The job
Modelled, not recorded. Every figure here is the answer the Insulation R-Value by Climate Zone Calculator (IECC 2021 and NBC 2020) gives for these inputs, written down in both unit systems and re-run whenever the site is built. No job was carried out, so there is no measured overrun on this page.
The house is a detached home being renovated in a Canadian town whose heating degree-days put it in zone 5, the band the code sets between three and four thousand Celsius degree-days. The NBC's Appendix C lists the degree-days for towns across the country, and the province's building code, which adopts the NBC with its own changes, is where a reader confirms both the zone and the table that applies. The question is the one most renovators ask first: how much insulation does the attic ceiling need?
The answer comes from Section 9.36, the energy-efficiency part of the code for houses, and it is expressed differently from what many product labels and American guides use. The table gives an effective thermal resistance, RSI in metric, for the whole ceiling assembly: the insulation together with the framing that interrupts it, the drywall, the air films and anything else in the build-up. A batt's printed rating is its nominal value alone, so meeting the code takes more nominal insulation than the effective figure might suggest.
The job is entered at zone 5 without a heat-recovery ventilator, the choice a Canadian reader's page opens on, because many existing houses have no HRV. The code allows a lower envelope figure where one is fitted, and that case is shown below. Everything on this page is a minimum to check a design against. Whether a particular assembly reaches it is worked out from its layers, by the designer or with the calculation methods the code describes, and the building official decides.
Open this job in the calculator
Embed this calculator on your own page
Every figure is worked again by the real calculators, in both unit systems; nothing is priced and nothing is saved until you press Use as my project.
The inputs, exactly as entered
| Input | Value | Why |
|---|---|---|
| Code and Climate Zone | NBC 2020 (Canada): zone 5 (3000 to 3999 Celsius degree-days), no heat-recovery ventilator | The NBC's zone 5 without a heat-recovery ventilator, the choice a Canadian reader's page opens on; the zone comes from the town's heating degree-days. |
| Part of the Building | Ceiling below an attic | Left at the calculator's own default. |
The working, step by step
1. In RSI (m²K/W)
8.67 m²K/W
The calculator reads the code's table for the zone, the ventilation case and the part of the building, and returns the minimum effective resistance: 8.67 m²K/W. RSI is resistance in metric units, square metres times kelvin per watt, and it is the unit the NBC tables are written in.
2. In R-value (hr·ft²·°F/BTU)
49.23 hr·ft²·°F/BTU
The same resistance restated in imperial units, 49.23 hr·ft²·°F/BTU, because insulation sold in Canada is often labelled with both and many guides quote the imperial figure. The conversion is exact; what is not exact is comparing it with a batt's label, since the label is nominal and this is effective.
3. The same as a whole-assembly U-value
0.12 W/m²K (0.02 BTU/(hr·ft²·°F))
Turned upside down, the resistance becomes a heat-flow rate for the whole assembly, 0.12 W/m²K (0.02 BTU/(hr·ft²·°F)). Designers who model the house as a whole, rather than component by component, work with this figure, and it makes plain that the target describes the assembly, framing included.
4. Windows and doors: U-value at most, in this zone
1.84 W/m²K (0.32 BTU/(hr·ft²·°F))
The same table sets a ceiling on how much heat windows and doors may lose in this zone, 1.84 W/m²K (0.32 BTU/(hr·ft²·°F)), and a separate one for skylights, 2.92 W/m²K (0.51 BTU/(hr·ft²·°F)). They are printed here because a renovation that opens the attic often adds a skylight, and the skylight has its own limit.
Minimum the code tabulates
8.67 m²K/W
The figure to design to is 8.67 m²K/W, effective, for the attic ceiling of a zone 5 house without an HRV. It is a floor, not a recommendation, and the calculator's confidence is medium because the zone and the ventilation case depend on facts about the house and the town that the calculator takes from the reader. A US reader's page reads the same assembly against the IECC instead, and the two cannot be swapped: the American table gives the insulation's nominal value, where the NBC gives the effective value of the whole assembly.
What to buy
| Quantity | Figure | What it is for |
|---|---|---|
| Minimum the code tabulates | 8.67 m²K/W | Nothing is bought from this figure directly: it is the effective resistance the ceiling assembly must reach, to be met by insulation chosen and layered by the designer or installer. |
The allowance, and what it does here
There is no allowance in a code minimum, and none should be added to it. The margin on a real job is elsewhere: loose-fill insulation settles after it is blown, so installers fill to the depth the manufacturer gives for the settled resistance, and batts compressed under storage boards or wiring lose some of their rating. Those are counted by the insulation calculators, with their own allowances, once the target here is known.
The common mistake
Reading the effective RSI as a batt's label rating
The NBC's figure is the effective resistance of the whole ceiling, framing included, and a batt's printed rating is the insulation alone. Where joists or truss chords cross the insulation, wood conducts heat several times faster than the insulation beside it, so the assembly's effective value is lower than the insulation's nominal one. Buying insulation whose label matches the table number leaves the ceiling short. Work the assembly through the code's effective-resistance method, or use an installed depth the manufacturer and the building official accept as meeting the effective figure, and add a continuous layer over the framing where the depth allows.
Change the job, and see what moves
The same ceiling, in a house with a heat-recovery ventilator
Code and Climate Zone: NBC 2020 (Canada): zone 5 (3000 to 3999 Celsius degree-days), with a heat-recovery ventilator → 6.91 m²K/W
With a heat-recovery ventilator in the house, the same zone 5 ceiling's minimum falls to 6.91 m²K/W. The code accepts a lighter envelope because the HRV recovers heat from exhaust air that would otherwise be lost; the window and skylight limits stay as they were.
The same house, for its wood-frame walls
Part of the Building: Wood-frame wall above grade → 3.08 m²K/W
Read the same table for the house's wood-frame walls above grade and the minimum is 3.08 m²K/W, far below the ceiling's. Walls have less depth to fill and are harder to improve once built, which is why an attic ceiling is usually the first and cheapest place a renovation adds resistance.
What to run next
- Attic Insulation Upgrade Calculator
Once the target resistance is known, the upgrade calculator works out the depth of loose fill or the batts to add over what is already in the attic.
- Attic and Loft Ventilation Calculator (Intake, Exhaust and Vent Count)
Adding insulation to an attic goes with checking its ventilation, which the NBC sets as a share of the same insulated ceiling.
- Attic Rafter Baffle/Chute Count Calculator
Deeper insulation needs baffles at the eaves so the soffit vents stay open, and they are counted from the eaves length and the rafter spacing.
Sources
The method and every constant behind these figures belong to the Insulation R-Value by Climate Zone Calculator (IECC 2021 and NBC 2020), version 1.0.0, last verified 2026-10-05. It rests on:
- International Code Council, IECC Residential Committee Action Report on the 2021 public input changes, updated 26 July 2022, proposal REPI-33-21: the 2021 IECC Table R402.1.2 (maximum assembly U-factors and fenestration requirements) and Table R402.1.3 (insulation minimum R-values and fenestration requirements by component) with their footnotes, printed as the base text being revised. The 2021 text is everything not underlined: in the ceiling cells the struck figures (R-49 and R-60; U-0.026 and U-0.024) are the 2021 text, and the underlined ones (R-38 and R-49; U-0.030 and U-0.026) are the proposal's
- Cross-checks: Washington County, Maryland, 2021 IECC Residential Energy Efficiency Code compliance form (climate zone 4 except Marine, both tables); US DOE, final determination technical support document for the 2021 IECC (changes from 2018: ceilings R-49 and R-60, zone 4 and 5 walls 20+5ci, slabs R-10 at 2 ft and 4 ft, fenestration 0.30); Maine 16-642 CMR ch. 6 §6 (amending the zone 6 and 7-8 wall entries); Delaware DNREC, 2021 IECC residential changes (R402.2.1: R-38 for R-49 and R-49 for R-60 where uncompressed insulation extends over the top plates at the eaves)
- Pacific Northwest National Laboratory (T. L. Gilbride et al.), Guide to Determining Climate Zone by County: Building America and IECC 2021 Updates (September 2022), the 2021 IECC climate zone of every US county
- National Research Council of Canada, National Building Code of Canada 2020, Division B: 9.36.1.2.(3) effective thermal resistance (RSI) as the inverse of an assembly's U-value; 9.36.1.3 compliance paths; Tables 9.36.2.6.-A and -B (above-ground opaque assemblies without and with a heat-recovery ventilator), 9.36.2.6.(3) the attic reduction near the eaves; Tables 9.36.2.7.-A and -B (fenestration, doors, skylights); Tables 9.36.2.8.-A and -B (below grade), 9.36.2.8.(3)–(9); Article 1.1.3.1 and Appendix C Table C-2 for degree-days
This job is one of that calculator’s published test vectors, which the test suite re-runs on every build.
Frequently asked questions
- How much attic insulation does the NBC require in zone 5?
- For a ceiling below an attic in a house without an HRV, an effective 8.67 m²K/W, which is 49.23 hr·ft²·°F/BTU in imperial units. With an HRV, 6.91 m²K/W. The province's adoption of the NBC governs.
- Is the NBC's RSI the same as the rating on a batt?
- No. The code's figure is effective, for the whole assembly with its framing, while a batt's label is nominal, for the insulation alone. Meeting 8.67 m²K/W effective takes more nominal insulation than that figure.
- Why does a heat-recovery ventilator lower the requirement?
- Because the HRV recovers heat from the air the house exhausts, the code accepts less resistance in the envelope: here 6.91 m²K/W instead of 8.67 m²K/W for the attic ceiling.