, off the same measurements.
also measuresRoofing ShingleRoofing UnderlaymentRoof Ridge CapRidge Vent Linear FootageRoof Truss Spacing & Count
also measures10 other trades
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-10-11 · v1.0.1
Regulatory standards & verification citations2
- IRC R905.1.2: self-adhering ice barrier membrane must extend from the eave edge to at least 24in inside the building's exterior wall line, measured along the roof slope
- IRC R905.2.8.2, valleys under asphalt shingles: a closed valley lined with one ply of smooth roll roofing at least 36 in (914 mm) wide, an open valley lined with metal at least 24 in (610 mm) wide; self-adhering polymer-modified bitumen underlayment (ASTM D1970) is permitted in place of the lining
Which documents these citations point at
- International Residential Code — R905.1.2, R905.2.8.2 (United States)One- and two-family dwellings and townhouses up to three storeys — structure, fire safety, energy, plumbing, mechanical and electrical in a single document.
Standards referenced: ASTM D1970 (ASTM International, United States).
A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.
Cite this page
Your workspace
Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.
Tools and safety for this job
To lay the roof underlay. Generic types, no brands, no prices.
Protection this work requires
- Most fatal falls on small jobs are from under three metres: use a tower or a ladder tied at the top, and never work off the top two rungs.
- Knives cause more site injuries than any power tool: cut away from your body, change blades often, and wear cut-resistant gloves to EN 388 level C for repeated cutting.
Show the 3 tools this job needsHide tools
Essential
Tape measure
Utility knife
Recommended
Staple gun
Also needed as materials: replacement blades, staples.
what each roofing tool is for, and the spec that decides which to buy where one does.