SettingsSettings for this calculationUS
The peak drainage flow rate from the fixtures connected to the grease interceptor.
Determine total flow rate from the PDI-G101 fixture flow rate tables for each connected fixture (sinks, dishwashers, etc.).
The minimum time wastewater must be retained in the interceptor to allow grease to separate.
PDI-G101 specifies a standard retention time (typically 2 minutes) for hydromechanical grease interceptors.
A multiplier accounting for grease storage capacity needed between service intervals.
Higher-volume or full-service food operations typically use a higher storage factor to extend time between required pump-outs.
Required grease trap capacity
136 gal
Flow rate and storage factor depend on the specific fixtures connected (per PDI-G101 fixture flow rate tables) and food service type — confirm against your local plumbing code's grease interceptor sizing requirements.
They open the calculator with your figures already in it
Grease Trap Sizing Calculator (PDI-G101 Method): 136 gal — shown in imperial, US market. The link sets both, so the result they see is the one on your screen.
Show calculation logicHide calculation logic
How this was calculated
Formula source(s)
- PDI-G101 method: required grease trap capacity = flow rate × retention time × storage factor, the standard plumbing industry method for sizing hydromechanical grease interceptors for commercial kitchen fixtures
Inputs used
- Flow Rate
- 40 gal/min
- Retention Time (minutes, Typically 2 per PDI-G101)
- 2
- Storage Factor (Typically 1.7 for Full-Service Restaurants)
- 1.7
Confidence note: Flow rate and storage factor depend on the specific fixtures connected (per PDI-G101 fixture flow rate tables) and food service type — confirm against your local plumbing code's grease interceptor sizing requirements.
What this calculation does not cover
- A PDI-rated interceptor only performs at its rated flow, and reaching that takes a flow-control fitting this sizing never mentions. The fitting's orifice plus its vent throttles the surge from a pot sink dumping so the water is actually inside the unit for the retention time assumed above; without it the slug blows straight through a correctly sized trap and takes the grease with it. It is the cheapest item in the installation and the one most often omitted.
- What gets connected matters more than the capacity. Dishwasher discharge at 60-80°C re-emulsifies grease so it passes through as a solution and re-solidifies in the sewer downstream, which is why many jurisdictions bar a dishwasher from a small point-of-use interceptor or divert it to a large in-ground one; a food waste disposer fills the same unit with solids that eat the grease storage this factor was meant to buy. Sanitary drainage must never be connected at all.
- The storage factor extends the service interval only until the rule catches up with it. Most authorities require pumping once grease and settled solids reach a quarter of the wetted volume, and many set a maximum interval regardless of size — 90 days is common — so a generously sized unit does not buy an open-ended run between visits, and the manifest for those visits is usually what an inspector asks for first.
- The answer is a liquid volume, which is not how a point-of-use unit is bought. Hydromechanical interceptors are certified as a flow rating with a paired grease capacity in pounds and sold in fixed steps, so this figure has to land on a catalogue model rather than a tank size. A gravity interceptor buried outside is the one specified as a volume, and most codes size that one by a different method again.
Estimated cost — your price
This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.
Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.
Sources checked 2026-09-06 · in the site-wide review of 2026-09-06 · v1.1.1
Regulatory standards & verification citations1
- PDI-G101 method: required grease trap capacity = flow rate × retention time × storage factor, the standard plumbing industry method for sizing hydromechanical grease interceptors for commercial kitchen fixtures