The Plate on the Back Panel
A stove arrives on a pallet, shrink-wrapped, with its manual in a polythene bag taped inside the firebox and a stamped metal plate screwed to the back panel. Every argument this job is going to have — how close the appliance may sit to the stud wall behind it, what the connector pipe is allowed to pass through, how far the floor protection runs out past the loading door, what flue diameter the collar will accept — is settled on that plate and in that bag. Both get read before anybody cuts a hole in a ceiling.
The plate exists because the appliance was tested as a complete assembly against a listing standard: UL 1482 for solid-fuel type room heaters in North America, the EN 13240 family for roomheaters in Europe. The clearances printed on it are the distances at which the surrounding surfaces stayed inside the temperature rise the test allows, measured on that stove in that rig. They are not a rounded-up guess, and they hold only for the configuration that was tested. Swap the connector for another maker's, stand the appliance diagonally in a corner instead of flat to a wall, or add a shield the manual does not describe, and the label has stopped describing your installation.
An unlisted appliance is a different job entirely. A salvaged parlour stove, a shop-welded barrel heater, an import with no plate — none of them carry tested clearances, so the code's default takes over, and the default in the NFPA 211 and IRC Chapter 10 lineage is a large fixed distance measured in feet rather than inches. It comes down only through the forms of protection those documents tabulate, each with its own conditions on air space and spacer material. That one difference decides more alcove installations than anything else on the drawing.
Framing a Box Around a Tested Distance
A chase is the least interesting thing a framer builds and one of the easiest to build wrong. It carries no load, it is four studs and some plates, and its inside dimension is set by a document the framer has usually not been handed. Whoever frames it is working to a figure that came off a chimney manufacturer's installation sheet, and when that sheet is still in somebody else's van the opening gets framed to whatever looked about right.
The arithmetic is not the hard part. The rough opening is the outside dimension of the chimney across the middle, plus the required clearance once on each side — and that doubling is what gets missed. A two-inch clearance around an eight-inch casing wants a twelve-inch opening, not a ten-inch one. Round pipe in a square hole is measured the same way, on the diameter, because the clearance has to hold at the closest point and the closest point is where the circle faces the middle of each stud.
The gap is then maintained by parts, not by intention. Firestop spacers at every floor and ceiling penetration, a support box at the appliance end where the system calls for one, a proprietary shield where the run passes through a ventilated loft — each is a listed component whose job is to hold the pipe central and stop somebody filling the space later. On an air-cooled system that space is the insulation. It is not a void waiting for a bag of loose fill, and treating it as one is the defect a sweep reports most often.
It is also a defect somebody built deliberately. A chase framed correctly and then insulated out to the sheathing line by a crew who saw a cavity has had its clearance removed by a trade that never read the chimney sheet and had no reason to. Mark the chase on the drawing, mark it on the framing itself, and tell the insulation contractor in writing that this cavity is not theirs.
The top of the chase is a small roof in its own right: a pan sloped away from the pipe, a storm collar bedded on the flue above it, counterflashing lapped by whatever the chase is clad in, and a cap sized to the system. Termination height comes from the same documents as the clearances — the chimney extends a stated distance above the point where it passes through the roof, and a further distance above any part of the building within a horizontal radius of it, the three-two-ten arrangement in NFPA 211 and the IRC. A chase built tall enough to look right and not tall enough for that rule gets rebuilt in October, when the stove will not draw.
What a stove and its flue are made of
- Storm collar and rain cap — closes the top of the system against rain and downdraught, and is sized to the chimney, never to the chase opening
- Framed chase — studs, plates and sheathing built to an inside dimension the chimney manufacturer sets, not to a stock stud bay Fireplace/Chimney Chase Framing Clearance Calculator
- Chimney shell — the outer casing or masonry the clearance is measured from, and the dimension the chase opening is built around
- Flue liner — carries the gas and the acid condensate, and grows measurably against the cold masonry every time the stove is lit Firebrick Chimney Liner Thermal Expansion Calculator
- Ceiling support box — a listed component that takes the weight of the run and holds the clearance at the penetration it passes through
- Single-wall connector — the pipe between stove collar and chimney, with its own clearance figure that is usually larger than the appliance's
- The appliance — rated for a heating area by its maker, and oversizing it is what makes a flue run cool and tar over Wood Stove & Fireplace BTU Calculator
- Floor protection — an assembly with a stated extent and a stated thermal resistance, added up layer by layer rather than bought as a product R-Value Calculator
Take the casing dimension off the chimney manufacturer's sheet and the clearance off the same sheet, and the opening follows — with the clearance counted once on each side, which is the half of it people leave out.
The width of the chimney or flue assembly itself.
The depth of the chimney or flue assembly itself.
The minimum clearance from the chimney/flue to any combustible framing, per the manufacturer's listing.
Required chase opening area
3.89 ft²
Clearance-to-combustibles is appliance- and chimney-system-specific per the manufacturer's listing and the applicable fuel gas/mechanical code (NFPA 211 governs solid-fuel chimneys) — always use the exact clearance from your specific unit's installation instructions, never an assumed value.
- Chase opening width
- 2.33 ft
- Chase opening depth
- 1.67 ft
They open the calculator with your figures already in it
Fireplace/Chimney Chase Framing Clearance Calculator: 3.89 ft² — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
What this calculation does not cover
- The airspace this opening creates has to stay empty for the life of the chase. It is the ventilated gap that keeps framing below its ignition temperature, so blowing attic insulation across it, or packing mineral wool into it because the chase feels cold, voids the very listing the clearance figure came from — the opening measures right and the framing still chars.
- Nothing here firestops the chase. Where it passes a floor or ceiling the gap around the chimney has to be closed at each level with the material the listing names, usually sheet metal or a listed firestop spacer, and a chase left open top to bottom is a vertical shaft that takes a basement fire into the attic in minutes.
- Flue termination height is a separate rule this page does not reach: the chimney has to finish at least 3 ft (0.91 m) above the roof where it passes through and 2 ft (0.61 m) above anything within 10 ft (3 m) of it. A chase framed to exactly the right clearance around a flue that stops short still pushes smoke back into the room every time the wind swings.
How Much Stove the Room Actually Wants
Wood stoves are oversized far more often than they are undersized, and the oversized one is the worse outcome. Run below its design output it smoulders, the flue runs cool, tar condenses in the top third of the chimney where the gas is coldest, and the glass blacks over on the first still evening. The occupant closes the air down further because the room is too hot, which accelerates all of it. A stove that has to work near its rated output through most of the winter burns clean and stays clean.
The connected volume decides the size, not the room the stove stands in. An open plan where the living space, the stair and a landing all share air behaves as one large space with poor distribution. A cottage of small rooms behind closed doors behaves as one small space with the rest of the house unheated. Neither is described by the floor area on the plan, which is why a rule-of-thumb figure per square foot needs reading with the layout in front of you and the manufacturer's own rated heating area beside it.
Insulation shifts the answer further than climate does. The forty BTU per square foot that lands about right on a moderate-climate house of ordinary construction is generous for a recently retrofitted envelope and thin for a solid-wall cottage with single glazing. Treat the output as a bracket to test a shortlist against, then let the rated heating area and the burn time between reloads choose between two stoves inside that bracket.
Enter the length and width of the space that genuinely shares air rather than the room on the plan, and read the result as a bracket to check the shortlist against. It works on floor area, so a vaulted or double-height room is asking for more than the bracket says — and the manufacturer's rated heating area is the number that settles it either way.
The length of the area you want to heat.
The width of the area you want to heat.
Colder climates need proportionally more heating capacity per square foot.
Recommended heating capacity (BTU/hr)
23,900 BTU/hr
A rough planning estimate — actual heating needs also depend on insulation quality, ceiling height, and how open the floor plan is to adjacent rooms.
- Space area
- 598 sq ft
They open the calculator with your figures already in it
Wood Stove & Fireplace BTU Calculator: 23,920 BTU/hr — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 23,900 BTU/hr — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- This sizes from floor area alone. There is no ceiling height or volume input, so a vaulted or cathedral room, a double-height space, or a stove on a lower floor with an open stairwell all read the same as a flat-ceilinged room of the same footprint, and all hold considerably more air to heat than this figure assumes.
- Insulation, air-tightness and glazing are not inputs. The climate selector is the only lever in the model, and it moves the answer across the whole 30-60 BTU per square foot band on its own. An uninsulated house with single glazing and a recently air-sealed one of the same footprint in the same town get an identical number here.
- This is a heat-output estimate, not an installation design. It says nothing about clearances to combustibles, hearth and floor protection, flue and chimney sizing, or combustion and make-up air for a tight house. A solid-fuel appliance install is governed by the manufacturer's listing and by local code and has to be inspected on that basis, not on a BTU figure.
- A manufacturer's published maximum output is not directly comparable to this number. Those ratings come from a laboratory test burn on prepared fuel; sustained output on your own cordwood, at your species and moisture content, is lower. Sizing to a peak rating and then damping the stove down to avoid overheating is what builds creosote in the flue.
- A stove is a single point source, and this assumes the heat reaches everything you measured. Closed doors, corridors and rooms off the stove room will stay cold while the stove room overheats, and no allowance is made for fans, ducting or a heat-distribution kit.
The Building Is Competing for the Same Air
A naturally aspirated stove has no fan. It takes combustion air out of the room and relies on the buoyancy of hot flue gas to pull it, which puts it in competition with every other opening in the envelope and loses it to anything with a motor. A range hood at boost, a dryer, two bathroom fans and a central vacuum can between them hold a tight house several pascals negative, while a stove flue develops only a few pascals of draught when it is warm and close to none when it is cold.
The failure is not a smoky room, or not only that. It is spillage: flue gas leaving through the door seal and the connector joints instead of going up the chimney, carrying carbon monoxide into the space with it. It arrives at exactly the wrong moments — a cold flue at start-up, a reload with the door open, a windy evening with the extract running while dinner cooks. A carbon monoxide alarm is required by the adopted residential code wherever a fuel-burning appliance is installed, and it is the last line of defence, not the design.
Screen it with arithmetic long before anyone books a test. A blower-door result, its reference pressure, and a total of everything that can exhaust at once feed the envelope power law, and that law extrapolated down from the test pressure estimates how negative the building goes. A house that needed five hundred litres per second to hold fifty pascals, then asked to give up two hundred and fifty litres per second with nothing coming back, lands near seventeen pascals negative — against a cap that in the CSA F326 lineage is a small single-digit number. That is not a marginal result to argue about.
Only three remedies exist and all of them are structural. Interlock a powered makeup-air unit to the exhaust appliance that causes the problem so it runs whenever that appliance runs. Move to a sealed-combustion stove drawing its air from outdoors through a direct-air kit the appliance and the chimney are both listed for. Or reduce the exhaust. What is not a remedy is a passive hole in a wall with no damper on it, and neither is a line in the handover pack asking the occupants to open a window before lighting the stove — that is a control which depends on a person doing something in an order nobody wrote down.
- Total every exhaust device that can run simultaneously — range hood at boost, dryer, each bathroom and utility fan, central vacuum, and the exhaust side of any recovery unit — at real flows rather than nameplate.
- Take envelope leakage and its reference pressure from the blower-door report for the same envelope, in the configuration the worst-case test will use.
- Run the screening estimate before the appliance is ordered, while a sealed-combustion model is still a specification decision and not a change order.
- Where the estimate lands anywhere near the limit, book the worst-case test: envelope closed, every exhaust running, interior doors in their least helpful positions, manometer referenced outdoors.
- Confirm both the depressurisation limit and the exhaust capacity that triggers mandatory makeup air with the local authority, because both are jurisdictional and neither travels between provinces or states.
- Retest after any later work that tightens the envelope or adds an extract, since the figure that passed at handover described the house as it stood that day.
Pair the blower-door leakage with the pressure it was measured at, total the exhaust honestly, and the power law says whether this house can host an atmospheric appliance at all — before the stove is on order.
Airflow the blower door had to move to hold the envelope at its reference pressure.
Pressure difference the leakage figure above was measured at.
Exponent in the leakage power law, from a multi-point test report where one exists.
Everything that can exhaust at once: range hood, dryer, bathroom fans, central vacuum, and the exhaust side of the recovery unit.
Supply air the ventilation system delivers while the worst case is running.
Dedicated makeup air that is interlocked to open or run whenever the large exhaust appliance does.
The cap the governing code or standard applies to this building.
Worst-case envelope depressurisation
17 Pa
This configuration exceeds the limit on the power-law estimate, and the remedies are interlocked makeup air, a sealed-combustion appliance, or a smaller hood — never a note in the handover pack asking the occupants to crack a window. Confirm with a blower door and a manometer before changing the design.
- Net exhaust flow across the envelope
- 529.72 CFM
- Permitted depressurisation
- 5 Pa
- Margin to the limit
- -12.21 Pa
- Net exhaust the envelope carries at the limit
- 237.18 CFM
They open the calculator with your figures already in it
Worst-Case Envelope Depressurisation Calculator: 17.21 Pa — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 17 Pa — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- Ignores stack effect and wind, both of which add to or subtract from the mechanical pressure and can dominate on a cold or exposed day.
- Treats the envelope as one zone. A closed interior door between the exhaust and the leakage it draws through creates a worse local pressure than this whole-building figure.
A Liner That Grows Inside Masonry That Does Not
Where the stove is being connected into an existing masonry chimney rather than a factory-built system, the liner becomes the component the installation lives or dies on. Clay liners to ASTM C315, firebrick, and cast-in-place refractory all do the same three jobs: carry the gas, keep the products of combustion out of the masonry, and resist the acid condensate that forms whenever the flue runs cool. All three also get far hotter than the brickwork around them, quickly, every time the appliance is lit.
That difference is a movement problem before it is anything else. Fireclay refractory expands at roughly five and a half parts per million per degree Celsius, and a wood flue commonly runs between two hundred and fifty and five hundred degrees in normal operation. Take a six-metre liner from a twenty-degree install temperature through a four-hundred-degree rise and it grows about thirteen millimetres over its length — half an inch of movement inside a stack that has no intention of moving with it.
Thirteen millimetres has to go somewhere. Accommodated, it goes into the joints the liner system was designed with and into whatever gap was left at the termination. Unaccommodated, it goes into cracked sections, a lifted crown, or a liner that has quietly pushed the top course of brick out of line over a decade of heating cycles. Refractory mortar of the kind tested to ASTM C199 is formulated for the heat and for some movement, but it is a mortar and not an expansion joint; manufacturers still specify accommodation gaps on longer runs and at the top. ASTM C1283 sets out the installing practice for clay lining and is the document to work from rather than habit.
Two arithmetic traps sit inside the same short calculation. The first is the temperature field, which wants the rise from installation to peak and not the flue reading, so a flue at five hundred degrees off a twenty-degree install is a four-hundred-and-eighty-degree rise. The second catches anyone working in Fahrenheit: a temperature difference converts by nine fifths with no thirty-two degree offset, so that same rise is eight hundred and sixty-four Fahrenheit degrees, not the nine hundred and thirty-two the flue itself reads. Typing the reading where the rise belongs overstates the movement by about eight per cent, and it is the easier of the two to do without noticing.
Chimney fires sit outside all of it. A flue fire runs far above normal operating temperature and asks the liner to take that rise in minutes rather than over an evening, and an allowance sized for normal service is not what keeps the stack intact through one. That is a reason the sweeping interval matters more than any number on this page.
Enter the vertical run and the temperature RISE — not the flue reading — with the coefficient from the liner product's own data sheet, and the result is the movement the top of the system has to be built to swallow.
The total vertical run length of the firebrick liner section being checked.
The difference between installation temperature and expected peak operating temperature.
The specific firebrick material's coefficient of thermal expansion, per °C.
Expansion gap needed
0.515 in
The thermal expansion coefficient varies meaningfully between different firebrick/fireclay formulations — use the specific manufacturer's published value for an accurate result on a critical installation.
They open the calculator with your figures already in it
Firebrick Chimney Liner Thermal Expansion Calculator: 0.5148 in — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Add the equipment this sizes
This result is a specification — 0.515 in — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
What this calculation does not cover
- The whole run is treated as reaching the peak rise at once. A real flue is hottest at the appliance and cools toward the terminal, so a fully heat-soaked liner is a bounding case rather than what a tall stack sees in normal operation.
- This is the liner's own free expansion, not its movement relative to what encloses it. The masonry chimney, outer stack or steel casing expands as well, and the clearance that actually has to be left is the difference between the two, not the figure given here.
- The coefficient is applied as a single constant. A published value is a mean over the temperature band the manufacturer states, and refractory expansion is not linear across a wide range. Permanent, irreversible dimensional change from first firing or from moisture is a separate movement and is not included at all.
- Only the vertical run you enter is expanded. Circumferential growth of the liner and movement in the mortar or joint filler are not calculated, and the result says nothing about how many expansion joints to use, where they go, or how much of its own thickness a compressible joint material will actually take up.
- This is a movement figure, not an installation specification. It does not replace the liner manufacturer's expansion-joint and fixing instructions, and it checks nothing about clearance to combustibles, support and restraint of the liner, flue sizing, or the condition of the existing chimney.
Four Clearances, Four Documents
The word clearance covers four different distances on a stove installation and they come from four different places. Confusing them is how a job passes a self-check and fails an inspection: the installer read the appliance clearance off the label and applied it to the connector, which usually wants more, or applied the chimney's figure to the stove body, which usually wants less.
Reductions exist for all four and every one of them is conditional. A sheet of non-combustible board screwed flat against the wall reduces nothing at all, because it conducts. What reduces a clearance is a shield with a ventilated air space behind it, held off the combustible surface on non-combustible spacers, open at top and bottom so air moves through the gap, and carried far enough past the appliance that the heat does not simply go round the edge. The tabulated reduction belongs to that whole detail, not to the material anyone bought.
Floor protection is the piece built last and considered least. The listing states what it has to be and how far it runs, and the extent in front of the loading door is always greater than at the sides and back, because that is where embers land during a reload. Where an unlisted appliance falls to the code table instead, the requirement is expressed as a dimension and a thermal performance together — which makes the pad an assembly to be added up rather than a product to be bought.
| Clearance | What it keeps cool | Where the figure comes from |
|---|---|---|
| Appliance to combustible surface | The stud wall, cabinet run or trim behind and beside the stove body | The listing label and manual, from testing to UL 1482 or EN 13240; an unlisted stove falls back to the table in NFPA 211 or IRC Chapter 10 |
| Connector to wall and ceiling | Everything the single-wall pipe radiates onto between the stove collar and the chimney | The same manual, stated separately and usually as a larger distance; NFPA 211 and CSA B365 carry the fallback figures |
| Chimney to combustible framing | Chase studs, plates, joists and sheathing anywhere the chimney passes them | The chimney system's own listing — UL 103 HT for a factory-built system — or the masonry chimney provisions of NFPA 211 and the IRC |
| Floor protection extent | The floor under and in front of the appliance, against embers and radiant heat | The listing label gives material and extent; unlisted appliances take the code's dimensions together with a stated thermal resistance |
A Season of Wood, Ordered a Year Early
Fuel is the part of this job the installer hands over and the occupant gets wrong, and the wrong version damages the appliance that was just fitted. Wet wood cannot burn hot enough to keep the flue above the temperature at which tar condenses, so the tar lines the chimney instead of leaving it. A stove fed on unseasoned wood produces a chimney needing twice the sweeping and glass that blacks over in an evening, and the customer blames the stove.
Under about twenty per cent moisture, measured on a freshly split face rather than the weathered outside of a round, is the target that appliance manuals and the EPA's Burn Wise guidance converge on. Reaching it takes a summer for softwood split small and most of two for dense hardwood split large — stacked clear of the ground, open at the ends, covered on top only. Which is why the woodpile is a first-year decision and not an autumn one: whatever is bought in September is being burned the winter after this one.
Buying it is a measurement problem with a legal answer. A full cord is a stacked pile four feet by four by eight, one hundred and twenty-eight cubic feet, and in the United States the method of sale in NIST Handbook 130 recognises the cord and decimal fractions of it for fireplace and stove wood. Face cord, rick and rack are not units at all — they describe a stack four feet high and eight feet long with the depth left to whatever the seller's log length happens to be, so two sellers' ricks can differ by half. Measure the delivery stacked, on the ground, before the truck leaves the drive.
Then turn the stack into seasons honestly. A neat row two and a half metres long, a little over a metre deep and the same again high is not far off a full cord. How many of those a winter takes depends on the appliance output, the hours it runs and above all the species: the spread between dense hardwood and light softwood by stacked volume approaches a factor of two on the published species tables, which is a larger effect than most people expect and the reason a cord that lasted the neighbour until February runs out here in January.
| Term | Stacked dimensions | What it settles |
|---|---|---|
| Full cord | 4 ft x 4 ft x 8 ft — 128 cubic feet, about 3.62 cubic metres, neatly stacked | The unit the NIST Handbook 130 method of sale recognises for fireplace and stove wood, along with decimal fractions of it |
| Face cord, rick, rack | 4 ft high and 8 ft long, with the depth left to the seller's log length | Nothing until that log length is agreed: a 16 in rick is about a third of a cord, a 24 in rick about half |
| Thrown or loose measure | The volume of the pile as tipped, before anyone has stacked it | Mostly air — a tipped load occupies noticeably more space than the same wood stacked, so measure after stacking and not on delivery |
Measure the row after it is stacked — length along the row, depth front to back, height off the ground — and the result says whether the load that arrived is the cord that was paid for.
The length of the stacked woodpile.
The front-to-back depth of the stack — usually the length of one log.
The height of the stacked pile.
Estimated firewood cord needed
1 cord
- Stack volume
- 128 cubic ft
They open the calculator with your figures already in it
Firewood Cord Calculator: 1 cord — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
What this calculation does not cover
- It treats the pile as a rectangular block of length by width by height. A row that tapers, leans, domes at the top or stands on uneven ground holds less wood than the block implies, and a height taken from the ground rather than from the underside of the lowest log adds the bearers or pallet to the answer.
- The result is stacked volume with the air gaps included, which is how a cord is defined — it is not a measure of solid wood. Nothing here corrects for how tightly the row was built, for crooked or knotty rounds, or for a thrown load that has not been stacked at all; a loose pile of the same outer dimensions holds substantially less wood than a ranked one.
- Species, density and moisture content are not inputs, so a cord of pine and a cord of oak return the same figure. This sizes volume, not heat: it says nothing about usable heat output, burn hours, or whether the wood is dry enough to burn.
- It reports the stack as measured on the day. Wood shrinks across the grain and the pile settles as it seasons, so the same wood re-measured after a season reads as fewer cords, and this calculation does not project that change.
- This is not a determination of what was sold. It converts three measurements into cords; it cannot tell you whether a delivery matched the order, and it does not resolve terms such as face cord, rick or truckload, which carry no fixed depth and vary between sellers.
Sweeping Access, and the First Fire
An installation that cannot be swept will not be swept. Before the chase is closed, walk the run and ask where the rods go in, where the soot comes out, and whether the person doing it has to break a connector joint every visit. A tee with a capped clean-out at the base of the chimney answers all three questions; a series of elbows buried behind plasterboard answers none of them, and the sweep's report will say so in year two.
Commissioning is where the paperwork and the appliance finally meet. The first fire is deliberately small and the manual usually prints a schedule for it — a break-in sequence that cures the paint, drives residual moisture out of any refractory and lets the seals settle without cracking anything. Do it before handover, with the extract fans running for part of it, because spillage found on a commissioning fire is a design conversation and the same spillage found in December is an emergency.
- Check the termination height against the rule with a tape from the roof, not by eye from the ground.
- Verify the clearance at every framed penetration once more before anything is boarded, and photograph each one with a rule in shot.
- Fit the floor protection and any wall shields, then measure the finished clearances to the appliance as installed rather than as drawn.
- Run the break-in fires to the manual's schedule, with the room ventilated and the appliance watched.
- Repeat the spillage check at the end of the break-in with every exhaust device running and the interior doors closed.
- Hand over the manual, the chimney system's data plate details, the sweeping interval and the fuel moisture target in writing, and register the appliance where the manufacturer requires it.
What has to be settled before the appliance is ordered
The stove is the short lead item on this job. These are the six figures that decide whether it fits the chase, whether it will draw at all, and whether the fuel arrives early enough to be dry.
- Chimney casing dimension and its listed clearance — Both come off the chimney manufacturer's installation sheet, and the clearance counts once on each side of the opening rather than once overall.
- Connected floor area the stove is expected to heat — Measure the length and width of the space that genuinely shares air, then read the bracket against the maker's rated heating area rather than against the room on the plan.
- Everything in the house that can exhaust at once — Range hood at boost, dryer, every bathroom and utility fan, central vacuum, and the exhaust side of any recovery unit, totalled at real flows.
- Blower-door leakage with the pressure it was measured at — The pair is what the power law needs — a leakage figure separated from its reference pressure cannot be extrapolated to anything.
- Liner run length and the rise from install to peak flue temperature — The rise, not the flue reading; and a difference converts by nine fifths with no offset when the job is being worked in Fahrenheit.
- Stacked dimensions of the woodpile, taken after stacking — Length, depth and height on the ground, so the delivery is checked as a cord instead of as whatever the seller chose to call it.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.
