SettingsSettings for this calculationUS
The height of soil against the wall, from the base slab to the ground surface behind it.
Take it from the underside of the base, or the level the wall is designed to span from, to the finished ground behind the wall — not to the top of the wall where it stands proud of the ground.
At rest for a wall held by the floor at its head; an entered value for anything else the designer has set.
A basement wall propped by the ground-floor slab cannot move away from the soil, so the soil stays at rest and the at-rest coefficient applies. Enter a coefficient instead where the design has fixed one — an active coefficient for a wall genuinely free to rotate, or a value from the ground investigation.
The drained friction angle of the retained soil, from the ground investigation.
A well-graded granular backfill commonly sits in the low to mid thirties and a clay lower. It is the effective, drained angle — the one that governs a wall in the long term — and it comes from the report or the fill specification, not from a table chosen afterwards.
1 for normally consolidated soil and placed fill; higher for ground that was once under more load.
Eurocode 7 raises the at-rest coefficient by the square root of the OCR and warns against the formula at very high ratios, which is why this field stops at 4. A heavily overconsolidated clay behind a wall is a question for the geotechnical engineer rather than a larger number here.
The weight of the retained soil as it is in service, water in the pores included.
The moist, not the dry, figure: backfill in service is never oven-dry, and the dry figure from a compaction report leaves the pore water out of the driving load. The soil phase relationships calculator converts a laboratory sheet into it.
The weight of the soil with its voids full, used below the water table.
The page takes the buoyant weight from it — the saturated figure less the unit weight of water — for the soil below the water table, and carries the water as its own load.
How far below the retained surface the design water level sits; the full height or more means no water on the wall.
The DESIGN water level, which is a decision rather than the level seen in the excavation on the day: the highest the water can credibly reach against the finished wall, from standpipe readings over a season, flood levels and the site's drainage. Zero puts the water at the surface.
A load spread over the ground behind the wall — a drive, stored material, a building's floor.
It adds the coefficient times the surcharge at every depth, a rectangle on the pressure diagram rather than a triangle. A line load or a strip footing close to the wall does not spread like that and needs its own treatment.
Total thrust on the wall per unit run
3,450 lbf/ft
At rest: the soil stays where it was placed, which is the state of a wall propped by the floor at its head. A wall genuinely free to lean away could use the lower active coefficient, but only if it can move enough to earn it. Below the water table the soil contributes only its buoyant weight times the coefficient, and the water acts on top of it at full hydrostatic pressure.
- At-rest coefficient K0
- 0.5
- Soil pressure at the base
- 464.55 psf
- Water pressure at the base
- 312.25 psf
- Total pressure at the base
- 776.8 psf
- Soil thrust per unit run
- 2,673.27 lbf/ft
- Water thrust per unit run
- 780.62 lbf/ft
- Height of the resultant above the base
- 3.13 ft
They open the calculator with your figures already in it
Basement Wall At-Rest Earth Pressure Calculator (with Groundwater): 3,454 lbf/ft — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- BS EN 1997-1 (Eurocode 7), 9.5.2: for a horizontal ground surface the at-rest coefficient is K0 = (1 − sin φ′) × √OCR, not to be used for very high overconsolidation ratios; with OCR = 1 it is Jaky's relation, K0 = 1 − sin φ′
- Effective-stress earth pressure with the pore water on its own line: horizontal pressure = K × σ′v on the soil skeleton plus γw × depth below the water table, the water taking no earth-pressure coefficient because it has no shear strength (Craig's Soil Mechanics; CIRIA C760); IBC 1610.1 requires at-rest pressure for walls restrained from moving at the top
Inputs used
- Retained Height
- 10 ft
- Earth Pressure Coefficient
- At rest, from the friction angle (Eurocode 7 9.5.2)
- Effective Friction Angle φ′ (degrees)
- 30
- Overconsolidation Ratio (OCR)
- 1
- Earth Pressure Coefficient K
- 0.5
- Moist Unit Weight Above the Water Table (γ)
- 120.95 pcf
- Saturated Unit Weight Below the Water Table (γsat)
- 127.32 pcf
- Depth to the Water Table Below the Ground Surface
- 5 ft
- Uniform Surcharge at the Surface
- 0 psf
Intermediate steps
- At-rest coefficient K0
- 0.5
- Soil pressure at the base
- 464.55 psf
- Water pressure at the base
- 312.25 psf
- Total pressure at the base
- 776.8 psf
- Soil thrust per unit run
- 2,673.27 lbf/ft
- Water thrust per unit run
- 780.62 lbf/ft
- Height of the resultant above the base
- 3.13 ft
Confidence note: At rest: the soil stays where it was placed, which is the state of a wall propped by the floor at its head. A wall genuinely free to lean away could use the lower active coefficient, but only if it can move enough to earn it. Below the water table the soil contributes only its buoyant weight times the coefficient, and the water acts on top of it at full hydrostatic pressure.
What this calculation does not cover
- Characteristic, unfactored pressures for a screening check. A design applies the partial or load factors of the code in force, and the structural engineer sets the design water level and the coefficient the wall is designed to.
- Horizontal ground behind the wall. A slope rising away from the wall increases the at-rest coefficient — Eurocode 7 multiplies it by (1 + sin β) — and is not modelled here.
- Compacting backfill in layers against a propped wall can lock in pressures above the at-rest figure near the top of the wall. AASHTO LRFD 3.11 and CIRIA C760 set out methods for it; this page does not add them.
- The water is static and the soil's cohesion is ignored. Seepage towards a drained wall changes the pore pressures, and a line load or strip footing close to the wall adds pressure that a uniform surcharge does not represent.
Add the equipment this sizes
This result is a specification — 3,450 lbf/ft — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-22 · v1.0.0
Regulatory standards & verification citations2
- BS EN 1997-1 (Eurocode 7), 9.5.2: for a horizontal ground surface the at-rest coefficient is K0 = (1 − sin φ′) × √OCR, not to be used for very high overconsolidation ratios; with OCR = 1 it is Jaky's relation, K0 = 1 − sin φ′
- Effective-stress earth pressure with the pore water on its own line: horizontal pressure = K × σ′v on the soil skeleton plus γw × depth below the water table, the water taking no earth-pressure coefficient because it has no shear strength (Craig's Soil Mechanics; CIRIA C760); IBC 1610.1 requires at-rest pressure for walls restrained from moving at the top
Which documents these citations point at
- Eurocode 7 — Geotechnical design (BS EN 1997) (European (EN))Foundations, retaining structures and slopes, and the ground investigation they rest on.
- International Building Code — 1610.1 (United States)Buildings other than the dwellings the IRC covers — occupancy, egress, fire resistance and structural provisions.
A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.
Cite this page
Your workspace
Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.