Plumbing

Running the Discharge Pipe From an Unvented Cylinder: D1, the Tundish and the Elbow Count That Sizes D2

The discharge is two pipes with two different rules and a safety device between them, and the bend count on the second one is what sizes it.
  • 20 minReading time
  • 10Sections
  • 4Calculators inline
  • Last reviewed

The cylinder is on the landing and the pipe has nowhere to go

Mid-terrace, airing cupboard on the first floor half-landing, cylinder delivered at eight and the old vented one already cut out. The hot and cold connections are twenty minutes of work. The problem standing in the way of a working installation by teatime is that the only external wall within reach of that cupboard is the front elevation, above a public footway, and nothing may terminate there. The route to the back of the house is fourteen metres and passes a purlin, two joist runs and a soil stack.

That is the part of an unvented job that gets designed on the day, and it is the part that has a table behind it. Everything else about the installation is forgiving — a hot main can be 22 mm or 28 mm and both will work, a cylinder can sit a metre either side of where it was drawn. The safety discharge is not forgiving, because the rules governing it are dimensional and prescriptive: this size, this fall, this many metres, minus this much for every bend. You either satisfied the table or you did not, and it is the first thing a Building Control officer or a scheme assessor puts a tape on.

It is also two pipes rather than one, with a safety fitting between them, and each half is sized by a different rule. Calling the whole run "the discharge" is how the mistake starts. The short leg above the tundish is D1 and it is sized off the valve. The long leg below it is D2 and it is sized off the route.

Read the badge, not the carton

Before anything is cut, the cylinder's data badge decides four of the five components below it. Write down the nominal capacity in litres, the maximum working pressure, the outlet thread size stamped on the temperature and pressure relief valve, and the total heat input the cylinder is rated for. The last one has to be a sum, not a reading: an indirect coil at 15 kW plus a 3 kW immersion is 18 kW, and if a solar coil or a heat pump connection is present it joins the total too.

An unvented cylinder carries three levels of protection and only the last of them discharges. The control thermostat holds the store at its set point in normal service. Behind it sits a non-self-resetting energy cut-out, which kills the heat source and stays killed until somebody presses it — a fault indicator as much as a safety device. Behind that sits the temperature and pressure relief valve, stamped to lift before the store reaches 100 °C, typically at 90 or 95 °C, and to lift on pressure at the cylinder's design figure. On most domestic cylinders a second device discharges into the same tundish: the expansion relief valve in the inlet control set, set below the cylinder's pressure rating and there to release the volume increase of every heating cycle when the expansion provision cannot.

The relief valve is rated by discharge capacity, not by thread size, and the two are not interchangeable facts. In the UK that rating appears in kilowatts, under BS EN 1490 for combined temperature and pressure relief valves; in North America the equivalent valve is stamped in BTU per hour under ANSI Z21.22. Either way the rule is the same and it is broken constantly on retrofits: the valve's rated capacity must equal or exceed the total heat input to the vessel. Add a second immersion heater or a solar coil to a cylinder five years after it was commissioned and the factory-fitted valve may no longer cover the input, which invalidates the whole safety case without touching a single pipe.

Where the cylinder itself is still being chosen, size it on the household and the peak hour rather than on the pallet that fits the cupboard — that argument belongs to the two hot water guides linked below and is not repeated here. What matters for this job is that the capacity figure feeds the expansion provision, and the expansion provision is what keeps the discharge pipe dry for the next fifteen years.

The five components of a safety discharge

A safety discharge arrangement in the order water passes through it: the relief valve on the cylinder, a short metal leg down to a tundish that breaks the run with a visible air gap, then a longer pipe falling continuously to an open termination over a trapped gully.
  1. Temperature and pressure relief valve — factory-fitted to the cylinder boss, rated in kilowatts or BTU per hour, and that rating has to cover every heat source feeding the vessel
  2. Discharge pipe D1 — metal, full bore, never smaller than the valve outlet, and it carries no valve, isolator or restriction of any kind
  3. Tundish — the visible air gap that separates the safety device from everything downstream, sized to the valve and mounted vertically below it Backflow Preventer Relief Valve Discharge Calculator
  4. Discharge pipe D2 — one size larger than D1 at least, 300 mm straight below the tundish before any bend, then a continuous fall the whole way out Pipe Fitting Equivalent Length Calculator
  5. Termination and receiving point — an open end somebody can see, discharging where near-boiling water cannot reach a person, a plastic gutter or a doorway

Only useful at the point where the cylinder has not been ordered yet: it gives a household bracket in gallons and knows nothing about store temperature or peak hour. Take the bracket, convert it, then let the delivered cylinder's badge overrule it — every dimension below this section keys off the badge, never off the estimate.

How many people regularly use hot water in the home.

Recommended tank size

57.5 gallons (recommended)

Medium confidence

This is a rough rule-of-thumb range. Homes with multiple bathrooms used simultaneously, soaking tubs, or high-flow fixtures should size toward the higher end or consider a tankless system sized by flow rate instead.

Recommended range, low
50 gal
Recommended range, high
65 gal

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

What this calculation does not cover

  • Sizes stored volume only — the heat source is not in the model. A gas, electric-resistance and heat-pump tank of the same nominal size recover at very different rates, and an electric or heat-pump cylinder usually needs more volume than these ranges give to cover the same back-to-back demand.
  • Headcount stands in for peak-hour demand rather than measuring it. No fixture count, bathroom count, simultaneous-use scenario, shower flow rate or duration, and no bath or soaking tub enters the calculation, so two houses with the same number of occupants and completely different fixtures get the same answer.
  • No water temperatures are entered. Incoming mains temperature falls in winter, storage set point and thermostatic blending change how much usable hot water a given tank delivers, and stratification breaks down before a tank is nominally empty — this is nameplate volume, not what you will draw at temperature.
  • The bands stop at five occupants and describe a conventional storage heater. A household of ten returns the same range as a household of five, and heat-pump cylinders, solar-preheated stores and instantaneous units are sized on different grounds entirely.
  • This is not an installation or compliance check. Tank size says nothing about the relief and expansion arrangements a stored hot-water system requires, scald protection at outlets, legionella control in storage and distribution, or whether the gas, flue or electrical supply can serve the appliance — those come from the code in force where the work is done and from the installer competence that code demands.

D1 is short, metal, and contains nothing

The leg from the safety device to the tundish is the simplest pipe on the job and it is where the shortcuts happen. It must be metal — this is water that can arrive at close to boiling and flash to steam the moment it meets atmosphere, and a push-fit plastic connector on the valve outlet is a failure waiting for the one day it is asked to work. It must be at least the nominal outlet size of the safety device, so a G½ valve gets 15 mm and a G¾ valve gets 22 mm, and it must run at a continuous fall with no dips a slug of water could sit in.

The tundish goes vertically below the valve and within a few hundred millimetres of it. The exact maximum is dimensioned on Diagram 2 of Approved Document G and repeated, sometimes tighter, in the cylinder manufacturer's own instructions — take it from whichever of those your work is signed off against, because a tundish mounted at the far side of the cupboard on the end of a metre of pipe is a straightforward fail and an easy one to spot from the doorway. It also has to be in the same space as the cylinder and where somebody standing at the cupboard can see it, which rules out the neat solution of hiding it in the floor void.

Then the rule that has no exceptions anywhere in the chain: there is no valve, no isolator, no restrictor, no flexible hose and no strainer between the safety device and the point of discharge. Not in D1, not in D2, not at the termination. A service valve fitted "so it can be isolated for maintenance" converts a safety device into a decoration, and it is the single defect most likely to appear on a system somebody else worked on last.

What the tundish has to swallow without spitting it back

A tundish is an air break with a viewing slot, and it does two jobs at once. It severs the safety discharge from anything downstream, so a blocked D2 can never pressurise the valve outlet, and it makes a discharge visible to a householder who would otherwise never know one had happened. Both jobs fail in the same way: if the discharge arriving from above exceeds what the tundish outlet and D2 can carry away, the tundish backs up and puts near-boiling water on the cupboard floor.

In practice this is rarely the binding constraint, and it is worth knowing that with a number rather than a shrug. Take a 22 mm tundish outlet with a bore around 20 mm — an area of roughly 314 mm² — and the shallow head of water that can stand in the bowl before it spills, call it 50 mm. The orifice equation puts about 0.19 litres a second through it, better than 11 litres a minute. The steady discharge from a runaway heat source, worked out in a later section, is between half a litre and three litres a minute. The tundish has an order of magnitude in hand, and what actually constrains the arrangement is D2's resistance and where the pipe is allowed to end.

The sizing check that does matter here is matching: a tundish is sold sized for a valve, and a 15 mm × 22 mm tundish fitted under a G¾ valve is undersized at its inlet regardless of what the bowl can pass. Buy the tundish against the valve stamp.

Read this one's badge before you trust it: it is written for the relief valve on a reduced-pressure backflow preventer, and what carries across is the arithmetic underneath — orifice area, a discharge coefficient and a head. Use it on the receiving side, where the head is the few centimetres standing in a tundish or a hopper: a 20 mm bore is 314 mm², the coefficient stays at 0.6, and 50 mm of standing water is entered as 0.05 m. Three things it will not do: its head field stops short of the head a 7 bar valve seat represents, so it cannot be fed the supply side; it models cold liquid, not the two-phase flashing discharge a temperature relief valve actually produces; and it is no substitute for the capacity stamped on the valve body.

The open cross-sectional area of the relief valve's discharge orifice.

An empirical factor accounting for orifice flow contraction and friction losses.

The pressure head driving flow through the relief valve orifice, expressed as a water column height.

Relief valve discharge flow

36.8 gal/min

Medium confidence

Confirm the actual relief valve orifice area and discharge coefficient from the specific backflow preventer manufacturer's data — this is a general orifice-flow estimate, not a substitute for the manufacturer's rated relief capacity.

Discharge velocity
913.37 ft/min

Add the equipment this sizes

This result is a specification — 36.8 gal/min — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

What this calculation does not cover

  • Takes the head as given and does not derive it. During a genuine relief event the driving head is the supply-side pressure at that instant, not a static column — a 70 psi (483 kPa) main is about 50 m (164 ft) of water, not the 3 m (10 ft) the field opens on — and because flow goes with the square root of head, an assumed head that low understates the discharge by roughly a factor of four.
  • Says nothing about how the discharge is piped. Relief from a reduced-pressure assembly must reach the drain through an air gap and never a direct connection — hard-piping it into the waste system rebuilds the exact cross-connection the assembly was installed to prevent, and it also means a relief event pushes into the drain instead of showing itself on the floor where someone notices it.

D2 is sized on resistance, and the bends are the resistance

The second leg is where the design work is, and the rule behind it is not a friction calculation. Approved Document G publishes a table of permitted resistance, expressed as a maximum length of straight copper pipe for each combination of valve size and pipe size, with a fixed allowance in metres to be subtracted for every elbow or bend. It is prescriptive arithmetic: measure the run, count the bends, subtract, compare. There is no velocity, no roughness coefficient and no flow rate anywhere in it.

Start with the two dimensional constraints that come before the table. D2 must be at least one pipe size larger than D1, and it must drop at least 300 mm vertically straight out of the tundish before the first elbow — that vertical section is what lets a flashing discharge separate and get moving rather than hitting a bend at the tundish outlet. After that the pipe falls continuously, at a minimum of 1 in 200, all the way to the termination. A continuous fall over fourteen metres of joist void is a real coordination problem, not a note on a drawing, and it is the reason the route has to be walked before the cylinder is unwrapped.

Then the table. Work the canonical case: a G½ relief valve, a measured run of 7 m from tundish to termination, and four elbows on the route. Twenty-two millimetre copper is allowed 9 m of resistance and each 22 mm bend costs 0.8 m, so four bends take 3.2 m off and leave 5.8 m of allowance against an actual 7 m run. Twenty-two millimetre fails. Step up: 28 mm copper is allowed 18 m and its bends cost 1.0 m each, so four take 4 m off and leave 14 m against 7 m of run. Twenty-eight millimetre passes comfortably, and that is the answer.

Notice what that example does to intuition. The pipe went up a size not because it was long — 7 m against an 18 m allowance is nothing — but because four bends on a 22 mm run consumed more than a third of the smaller pipe's entire budget. On a real retrofit route the count is rarely four. Around a purlin, down past a stack, along a joist run and out through a wall is eight or ten changes of direction, and at 0.8 m each that is the whole 22 mm allowance gone before a single metre of pipe is counted. Long-sweep bends are the fix worth having: pulling a bend in the copper instead of soldering an elbow keeps the fitting count down, and on a tight route it is the difference between 28 mm and 35 mm.

Two boundaries on that table are worth stating plainly, because both get crossed. It is a copper table — the resistance figures belong to copper and to nothing else, so a D2 in any other material cannot be sized from it and has to be sized on the manufacturer's own data for a pipe demonstrated fit for the discharge temperature. And where one common discharge pipe serves several dwellings, as it does on a stack of flats, the number of systems on it is capped so a discharge can still be traced to its cylinder, and the common pipe steps up a size above the largest D2 joining it. Both of those are in Approved Document G, and both are cheaper to read than to rebuild.

Permitted resistance for a copper discharge pipe D2, from Approved Document G Table 1. The allowance is a maximum length of straight pipe; every elbow or bend on the route is subtracted from it at the rate in the last column.
Valve outletMinimum D1D2 sizeStraight-pipe allowanceDeduct per bend
G½15 mm22 mm9 m0.8 m
G½15 mm28 mm18 m1.0 m
G½15 mm35 mm27 m1.4 m
G¾22 mm28 mm9 m1.0 m
G¾22 mm35 mm18 m1.4 m
G¾22 mm42 mm27 m1.7 m
G128 mm35 mm9 m1.4 m
G128 mm42 mm18 m1.7 m
G128 mm54 mm27 m2.3 m
Permitted resistance for a copper discharge pipe D2, from Approved Document G Table 1. The allowance is a maximum length of straight pipe; every elbow or bend on the route is subtracted from it at the rate in the last column.

Put the walked bend count in against the per-bend figure from the table row you are working — 0.8 m for 22 mm off a G½ valve, 1.0 m for 28 mm, and so on. The total it returns is what comes off the straight-pipe allowance before you compare it with the tape. Set the tee count to zero: a discharge pipe has no branches in it, and if yours does, that is the finding rather than the arithmetic.

The total count of 90° elbow fittings in the piping run.

The straight-pipe length that produces the same friction loss as one elbow.

The total count of tee fittings where flow branches off the run.

The straight-pipe length that produces the same friction loss as one branch-flow tee.

Total fitting equivalent length

12 ft

High confidence
1.5 ft
Schematic, drawn to the proportions you entered — not to scale on screen.

What this calculation does not cover

  • Totals fittings, not the components that usually dominate the head. A coil, heat exchanger, strainer, balancing valve or control valve is published as a pressure drop at a stated flow - feet of head or kPa, not an equivalent length - and on a typical hydronic circuit those together exceed the whole pipe-and-fitting figure. A pump chosen from this total plus the straight pipe alone lands short, and the shortfall turns up as the branch that will not balance.
  • One path, not a system. Pump head is set by the INDEX circuit, the single worst route from the pump out to the furthest or most restrictive terminal and back, so the fittings that belong in this box are the ones along that path only. Adding up every elbow in the building inflates the total enormously and buys a pump that overpumps every other branch; the parallel branches get balanced down to the index circuit, they do not add to it.

Where the pipe is allowed to end

"Safe" and "visible" are both requirements and they pull against each other, which is why the termination is negotiated with the householder rather than chosen by the plumber alone. Safe means water at close to 100 °C, possibly for hours, cannot reach a person, a pet or anything it will destroy. Visible means somebody will notice it running — a discharge nobody sees is a fault that continues until the cylinder is condemned or the water bill arrives.

The terminations Approved Document G describes come down to four patterns. Into a trapped gully, with the pipe end below the fixed grating and above the water seal, which is the tidiest answer where a gully exists near the right elevation. Downward at low level, within 100 mm of the ground over a hard standing or a grassed area, with a wire guard preventing contact but not obscuring the view of it — the standard answer for a rear elevation. Upward or sideways at high level into a metal hopper and metal downpipe, with the pipe end clearly visible where it enters. Or onto a roof able to take a high-temperature discharge, kept well clear of any plastic gutter that would collect it, with a stated separation of 3 m.

The material rule follows the water rather than the pipe. Anything the discharge lands in or passes through has to survive it: a plastic hopper, a uPVC downpipe or a plastic gutter under a discharge point is a soft, slow failure that nobody attributes to the cylinder until the section deforms. That is also why a pipe terminating over a gully must not simply be pushed into a plastic soil branch — the connection has to be an air break at an open fitting, not a joint into the drainage system.

Then the constraints the drawing never shows. A discharge over a footway, a doorstep, a fire escape, a car parking bay or a bin store is not a safe place regardless of how the table works out. An external run on a north elevation freezes, and a frozen D2 is a blocked D2 — the mitigation is to keep the exposed length short and the fall generous rather than to lag it, because insulating a discharge pipe hides the thing that has to be seen. And where no lawful termination exists at all, the fallback is a proprietary discharge collection vessel accepted by the cylinder manufacturer, which is a component with its own capacity limit and its own commissioning record, not a bucket.

The same hazard under the IPC, answered a different way

A plumber crossing between the British and North American versions of this job finds the physics identical and the arrangement barely recognisable. There is no tundish. There is no equivalent-length table. The relief valve discharge under the International Plumbing Code at Section 504.6, and the International Residential Code at Section P2804.6.1, runs full-size from the valve outlet by gravity to a floor, an indirect waste receptor or the outdoors, and the air gap is made at the receiving end rather than partway along the pipe.

The list of requirements there is short and worth knowing verbatim if you work both sides: the pipe is not smaller than the valve outlet, serves one relief device only, is not trapped, has no valves or tee fittings in it, flows by gravity, is readily observable, is made of material rated for the discharge temperature — 250 °F is the usual figure — and terminates between two pipe diameters and 6 inches above the receptor. The end is left plain, because a threaded end invites somebody to cap it.

The differences are instructive in both directions. The North American arrangement puts the visible air gap at the point of discharge, which is easier to inspect and worse at telling a householder upstairs that anything is happening. The British arrangement puts the break in the airing cupboard next to the cylinder, which is what makes a dripping tundish such a good diagnostic, and pays for it with a long pipe that has to be sized on a table. What neither permits is a discharge connected into the drainage system, and that is the rule to carry across.

How long the pipe runs once it starts

The termination decision hinges on a number nobody usually works out: once a temperature relief valve lifts on a control fault, how long does it discharge, and how fast? A discharge that lasts eleven seconds and a discharge that lasts eleven hours are different hazards, and they justify different answers about the doorstep.

The fault is a heat source that will not stop — a welded thermostat contact, a stuck immersion contactor, a boiler with a failed cylinder call. Two phases follow. First the store climbs from its set point to the valve's lift temperature, which is simple heat capacity: raising a litre of water by one kelvin takes 4.186 kJ, so a 210 litre cylinder going from 60 °C to 95 °C absorbs about 30.8 MJ. A 3 kW immersion element takes nearly three hours to deliver that. A 15 kW indirect coil takes thirty-four minutes. That interval is the fuse, and it is also the window in which the energy cut-out should have acted.

Then the second phase, which is the one that sizes the hazard. With the valve open, the cylinder holds at its lift temperature and everything the heat source delivers leaves as hot water replaced by cold mains. Balance the two — a 3 kW input against an 85 K rise from 10 °C mains — and the steady discharge is about half a litre a minute. Fifteen kilowatts gives about two and a half. Those are trivial flows and they are the whole point: the pipe does not gush, it trickles water at close to boiling, continuously, for as long as the fault lasts. Which is precisely why a low-level termination needs a guard and why a discharge over anything a person stands on is unacceptable no matter how small the flow.

The recovery calculator below runs the same arithmetic for the normal case, and using it here needs one correction stated openly. It applies a 0.75 recovery efficiency drawn from a flued gas storage heater, so it returns a longer time than the physics — a safe direction when you are asking how long a household waits, and the wrong direction entirely when you are asking how quickly a fault reaches a safety valve. For an immersion element, where essentially all the input reaches the water, multiply its answer by 0.75 to get back to the real interval. Its target temperature field also stops at 71 °C, so the 60-to-95 °C runaway band cannot be entered directly; the table below carries that extension.

Time for a stuck heat source to drive a store from 60 °C to its relief valve's lift temperature, and the steady discharge once the valve is open. Water at 4.186 kJ/kg·K, mains at 10 °C, all input assumed to reach the water.
Cylinder and heat sourceEnergy to reach 95 °CTime to liftSteady discharge
150 L, 3 kW immersion22.0 MJ2 h 02 min0.5 L/min
210 L, 3 kW immersion30.8 MJ2 h 51 min0.5 L/min
210 L, 6 kW heat pump into coil30.8 MJ1 h 25 min1.0 L/min
210 L, 15 kW boiler coil30.8 MJ34 min2.5 L/min
300 L, twin 3 kW immersions43.9 MJ2 h 02 min1.0 L/min
Time for a stuck heat source to drive a store from 60 °C to its relief valve's lift temperature, and the steady discharge once the valve is open. Water at 4.186 kJ/kg·K, mains at 10 °C, all input assumed to reach the water.

Enter the delivered cylinder's litres, the winter mains temperature and the real input at the coil or element to get the normal reheat, then read the recovery rate in its breakdown — that rate is the same one driving the runaway, scaled to a different temperature band. Take the 0.75 efficiency back off for an immersion element before you treat any of it as a fault interval.

The rated storage capacity of your water heater, in the unit shown.

The temperature of the cold water feeding the tank.

The thermostat setting on the water heater.

The heater's rated power input, from its data plate, in the unit shown.

How much of the input energy actually ends up in the water.

Recovery time

58.5 minutes

Medium confidence

This estimates recovery from a fully-drained tank using the nameplate input rating — real-world recovery is somewhat slower due to standby losses and burner cycling.

Recovery rate
0.86 gal/min

What this calculation does not cover

  • This is the time to reheat the entire tank contents from your incoming temperature up to the thermostat setting. It is not the time until you have usable hot water again — a tank stratifies, so the top of the cylinder is back up to temperature well before the whole volume is.
  • It assumes nothing is drawn off while the tank recovers. Any continuing draw replaces heated water with cold and pushes the time out; a draw that outruns the recovery rate means the tank never catches up at all.
  • Nameplate input is taken at face value, with no allowance for gas derating at altitude, an electric element running below its rated supply voltage, or scale on the element and fouling on the flue side of an older heater. Most residential dual-element electric heaters energise only one element at a time, so enter one element's rating rather than the sum of both.
  • Recovery efficiency stops at 1.0, so this cannot represent a heat pump water heater, which moves more heat than it draws in electricity and whose output falls as the surrounding air gets colder. For an indirect coil the figure you enter is the heat reaching the coil — a boiler that cannot sustain that output, or a coil undersized for it, recovers more slowly than this predicts.
  • Nothing here checks the target temperature for safety. Stored water temperature is a trade-off between scald risk at the outlet and controlling bacterial growth in the tank, and this calculator will model any setting in its range without comment — set it against the requirements that apply to your installation, and fit a thermostatic mixing valve where outlet temperature has to be limited.

A tundish that is doing something

On a system already in service, water moving through the tundish is a diagnosis waiting to be made, and which valve is passing tells you where to look. A temperature relief valve discharging means a control failure and the cylinder should be isolated the same day. An expansion relief valve discharging means the volume increase of each heating cycle has nowhere to go, and that is the far commoner finding: a waterlogged expansion vessel that has lost its air charge, a bubble-top cylinder whose internal air gap needs re-forming by draining, an inlet pressure reducing valve that has drifted upward, or a standing mains pressure that has risen since commissioning and now sits close to the relief setting.

The check is quick. Read the vessel's schrader valve pressure against the cold system pressure with the system depressurised, put a gauge on the inlet set's reduced pressure, and confirm the relief setting on the badge is genuinely above it with margin. Fix the cause rather than the symptom — a relief valve that has been passing for months has usually picked up enough scale on the seat that it will weep afterwards regardless, and at that point it is a replacement rather than an adjustment. The quantity of water this wastes is not trivial and is covered from the metering side in the water bill guide linked below.

Signing it off and handing it over

Unvented hot water storage above 15 litres is notifiable building work, and the normal route is self-certification by an operative holding the relevant unvented competence and registered with a competent person scheme. The discharge arrangement is the part of that certificate most likely to be looked at, so leave the evidence behind: the route, the size, the bend count and the arithmetic on the commissioning sheet, not in your head.

  1. Take the valve stamp, the cylinder capacity and the total heat input from the badge, adding every heat source rather than the largest one.
  2. Confirm the relief valve's rated capacity covers that total, and record it — this is the check that fails after somebody adds an immersion or a solar coil later.
  3. Walk the D2 route before cutting anything, counting every change of direction and confirming a continuous fall of at least 1 in 200 exists the whole way.
  4. Size D2 from the table: straight-pipe allowance for that valve and pipe size, minus the per-bend deduction times the walked count, against the measured length.
  5. Set the tundish vertically below the safety device within the distance the document and the manufacturer's instructions allow, in the same space as the cylinder and in plain sight.
  6. Drop 300 mm straight below the tundish before the first bend, and keep the whole run free of valves, isolators, strainers and flexible connections.
  7. Terminate where near-boiling water can be seen and cannot reach anybody, with a guard at low level, and confirm nothing plastic sits in the discharge path.
  8. Commission the expansion provision: vessel charge against system pressure, inlet reduced pressure gauged, and the relief settings checked to sit above it with margin.
  9. Operate both relief valves manually against the tundish, watch the discharge run away cleanly, and confirm both reseat dry.
  10. Show the householder the tundish, say plainly that anything running through it is a fault, and leave the discharge sizing on the certificate with the annual service interval.

What has to be written down before the first cut

Seven items, all of them collected in the twenty minutes between the cylinder arriving and the pipe being marked out. Six of the seven come off a badge or a tape; the seventh is a conversation with the householder that is far cheaper before the pipe is run than after.

  • Safety device outlet size, read off the valve body — G½, G¾ or G1. The whole resistance table is indexed on this one character and nothing else on the cylinder changes it.
  • Total heat input, every source added together — Indirect coil plus immersion plus solar plus heat pump. This is the figure the valve's kilowatt rating has to cover, and it is a sum people take as a reading.
  • Measured tundish-to-termination length — Walked with a tape along the route the pipe will actually take, including the drops around obstructions. Not scaled off a plan.
  • Bend count on that route — Every elbow and every pulled bend, counted on the walk. At 0.8 m each on 22 mm it is usually what forces the size up, not the length.
  • Termination point, named and agreed — Gully, low-level guarded outlet, metal hopper or collection vessel — chosen with the householder, and checked against footways, doorways and parking.
  • Standing mains pressure and the inlet set's reduced pressure — Both gauged, both recorded. A main that rises later is the most common reason a discharge pipe starts weeping years after a clean commission.
  • Material of D2 and of everything it discharges into — The published resistance table is a copper table. Anything else is sized on the manufacturer's data, and anything plastic in the discharge path is a finding.
Open this as a workspace →

Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.

Drawn from

  • Approved Document G, Sanitation, hot water safety and water efficiency (England), requirement G3 and its discharge pipe provisions — Diagram 2 for the arrangement and dimensions, Table 1 for the sizing of copper discharge pipe D2
  • The Building Regulations 2010, Schedule 3, competent person self-certification schemes
  • BS EN 12897, Water supply — Specification for indirectly heated unvented (closed) storage water heaters
  • BS EN 1490, Building valves — Combined temperature and pressure relief valves — Tests and requirements
  • BS 8558, Guide to the design, installation, testing and maintenance of services supplying water for domestic use within buildings and their curtilages
  • The Water Supply (Water Fittings) Regulations 1999 (SI 1999/1148), and the equivalent Water Supply (Water Fittings) (Scotland) Byelaws 2014 and Water Supply (Water Fittings) Regulations (Northern Ireland) 2009
  • International Plumbing Code, Section 504.6, Requirements for discharge piping, and International Residential Code, Section P2804.6.1
  • ANSI Z21.22 / CSA 4.4, Relief Valves for Hot Water Supply Systems
  • ASME Boiler and Pressure Vessel Code, Section IV, Rules for Construction of Heating Boilers, for the water heaters it covers
  • HSE Approved Code of Practice L8 and HSG274 Part 2, The control of legionella bacteria in hot and cold water systems
  • The cylinder manufacturer's installation and commissioning instructions for the specific model — the tundish separation, the expansion vessel charge pressure, the relief valve settings and any accepted discharge collection vessel are model-specific figures and are taken from that document rather than from a general rule

Guidance, not a specification. Local codes, the engineer of record and the product manufacturer’s instructions govern where they differ from anything written here.