Geotechnical

Reading a Soil Report

A lab sheet gives specific gravity and dry density; a wall check wants moist and buoyant unit weight. The conversion between them, and where it goes wrong.
  • 20 minReading time
  • 12Sections
  • 5Calculators inline
  • Last reviewed

Four Numbers, and Only One of Them Is a Unit Weight

Borehole BH-3, sample at 4.2 m, and the laboratory has sent back one sheet. A grading curve, liquid and plastic limits, a classification symbol, water content 18.4 per cent, dry density 1.66 Mg/m³, specific gravity of solids 2.68. On the other side of the desk is a retaining wall check that wants the moist unit weight of the retained soil above the water table and the buoyant unit weight of everything below it. Neither figure appears anywhere on the sheet, and neither is missing. They are derived, and the derivation is four lines long.

The laboratory stopped where it did on purpose. Dry density is something a technician measured on a specimen of known volume; saturated unit weight is a claim about a condition that specimen was never in. The moment a lab writes γsat it has assumed the voids are completely full of water — a statement about your site rather than about the material in the mould — and a buoyant weight assumes a water table it has not seen. That division is correct, and it is why the conversion belongs to the engineer holding the drawing.

All of it runs on one idea. Take any volume of soil and it is three things — mineral solids, water, and air — and every quantity on the sheet is a ratio between two of them. Specific gravity fixes how heavy the solids are compared with water. Dry density fixes how much solid there is in a given volume. Between them they fix everything else on the page, and the quantity that carries the information from one to the other is the void ratio.

What each row of a routine classification sheet is for
Row on the sheetTest behind itWhat the design does with it
Specific gravity of solids, GsWater pycnometer to ASTM D854, or BS EN ISO 17892-3, or AASHTO T 100Nothing on its own — it is the bridge that turns a measured density into a void ratio
Dry densityLaboratory specimen to ASTM D7263, or in place by sand cone to ASTM D1556 or nuclear gauge to ASTM D6938Multiplied to a unit weight, then straight into the void ratio
Water content, wOven drying to ASTM D2216Turns the dry unit weight into the weight the ground actually has today
Maximum and minimum index densityVibratory table to ASTM D4253 and the loosest-state method of ASTM D4254Supplies emax and emin, without which relative density has nothing to compare against
Grading and Atterberg limitsASTM D6913 sieve analysis and ASTM D4318, classified by ASTM D2487Decides whether relative density is even the right way to describe this soil's compactness
What each row of a routine classification sheet is for

Density, Unit Weight, and the Number That Is the Same in Both

A metric laboratory reports density, in Mg/m³ or g/cm³, and the calculators here take unit weight. Density is mass per unit volume and unit weight is force per unit volume, so the conversion is gravity: a dry density of 1.66 Mg/m³ — identical to 1.66 g/cm³, the sheet may use either — becomes 1.66 × 9.81 = 16.28 kN/m³. That single multiplication is the most common thing to leave out, and leaving it out understates the weight of the ground by an order of magnitude, which is large enough that it usually gets caught. The dangerous errors are smaller.

Imperial practice hides the distinction, and hides it in a way that never fails locally. The same soil is 103.6 lb/ft³ as a mass density and 103.6 lbf/ft³ as a unit weight, because the pound-mass and the pound-force were defined to make that true at standard gravity. A sheet reading 103.6 pcf is therefore correct whichever quantity the reader believes it to be, and nothing goes wrong until somebody converts to SI and has to pick. One lbf/ft³ is 0.1571 kN/m³, so 103.6 × 0.1571 = 16.28 kN/m³ — the same soil by the other road. Water is the reference at either end, 9.81 kN/m³ or a shade over 62.4 lbf/ft³, and a conversion that produces a soil lighter than water has gone in upside down.

The dry unit weight field follows the metric and imperial switch at the top of the page, reading kN/m³ or pcf, and a unit weight the calculators return comes back in the same unit; specific gravity and void ratios are pure ratios and read the same either way. The switch cannot turn a density into a unit weight: a metric sheet's Mg/m³ is multiplied by gravity before it goes in, as above, while a pcf reading goes in as it stands. The unit weight of water is fixed internally at 9.81 kN/m³, which is fresh groundwater; a pore fluid that is brine, a tailings liquor or a contaminated leachate has a different density and the phase relationships have to be worked longhand with the right value in them.

Specific Gravity Is the Number You Can Borrow, Within Limits

The specific gravity of soil solids is measured with a water pycnometer under ASTM D854, with AASHTO T 100 as the highway equivalent, BS EN ISO 17892-3 as the European particle density method and the corresponding parts of BS 1377 and AS 1289 elsewhere. It is reported against a reference temperature with a correction applied, because water's own density moves with temperature, and a sheet that gives a specific gravity without saying at what temperature has left out part of the result. For ordinary quartz and feldspar soils the answer lands between about 2.60 and 2.75 with dull regularity, which is exactly why it is the number people stop measuring.

There is a limit on the borrowing that catches gravelly fills. ASTM D854 is written for the material passing the 4.75 mm sieve; the coarse fraction is tested separately as a coarse aggregate under ASTM C127 and the two results are combined by mass into a composite value. A single specific gravity quoted for a sandy gravel has, in most laboratories, described only the matrix, and if the gravel is a different rock from the sand — a limestone gravel in a quartz sand, a slag or a recycled concrete — the composite is genuinely different from either. Ask what was tested before assuming the number covers the whole sample.

It helps to know what a borrowed value costs. On the BH-3 sample, a Gs of 2.68 with a dry unit weight of 16.28 kN/m³ gives a void ratio of 0.615. Push the specific gravity to 2.73 — roughly the width of the plausible mineral range — and it becomes 0.645, five per cent higher. Leave it alone and let the dry density be three per cent low at 15.79 kN/m³ instead, and the void ratio goes to 0.665, eight per cent out. The measurement least trusted moves the answer less than a modest error in the one most trusted. That collapses for organic and micaceous soils, iron-rich residual soils and manufactured fills such as ash or slag, where the specific gravity is not 2.65 and no convention makes it so.

Void Ratio Is the Hinge Between the Sheet and the Design

Void ratio is the volume of voids divided by the volume of solids, and it comes out of the two numbers already on the sheet: e = Gs γw / γd − 1. The reasoning reconstructs at a desk. Gs γw is the unit weight the soil would have as solid mineral with no voids at all; divide the real dry unit weight into it and the ratio of total volume to solid volume falls out, which is 1 + e by definition. Porosity measures the same void space against total volume instead, n = e / (1 + e). It is the friendlier number to quote and the wrong one to carry into a settlement calculation, because solid volume does not change under load and total volume does, so only e has a stable denominator.

On BH-3 the arithmetic runs 2.68 × 9.81 = 26.29 kN/m³ for the solids, divided by 16.28 gives 1.615, and the void ratio is 0.615 with a porosity of 38.1 per cent. That is an unremarkable figure for a firm clay and it should be treated as a sanity check rather than a result: dense sands and stiff clays sit in the region of 0.4 to 0.7, loose sands and soft clays run higher, and a soft organic silt can be above 1.5 without anything being wrong. A void ratio that arrives negative means the dry unit weight exceeds Gs γw, which is physically impossible and means a unit conversion has gone missing upstream.

Give it the specific gravity from the pycnometer test and the dry unit weight after you have converted it to kN/m³, and read the porosity in the breakdown as a second opinion on whether the answer is plausible for the material described on the sheet.

The soil particles' specific gravity.

The soil's dry unit weight, from a lab or field density test.

Void ratio

0.5755 (e)

High confidence
Equivalent porosity
36.53 %

What this calculation does not cover

  • The dry unit weight has to be genuinely dry. There is no moisture content input, so the calculation cannot strip pore water out of a bulk or wet density — feed it an uncorrected nuclear-gauge or sand-cone wet unit weight and the void ratio comes back too low.
  • It separates voids from solids, not water from air. There is no degree of saturation anywhere in the model, so the result carries no water content, no saturated or buoyant unit weight, and nothing about effective stress, buoyancy or seepage below the water table.
  • Specific gravity is defaulted, not measured. 2.65 is a quartz-sand figure; carbonate, mica-rich, iron-rich, volcanic and organic soils sit away from it, and because void ratio is a ratio with one subtracted, a few percent of error in either input turns into a larger percentage error in e.
  • Void ratio is an index property, not a design check. This is not compaction acceptance — that is a Proctor or relative density comparison against a laboratory maximum — and it is not a settlement, bearing capacity or liquefaction assessment. It does not replace a site investigation or a geotechnical engineer's sign-off.
  • One sample, one point in the ground. Nothing here allows for layering across a site, for the oversize gravel and cobbles a field density test leaves out of the sample, or for the void ratio changing as the soil is loaded, drained or remoulded.

Reading the Element Back Out as Four Weights

The same relationship run backwards is what produces the design weights. Rearranging gives γd = Gs γw / (1 + e), which is not a new formula so much as the previous one with the terms moved, and that makes it a free check on your own arithmetic: put 2.68 and 0.615 back in and the answer must be the 16.28 kN/m³ you started with. If it is not, one of the two entries was mistyped, and finding that here costs a minute rather than costing a wall.

Fill every void with water and the same element becomes γsat = (Gs + e) γw / (1 + e). The numerator has grown by the weight of water occupying the void volume, which is why e appears twice with different jobs — once as extra weight, once as extra volume. On BH-3 that is (2.68 + 0.615) × 9.81 / 1.615 = 20.01 kN/m³. Note what the calculator is doing: the saturated figure sits in the breakdown beneath the dry figure, both from the same two inputs, because they are the same soil described in two states rather than two different soils.

Buoyant unit weight is the one the calculator leaves for you, and it is a subtraction: γ′ = γsat − γw, or 20.01 − 9.81 = 10.20 kN/m³. That is Archimedes applied to a skeleton of grains — below the water table the solids are supported by the water they displace, and what remains to press down on whatever lies beneath is a little over half what the same soil weighs in air. Engineers who have not used it before tend to disbelieve the size of the drop. It is correct, it is why effective stress grows so slowly below a high water table, and it is the difference between a footing check that passes and one that does not.

The four weights of the BH-3 sample, and where each one is used
QuantityValueWhere it belongs
Dry unit weight, γd16.28 kN/m³Compaction control and the input to the void ratio; almost never the weight of soil in the ground
Moist unit weight, γ19.28 kN/m³Retained fill and overburden above the water table, and the surcharge term of a bearing capacity check
Saturated unit weight, γsat20.01 kN/m³Total vertical stress below the water table, before pore pressure is taken back out
Buoyant unit weight, γ′10.20 kN/m³Effective stress below the water table, with water pressure carried as its own separate load
The four weights of the BH-3 sample, and where each one is used

Feed the void ratio you just computed straight back in with the same specific gravity: the dry unit weight it returns should reproduce your starting figure, and the saturated value in the breakdown is the one you subtract 9.81 from to get the buoyant weight.

The soil particles' specific gravity.

The soil's void ratio.

Dry unit weight

103.4 pcf

High confidence
Saturated unit weight
126.85 pcf

Add the equipment this sizes

This result is a specification — 103.4 pcf — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

What this calculation does not cover

  • Dry and saturated are the two end states of the same soil, and the calculator has no water content field, so it never gives the moist (field) unit weight the ground actually has. That is the dry unit weight times (1 + w), and a compaction report's dry density carried straight into an earth pressure, overburden or haul weight check leaves the pore water out of the load.
  • The saturated figure assumes every void is completely filled with water. Ground above the water table and a partially saturated fill weigh less than this, and the buoyant (submerged) unit weight that effective stress work below the water table is built on is not printed — you subtract the unit weight of water from the saturated value yourself.
  • The specific gravity field accepts 2.4 to 2.9 and the void ratio field 0.2 to 3, and a value outside those is replaced with the nearest limit rather than refused. Peat and organic soils sit below the specific gravity floor and above the void ratio ceiling, and iron-rich soils, slag and heavy mine tailings sit above the specific gravity ceiling, so for those materials the answer shown belongs to the substituted value, not to the one you entered.
  • Both inputs describe one specimen at one point. A borehole log gives different phase properties stratum by stratum and a fill varies across its lifts, so this returns a single unit weight rather than the layer-by-layer profile that vertical stress and effective stress calculations are assembled from.
  • This is a phase relationship, not a soil test and not a design value. It does not check that the specific gravity and void ratio came from the same specimen or are physically consistent, applies no factor of safety, and returns a number for any pair typed in; characterising ground for bearing, settlement or earth pressure design stays with a geotechnical engineer working from an actual investigation.

Water Content Is What Makes the Fill Heavier Than the Test

Moist unit weight is the dry unit weight with the pore water added back: γ = γd (1 + w), with w as a decimal. On BH-3 that is 16.28 × 1.184 = 19.28 kN/m³, three kilonewtons per cubic metre more than the dry figure and about eighteen per cent heavier. This is where a great many earth pressure calculations quietly go light. The compaction report on a backfill states a dry density because dry density is what compaction is specified against, and somebody carries that number into the wall check as the weight of the retained soil. Backfill in service is not oven dry and never will be, and the eighteen per cent goes missing from the driving load.

The water content also buys a free consistency check on the sheet itself. Degree of saturation is S = w Gs / e, and 0.184 × 2.68 / 0.615 gives 0.80 — the voids are eighty per cent full, which is ordinary for a firm clay a little above a water table. Two outcomes deserve a reaction. A saturation above 100 per cent is arithmetically impossible and means the density, the water content and the specific gravity did not all come from one specimen. A saturation near 100 per cent well above the reported water table means either the water table record or the sampling is wrong.

Give it the three figures on the sheet — dry unit weight, water content and specific gravity — and the moist weight comes back as the answer, with the void ratio, the saturated and buoyant weights and the degree of saturation beneath it: the four weights of the table above in one pass, and the check that the three figures came from one specimen.

The weight of the solids in a unit volume of soil, from the laboratory's dry density.

The mass of pore water as a percentage of the mass of dry solids.

The density of the soil grains relative to water — about 2.65 to 2.70 for most mineral soils.

Moist (bulk) unit weight

122.7 pcf

High confidence

The moist figure is the weight of the ground as dug, water included — the one retained soil carries above the water table. Below the water table a wall or footing check takes the buoyant figure and carries the water separately at full pressure.

Void ratio (e)
0.61
Porosity (n)
38.08 %
Degree of saturation (S)
80.19 %
Air voids
7.54 %
Dry unit weight
103.64 pcf
Saturated unit weight
127.42 pcf
Buoyant (submerged) unit weight
64.97 pcf

Add the equipment this sizes

This result is a specification — 122.7 pcf — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

What this calculation does not cover

  • The unit weight of water is fixed at 9.81 kN/m³ (62.4 pcf), which is fresh groundwater. A pore fluid that is brine, a tailings liquor or a contaminated leachate is heavier, and the saturated and buoyant figures need working with its own value.
  • Phase relations describe one specimen. The dry density, the water content and the specific gravity have to come from the same sample; mixed across samples they can produce a saturation over 100 per cent, which this page reports as impossible rather than rounding it away.
  • The saturated and buoyant weights assume the voids are completely full below the water table. A zone of partial saturation just above it, or gas in an organic clay, sits between the moist and saturated figures.
  • It converts what the laboratory measured; it does not measure the ground. A density from a disturbed or remoulded sample describes the sample, and fill placed and compacted on site has its own figures, set by the compaction specification rather than by the natural ground beside it.

Which Weight Belongs on Which Line of the Wall Check

The rule is short. Above the water table, the soil thrust is built on the moist unit weight. Below it, the soil thrust is built on the buoyant unit weight and the water is carried as a separate hydrostatic load acting at full pressure on the back of the wall. Water has no shear strength, so no earth pressure coefficient applies to it — that is the entire reason it is handled on its own line rather than folded into the soil weight.

Both ways of getting that wrong are common and they fail in opposite directions. Take three metres of saturated soil with a coefficient of active earth pressure of 0.33. Done properly the soil contributes 0.33 × 10.20 × 3 = 10.1 kPa at that depth and the water contributes 9.81 × 3 = 29.4 kPa, for 39.5 kPa in total. Put the saturated weight into the soil line and keep the water line as well, and the soil term nearly doubles to 19.8 kPa for a total of 49.2 kPa — the water has been counted twice, once at full pressure and once at a third of it, and the wall is over-designed by a quarter. Use the moist weight throughout and forget the water line altogether, which is the more frequent mistake, and the answer is 19.1 kPa: less than half of the real load, from a sheet that contained everything needed to get it right.

The same discipline reaches the rest of the design. A bearing capacity check takes its surcharge term from the weight of soil above founding level — moist above the water table, buoyant below — and its self-weight term from the soil beneath the footing on the same basis. A blow count correction wants the effective overburden stress at the test depth, which accumulates moist weights down to the water table and buoyant weights below it; a consolidation calculation wants the initial void ratio and the effective stress at mid-layer. Four numbers, computed once, feeding half a dozen calculations.

The rule above as arithmetic: moist weight down to the water table, buoyant weight times the coefficient below it, and the water on its own line at full pressure. Enter the 0.33 used here as the coefficient, or let it derive the at-rest value from the friction angle for a wall propped at its head, and the breakdown gives the soil and water pressures at the base beside the thrust.

The height of soil against the wall, from the base slab to the ground surface behind it.

At rest for a wall held by the floor at its head; an entered value for anything else the designer has set.

The drained friction angle of the retained soil, from the ground investigation.

1 for normally consolidated soil and placed fill; higher for ground that was once under more load.

The weight of the retained soil as it is in service, water in the pores included.

The weight of the soil with its voids full, used below the water table.

How far below the retained surface the design water level sits; the full height or more means no water on the wall.

A load spread over the ground behind the wall — a drive, stored material, a building's floor.

Total thrust on the wall per unit run

3,450 lbf/ft

Medium confidence

At rest: the soil stays where it was placed, which is the state of a wall propped by the floor at its head. A wall genuinely free to lean away could use the lower active coefficient, but only if it can move enough to earn it. Below the water table the soil contributes only its buoyant weight times the coefficient, and the water acts on top of it at full hydrostatic pressure.

At-rest coefficient K0
0.5
Soil pressure at the base
464.55 psf
Water pressure at the base
312.25 psf
Total pressure at the base
776.8 psf
Soil thrust per unit run
2,673.27 lbf/ft
Water thrust per unit run
780.62 lbf/ft
Height of the resultant above the base
3.13 ft

Add the equipment this sizes

This result is a specification — 3,450 lbf/ft — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

10 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • Characteristic, unfactored pressures for a screening check. A design applies the partial or load factors of the code in force, and the structural engineer sets the design water level and the coefficient the wall is designed to.
  • Horizontal ground behind the wall. A slope rising away from the wall increases the at-rest coefficient — Eurocode 7 multiplies it by (1 + sin β) — and is not modelled here.
  • Compacting backfill in layers against a propped wall can lock in pressures above the at-rest figure near the top of the wall. AASHTO LRFD 3.11 and CIRIA C760 set out methods for it; this page does not add them.
  • The water is static and the soil's cohesion is ignored. Seepage towards a drained wall changes the pore pressures, and a line load or strip footing close to the wall adds pressure that a uniform surcharge does not represent.

Dense Compared With What

A void ratio on its own says nothing about whether a granular soil is loose or dense. The figure 0.615 is a tight packing for a well-graded sandy gravel and a slack one for a uniform fine sand, because the two soils have entirely different room to arrange themselves. Compactness is therefore always relative, and relative density is that comparison made explicit: where does this soil sit between its own loosest and densest achievable states. The two end points are laboratory results in their own right — the vibratory table maximum index density of ASTM D4253 and the loosest-state minimum index density of ASTM D4254 — and the terminology sits in ASTM D653.

Take the granular backfill going in behind the same wall. Its specific gravity is 2.66, and a nuclear gauge reading gives a field dry density of 1.723 Mg/m³, which is 16.90 kN/m³ and therefore a field void ratio of 0.544. The laboratory index tests on the same material returned emax of 0.82 and emin of 0.44. Relative density is the field value's position in that interval, (0.82 − 0.544) / (0.82 − 0.44), or 72.6 per cent — dense, and comfortably so. Run instead through the density form of the same expression, which is what you use when the sheet quotes index densities rather than index void ratios, and it returns the same 72.6 per cent — the two are one expression with the void ratios substituted out, so daylight between them means a density was rounded on the way in rather than on the way out.

Two cautions ride with it. The first is that emax, emin and the field void ratio have to describe the same soil: index limits run on one sample with a specific gravity borrowed from another produce a confident percentage meaning nothing, and a backfill whose grading drifted between test and delivery is not the material the limits were measured on. The second is that the descriptive bands have hard edges. With these limits, a field void ratio of 0.68 returns 36.8 per cent and reads as medium dense, while 0.69 returns 34.2 per cent and reads as loose. One hundredth changes the word in the report and nothing about the sand. Quote the percentage.

The two index void ratios have to come from the same laboratory on the same material as the field value, or the percentage is a comparison with somebody else's sand — and read the number rather than the classification word, because the band edges fall between adjacent hundredths.

The void ratio in the loosest possible state, from ASTM D4254 testing.

The void ratio in the densest possible state, from ASTM D4253 testing.

The soil's actual void ratio in the field.

Relative density

62.5 %

High confidence

Classification: Medium dense.

Field void ratio
0.6
Range between emin and emax
0.4

What this calculation does not cover

  • This is a packing index, not a strength or a design value. It returns no bearing capacity, settlement, friction angle or liquefaction resistance — relative density is an input to those analyses, not a substitute for any of them.
  • It is not a compaction acceptance test. Percent compaction against a Proctor maximum (ASTM D698 or D1557) is measured from a different reference state, there is no general conversion between the two scales, and a fill can pass one specification clause while failing the other.
  • The consistency check only confirms the field value sits between emin and emax. It cannot see index limits run on a different sample, a specific gravity borrowed from another test, or a grading that drifted between the laboratory sample and the material actually placed, and it describes one void ratio at one location and depth rather than the fill as built.
  • emax and emin are not material constants. They move with mould size, vibration amplitude and duration, moisture condition and operator, and repeat testing between laboratories scatters them; none of that scatter is carried into the percentage, and the classification bands have hard edges that a hundredth of a void ratio can cross.
  • The index tests behind emax and emin are written for free-draining cohesionless soils with only a small fines fraction — roughly 15 percent passing the No. 200 sieve in ASTM D4253 and D4254. Silts, clays, organic soils and sands with substantial fines fall outside those methods; the arithmetic still returns a percentage for their numbers and it is not a relative density.

Percent Compaction and Relative Density Answer Different Questions

Percent compaction measures a field dry density against a laboratory maximum obtained by impact compaction at an optimum water content, under ASTM D698 or ASTM D1557. Relative density measures a field void ratio against the loosest and densest states obtainable by the index methods. Those are different reference states produced by different energies, and there is no general conversion between them — a percentage on one scale cannot be translated to the other for an arbitrary soil. For clean, free-draining granular materials the impact compaction curve is often poorly defined in the first place, with no clear peak to call a maximum, and that is precisely the situation the index density tests were written for.

The backfill above makes the point concretely. Its standard effort maximum dry density is 1.815 Mg/m³, so the field value of 1.723 Mg/m³ is 94.9 per cent compaction — a fail against a 95 per cent specification, by a tenth of a per cent, on a soil the relative density test calls dense at 72.6 per cent. Neither is wrong; they are two rulers with different zero points laid against the same sand. The argument on site comes from a specification naming both with limits chosen independently, so a load can pass one clause and fail the other. Decide which governs before the compaction plant arrives, and let the other be information.

Two ways of saying a granular fill is compact enough
MeasureCompared againstSuits
Percent compactionA laboratory maximum dry density from impact compaction at optimum water content (ASTM D698 or D1557)Soils with a well-defined moisture-density curve; the familiar measure for mixed and cohesive fills
Relative densityThe soil's own maximum and minimum index void ratios (ASTM D4253 and D4254)Clean cohesionless sands and gravels, where the impact curve is flat and a peak is hard to identify
Two ways of saying a granular fill is compact enough

Where the Fields Stop, and What That Is Telling You

Every field on the calculators here carries a range, and the field states it. Those are not decoration. A value typed outside them is clamped to the nearest end and the field says out loud what it did and what you entered, which is the right behaviour — the alternative is an answer that looks the same as any other answer and was computed from a number you did not supply. If a clamp notice appears, read it rather than working around it.

The edges of those ranges are informative. Soft organic clays and peats sit outside them twice over: their dry unit weight can fall below the field's floor, and their specific gravity below its floor too, organic matter being far lighter than mineral grain, which is what ASTM D2974 exists to quantify. The phase relationships stay valid at any void ratio — they are definitions, not correlations — so run those soils by hand and note on the sheet that the calculators were outside their stated range.

What the Sheet Does Not Say

A specific gravity is frequently run once, on a composite made from several samples, and then applied to every density in the report. That is defensible where the deposit is uniform and quietly wrong where it is not — a made-ground fill with pockets of brick rubble, ash and clay has no single particle density, and the void ratios computed for it inherit whichever sample dominated the composite. The report will not tell you this unless you ask which specimens the pycnometer test was run on, and that question is usually answered by return of email.

Then there is what happened to the sample between the ground and the mould. A thin-walled tube specimen taken under ASTM D1587 can swell, drain or lose its structure in transit, and the dry density that comes off it belongs to the tube rather than to the ground. In-place methods avoid that — the sand cone of ASTM D1556 and the nuclear gauge of ASTM D6938 measure the fill where it lies — but they measure only the top of a lift and they measure it where the technician chose to stand. Neither limitation is a reason to distrust the number; both are reasons to know how many tests produced it and how far apart they were.

Finally, the water table on the report is a reading with a date on it rather than a property of the site. A standpipe dipped at the end of a dry summer describes a different wall from the same standpipe in late winter, and perched water over a clay layer or a river-linked groundwater regime moves it further still. Where the design is sensitive — and a wall retaining three metres below the water table is very sensitive — the honest input is the highest credible level with a justification attached, which is how EN 1997-2 frames the water regime: something established, not assumed.

The Line You Write Down

What comes out of an hour of this is four unit weights, a void ratio, a relative density where the soil is granular, and — the part that gets skipped — a note of where each one came from. Write the converted figure next to the original so the multiplication can be checked without opening the laboratory report again. Name the test and the sample against each derived value. State the water table depth and the date it was dipped beside the buoyant weight, because that weight is only meaningful with the level attached.

The reason is not tidiness. These four numbers will be read by a structural engineer sizing the wall, by whoever runs the bearing check on the footing, by the person correcting blow counts for overburden, and eventually by somebody investigating a movement three years after handover. All four will assume the values were derived rather than measured, and only one of them will be in a position to ask what they were derived from. The sheet you write is the answer to that question.

  1. Convert every reported density to kN/m³ before touching anything else, and keep the original figure and its units written alongside.
  2. Establish which specimens the specific gravity was run on, and whether a gravel fraction was tested separately and combined.
  3. Compute the void ratio from specific gravity and dry unit weight, and read the porosity beside it as a plausibility check against the soil description.
  4. Put that void ratio back through the unit weight relation and confirm it returns the dry unit weight you began with.
  5. Apply the water content to get the moist unit weight, then compute the degree of saturation and reconcile it with the reported water table.
  6. Subtract the unit weight of water from the saturated value for the buoyant weight, and use it below the water table only, with hydrostatic pressure carried on its own line.
  7. For granular fill, compute relative density from index void ratios measured on that same material, and record the percentage rather than the descriptive band.
  8. Write each figure down with the test standard, the sample reference and the date it came from, on the same page as the calculation that consumes it.

What has to be on the sheet before the conversion is worth doing

Six items, each of which changes an answer rather than decorating it. Missing any one of them turns a derived unit weight into an assumption with a decimal point on it.

  • Specific gravity, and what it was run on — The pycnometer test covers material passing the 4.75 mm sieve; a gravelly fill needs the coarse fraction tested separately and the two combined by mass.
  • Dry density, converted and kept beside its original — Mg/m³ multiplied by 9.81, or lbf/ft³ multiplied by 0.1571. Leave both figures on the page so the multiplication can be checked later.
  • Water content from the same specimen — Without it you hold the weight of an oven-dried sample rather than of the ground, and the moist unit weight the design needs cannot be formed at all.
  • Water table depth with the date it was read — The buoyant weight applies only below the level, and the level is a season and a rainfall record rather than a soil property.
  • Index void ratios for anything granular — Maximum and minimum from the same laboratory on the same material, or the relative density is a comparison against a different sand.
  • The classification symbol — It decides whether compactness is described by relative density at all, or whether this is a cohesive soil needing a consistency measure instead.
Open this as a workspace →

Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.

Drawn from

  • ASTM D854 Standard Test Methods for Specific Gravity of Soil Solids by Water Pycnometer
  • ASTM D7263 Standard Test Methods for Laboratory Determination of Density (Unit Weight) of Soil Specimens
  • ASTM D2216 Standard Test Methods for Laboratory Determination of Water (Moisture) Content of Soil and Rock by Mass
  • ASTM D4253 Standard Test Methods for Maximum Index Density and Unit Weight of Soils Using a Vibratory Table
  • ASTM D4254 Standard Test Methods for Minimum Index Density and Unit Weight of Soils and Calculation of Relative Density
  • ASTM D698 Standard Test Methods for Laboratory Compaction Characteristics of Soil Using Standard Effort
  • ASTM D1557 Standard Test Methods for Laboratory Compaction Characteristics of Soil Using Modified Effort
  • ASTM D1556/D1556M Standard Test Method for Density and Unit Weight of Soil in Place by Sand-Cone Method
  • ASTM D6938 Standard Test Methods for In-Place Density and Water Content of Soil and Soil-Aggregate by Nuclear Methods (Shallow Depth)
  • ASTM D1587/D1587M Standard Practice for Thin-Walled Tube Sampling of Fine-Grained Soils for Geotechnical Purposes
  • ASTM C127 Standard Test Method for Relative Density (Specific Gravity) and Absorption of Coarse Aggregate
  • ASTM D2974 Standard Test Methods for Determining the Water (Moisture) Content, Ash Content, and Organic Material of Peat and Other Organic Materials
  • ASTM D2487 Standard Practice for Classification of Soils for Engineering Purposes (Unified Soil Classification System)
  • ASTM D6913/D6913M Standard Test Methods for Particle-Size Distribution (Gradation) of Soils Using Sieve Analysis
  • ASTM D4318 Standard Test Methods for Liquid Limit, Plastic Limit, and Plasticity Index of Soils
  • ASTM D653 Standard Terminology Relating to Soil, Rock, and Contained Fluids
  • AASHTO T 100 Standard Method of Test for Specific Gravity of Soils
  • BS EN ISO 17892-2 Geotechnical investigation and testing — Laboratory testing of soil — Part 2: Determination of bulk density
  • BS EN ISO 17892-3 Geotechnical investigation and testing — Laboratory testing of soil — Part 3: Determination of particle density
  • BS 1377 Methods of test for soils for civil engineering purposes (classification tests)
  • AS 1289 Methods of testing soils for engineering purposes
  • EN 1997-1 Eurocode 7: Geotechnical design — Part 1: General rules
  • EN 1997-2 Eurocode 7: Geotechnical design — Part 2: Ground investigation and testing

Guidance, not a specification. Local codes, the engineer of record and the product manufacturer’s instructions govern where they differ from anything written here.