Eighteen hundred square metres, and not one of them is a person
The plate usually arrives as a landlord's lease drawing: an area in the title block, a core hatched in roughly the right place, two stairs the shell-and-core architect drew four years ago, and a demise line that has moved twice since. The first question anyone asks it is how many desks fit. The second, asked weeks later and usually by somebody else, is whether those two stairs are enough. Both are answered from the same rectangle by completely different arithmetic, and it is the second one that decides whether the floor can be let at the density the first one assumed.
Order matters because the two answers harden at wildly different speeds. A desk layout is a Tuesday afternoon. An exit is a hole through every slab in the building, a shaft wall, a discharge at ground level and a piece of the landlord's asset. If the occupant load a fit-out wants exceeds what the existing stairs can discharge, nothing inside the fit-out drawing fixes it: the available answers are fewer people, more suppression, or a third stair nobody is going to build.
The chain has four links and runs one way only: area to occupant load, occupant load to a number of exits, exits to a width for each, and then a check that nobody standing anywhere on the plate walks further than the adopted document permits to reach one. Every link has a named document behind it, and the numbers in those documents are not interchangeable between editions or across jurisdictions. What follows is the shape of the arithmetic and where each figure lives — not a substitute for the edition your authority has actually adopted, which is the only place the figures themselves are safe to read.
Counting people who are not there yet
Occupant load is not a forecast of attendance. It is a credible worst case derived from floor area by a factor keyed to use, and it is deliberately unkind, because that is its job. In International Building Code jurisdictions it comes from Section 1004, Occupant Load, and its table of maximum floor area allowances per occupant. NFPA 101, Life Safety Code, does the same work in Chapter 7, Means of Egress, with a factor table of its own. In England and Wales the equivalent is the floor space factor table in the appendices to Approved Document B, Volume 2, and BS 9999 offers a risk-profile route to the same figure for buildings that can justify it.
The trap in every one of those tables is the single word gross or net sitting against each entry. A gross factor is applied to the whole area inside the demise — corridors, washrooms, cupboards, internal wall thicknesses and all. A net factor is applied only to the area the use itself occupies. Swapping one for the other moves the answer by a fifth or more, which is enough to change the number of exits on its own, and the mistake survives review because both figures look entirely plausible on the page.
Then come the additions, which are not averaged into the main rate. Fixed seating is counted by seats rather than by area, with a stated length per person where a bench is fitted. A room whose use has its own denser factor — a training suite, a canteen, a town-hall space carved out of an office floor — is counted at that factor and added on top. A mezzanine puts its load into the storey below. And where an owner intends to hold more people than the table produces, the building official can accept a higher figure provided the exits are sized for it, which is why an assembly room ends up with a number screwed to the wall by the door.
The most expensive property of the number is that it may or may not stay on your floor, and which of the two it is has to be established rather than assumed, because the documents genuinely differ. The model codes size a stair on the occupant load of each storey considered individually, and add loads together only where routes from above and below converge at an intermediate level. Approved Document B and BS 9999 size an escape stair on the load accumulated from the storeys it serves, which is a different and usually larger number. Ask which of those two rules the adopted document applies, then ask for the design occupant load of every storey each stair serves, before assuming the shell-and-core figure still holds. A building let at one person per eight square metres, when its cores were designed at one per ten, has already spent capacity in a shaft that belongs to somebody else.
| The number | Where it is defined | What it is not |
|---|---|---|
| Occupant load | IBC Section 1004; NFPA 101 Chapter 7; Approved Document B floor space factors | The client's headcount, or the desk count |
| Number of exits required | IBC Section 1006; NFPA 101 occupancy chapters; Approved Document B limits on escape in one direction | The number of doors already on the plan |
| Width per occupant | IBC Section 1005; NFPA 101 capacity of means of egress; Approved Document B table of minimum widths | The structural opening, or the leaf width |
| Exit access travel distance | IBC Section 1017; NFPA 101 measurement of travel distance; Approved Document B travel distance tables | A straight line scaled off the drawing |
| Accessible means of egress and refuges | IBC Section 1009; ICC A117.1; Approved Document B refuges with Approved Document M | Something the general egress calculation already covers |
One exit, two exits, and the diagonal that settles it
How many exits a storey needs is a function of occupant load and, in several documents, of height and use as well. The threshold questions come first, and they are cliff edges rather than gradients: below a stated load and within a stated common path allowance, a space or a storey may have a single exit, and one occupant over the line it needs two. The IBC sets this out in Section 1006, Number of Exits and Exit Access Doorways, with separate tables for spaces and for storeys; NFPA 101 places it in the occupancy chapters; Approved Document B frames the same decision as whether escape in a single direction is acceptable at all, and for how far.
Two exits on a plan is not two exits in the code's sense. They have to be remote from one another, and remoteness is measured rather than judged: draw the diagonal of the area served, and the exits must be separated by at least half its length, reduced to a third where the building is sprinklered throughout. The separation is taken between the nearest edges of the two doorways, in a straight line, whether or not walls stand between them. Two doors at the same end of a plate satisfy a count and fail the diagonal, and that failure is dangerous precisely because the drawing looks compliant. The reason behind the rule outranks the arithmetic wherever no formula is written down: two exits exist so that one fire cannot take both. A pair either side of a single open kitchen, or a second exit reached only by walking past the first, is a scheme an assessor will push back on even where the diagonal passes comfortably.
- Fix the area the code counts, and state whether it is gross or net so it matches the factor about to be applied.
- Apply the factor from the adopted edition, adding fixed seating and any denser sub-use as separate figures.
- Read off the number of exits the load and the common path allowance require, for each space and then for the storey.
- Draw the diagonal of the area served and measure the separation between the two furthest-apart exit doorways against it.
- Ask what occupant load every stair is already carrying from the storeys above and below yours.
Width is sold by the occupant, and the stair charges more
With the load fixed, egress width becomes a rate. The model figures in IBC Section 1005, Means of Egress Sizing, are 0.3 inches of clear width per occupant for stairways and 0.2 inches per occupant for every other component of the route — doors, corridors, ramps, level passage. Where a building is sprinklered throughout to NFPA 13 and fitted with an emergency voice/alarm communication system, those rates drop to 0.2 and 0.15. NFPA 101 states the same base pair in its capacity factor table, but its reduced factors are keyed to occupancy rather than granted generally for sprinklers, so read them there rather than carrying the IBC reduction across by analogy. Approved Document B reaches the same place by a different road: a table of minimum widths of escape routes and exits against the number of people served, which becomes a millimetres-per-person rate above the tabulated thresholds.
Two features of the rate catch people out. The first is that a stair costs half again as much width per person as a level component does, which is why the stair rather than the door is nearly always the binding constraint on an upper floor. The second is that the calculated width is a floor, not a target: absolute minimum dimensions sit on top of it and routinely govern in smaller buildings, so a corridor serving a dozen people is not two and a half inches wide.
There is also a rule that stops the whole capacity being spent in one place. Where more than one exit is required, the loss of any single exit must not reduce the remaining capacity below half of what the storey requires. On a two-stair floor that means each stair carries half the load and neither may be sized to the leftovers. It rules out the scheme that meets the total by making one stair generous and the other minimal — which is exactly what happens when one stair is inherited from the shell and the new one is being squeezed into whatever corner is free.
Capacity is measured at the narrowest point of each component, and the narrowest point is rarely drawn. Handrails, an extinguisher cabinet, a surface-mounted closer arm, a column the finishes were drawn around, a radiator on a corridor wall: each takes width at the height where width counts. The model codes permit a stated projection from certain elements and none at all from others, and those allowances come from the adopted document rather than from the corridor looking generous when you stand in it.
The door is narrower than its opening and wider than the corridor
A door's contribution to capacity is its clear width, measured with the leaf open ninety degrees, from the face of the door to the stop on the opposite jamb. That is materially less than the structural opening, and it is the dimension the width rate is applied to. Hardware takes a further bite — a projecting closer body, an overpanel bolt, a push bar on a shallow rebate. Where a pair is fitted and only one leaf carries operable hardware, the model codes will generally credit the active leaf alone.
Swing direction is decided by occupant load, not by convenience. Above the stated threshold — fifty occupants in the model codes for most uses, and any occupant load in the high-hazard groups — the leaf must swing in the direction of egress travel, which turns it into an object that swings into whatever is on the far side. Panic hardware becomes mandatory in the same band for assembly and educational occupancies and for high-hazard groups. A door swinging out of a room into a corridor is limited twice over, and the two limits are the ones most often quoted the wrong way round: when the leaf is fully open it may project no further than a stated dimension into the required width, and at no point anywhere in its swing may it reduce that width by more than half.
Which is where the accessible clearance lands on top of all of it. The maneuvering clearance a door needs on each face is not egress width and cannot be traded against it, but the two occupy the same square metres of floor. The clearance is deeper on the pull side, deeper again on a latch-side approach, and deeper again where the door carries both a closer and a latch — which describes every fire door on an escape route. A corridor with a required width of 1200 mm and a latch-side approach at each doorway does not have 1200 mm of corridor at those points; it has 1200 mm less whatever the clearance takes out of it, and the deduction lands exactly where people are converging.
The doors on an escape route are the ones with a closer and a latch, which is the combination that demands the most floor alongside the opening — set the approach and the side and check the depth against the corridor width you were counting on.
Required clear depth at the door
60 in1,524 mm
- Clear space required alongside the doorway
- 18 in457.2 mm
- Total clear width of the maneuvering space
- 50 in1,270 mm
Corridor, common path and dead end are three tapes, not one
Three different measurements get called travel distance in meetings, and they are measured from different points to different endpoints against separate limits. Common path of travel is the stretch where the occupant has no choice of direction, from the most remote point until two independent routes genuinely become available. A dead end is the length of corridor beyond the last point at which somebody could have turned the other way. Exit access travel distance is the whole walk from the most remote point to the exit itself. A corridor can clear the travel distance limit with room to spare and still fail on the dead end at its far end, and the two failures have entirely different fixes.
Corridors carry requirements alongside width. A fire-resistance rating tied to occupancy and sprinkler status sits in IBC Section 1020, Corridors, with equivalents in NFPA 101 and Approved Document B; that rating has to be continuous above the ceiling and through every penetration; and where a corridor acts as an exit passageway, or as the exit access from a stair discharge, tighter rules apply again. None of it changes the width arithmetic, but all of it changes what the corridor costs, because a rated corridor is a different partition build-up, ceiling and firestopping schedule.
The dead end is the one that catches fit-outs rather than base builds. Shell floors are usually handed over as a clean loop or a straight run between two cores, with nothing that could be called a dead end anywhere on them. Then a tenant layout drops a cellular block at one end and leaves a nine-metre spur to a meeting room. That spur is a dead end whether or not anybody names it one, and its limit is a small number keyed to occupancy and to whether the building is sprinklered.
Measuring the walk the way an assessor measures it
Exit access travel distance is measured along the natural and unobstructed path of travel, on the floor, from the most remote occupiable point to the entrance to the exit — which in a multi-storey building means the door into the protected stair enclosure, not the street outside. That endpoint is the most misunderstood part of the whole exercise, and it is misunderstood in both directions: designers include the descent and conclude the plate fails when it does not, or stop the tape at the corridor and miss the last leg to the enclosure door.
The path bends. It goes around fixed furniture, around the reception desk, around the demountable partition run sitting in the tenant package, and along the centre of the route rather than through walls. It follows the aisle a bench layout actually leaves, not the diagonal across an empty floor. Where no layout is fixed at the time of the check, the honest method is to measure the worst plausible arrangement and write down which arrangement was assumed — that assumption is the thing a future fit-out will breach without ever knowing it existed.
The limit itself sits in a table keyed to occupancy group and to sprinkler protection: IBC Section 1017, Exit Access Travel Distance; NFPA 101's occupancy chapters read with the measurement provisions in Chapter 7; and the travel distance tables in Approved Document B, which distinguish escape in one direction from escape in more than one. The sprinkler increase is the largest single lever in the calculation, and on most commercial plates it has already been spent — the floor is only compliant because the building is sprinklered, which quietly makes any proposal to value-engineer, defer or partially omit suppression an egress decision rather than a suppression one. Where the walk still exceeds the allowance, the remaining levers in ascending order of cost are to move an exit, add an exit, add a protected corridor so the measurement stops earlier, or reduce the occupied depth of the plate.
The six hundred millimetre step in the middle of the route
Level changes inside a plate are common and almost never on the concept drawing: a raised plant area, a slab that steps at an old party line, a made-up floor over a former loading bay, a datum change between a retained building and its extension. On an escape route that step is a problem twice over. It has to be negotiable by everyone the accessible means of egress provisions cover, which normally means a ramp rather than steps, and a ramp is not a point on the plan — it is a length of travel distance.
That is the part that catches people. At the maximum slope permitted on an accessible route, a rise of 600 mm buys over seven metres of run before a single landing, and the standards break the run at a stated maximum rise with a level landing between each pair. The whole assembly sits inside the measured path and is measured along its surface, not across its plan chord. A step that reads as nothing at 1:200 can spend a dozen metres of the travel distance allowance without a wall moving anywhere.
Ramps also drag their own requirements onto the route. There is a maximum slope for egress purposes, landings at top, bottom and every change of direction, handrails once the rise passes the stated threshold, and edge protection along both sides — and the handrail extensions at each end land in the corridor and take width there, at exactly the point where people are being funnelled. Where the ramp is the only way past the level change, every metre of it is on the escape route and every metre of it is in the measurement.
Give it the rise and it returns the run plus the landings the standard forces, which is the length that has to come out of the travel distance allowance before the layout can be called compliant.
Total ramp horizontal length
53 ft16.2 m
- Number of ramp runs
- 2 runs
- Intermediate landings required
- 1 landing
Reserving the shaft before the core is issued
A stair enclosure is a plan dimension decided by a section. Storey height divided into equal risers gives the number of treads; treads multiplied by the going gives the flight length; two flights plus two landings, each landing at least as deep as the flight is wide, gives the internal length of the shaft. Get that wrong at concept and the core is either too small, which the stair contractor discovers eighteen months later with the slabs poured, or too large, which nobody discovers at all because the surplus quietly becomes a cupboard.
Escape stairs are not domestic stairs, and the geometry that governs them is stricter in precisely the directions that cost plan area: a lower maximum riser, a deeper minimum tread, a maximum vertical rise between landings that forces an intermediate landing on tall storeys, and a minimum clear width that in most small buildings exceeds the width the capacity arithmetic asked for. Take those from the stairways provisions of the adopted building code rather than from the residential rules, which are the defaults most stair tools ship with and the ones a commercial scheme will fail against.
Dividing the rise so that every riser is equal, and holding that equality through the finishes, is a separate craft with its own guide on this site. What the layout needs from it at this stage is one output only: how long the flight is, and therefore how much of the floor plate the shaft has to take.
Enter the finished floor-to-floor height and the riser and going you intend to hold, and the riser count it returns is what converts a section dimension into the plan length the stair shaft has to reserve — its compliance badge is checked against residential limits only, so take the escape-stair geometry itself from the adopted commercial provisions.
Number of risers needed
21 risers
- Actual riser height
- 6.86 in174.17 mm
- Number of treads (steps)
- 20 treads
The flight as a fabricated diagonal
Where the escape stair is a steel pan-and-plate flight inside a masonry or shaftwall enclosure, which describes most commercial escape stairs, the flight stops being a layout gesture and becomes a fabricated component with a diagonal length, two end connections and a delivery route. That diagonal is worth having early for two reasons that have nothing to do with the fabricator: it tells you whether the flight actually lands where you drew the landing edges, and it sets the line the headroom is measured from — which is where a stair scheme most often fails once a slab edge, a beam or a duct arrives above it.
It also decides how the stair gets into the building. A single flight for a 3.6 metre storey is a long, heavy, awkward object, and the difference between a shaft that can receive it in one piece and one that cannot is a fabrication break, a site splice and a bolted connection somebody has to detail. Establish the length before the shaft dimensions are frozen rather than after the enclosure has been built around a hole.
The rise and run of one flight give the diagonal the fabricator works to, and it is also the fastest check that the flight you have drawn reaches the landing you have drawn.
Stringer length
16.4 ft5 m
Where somebody waits, and what they wait in
The general egress calculation assumes everyone walks down the stair. The accessible means of egress provisions assume some people will not, and they put the consequence on the stair landing. IBC Section 1009, Accessible Means of Egress, requires the accessible route to continue to an area of refuge, an exterior area for assisted rescue, or a stairway or lift meeting stated criteria, and it sets a clear width between handrails on a stairway forming part of that route which is wider than the stair would otherwise need to be. In England the parallel arrangement is the refuge described in Approved Document B, sized around a wheelchair space of 900 mm by 1400 mm, with two-way communication to a point where somebody is actually listening.
One clause decides the geometry and carries a large consequence: the wheelchair space in a refuge must not reduce the width of the escape route it sits in. The space is therefore added to the landing rather than carved out of it, and a core sized to the minimum landing has nowhere to put it. On a retrofit that is why refuges end up in awkward positions — a widened lobby, a recess formed by shifting a riser, a bay borrowed from a cupboard — and each of those is a structural or a services change rather than a change to a drawing.
Check it as an available rectangle rather than as a circle drawn on the plan, because a rectangle is what the landing offers: clear width between the wall and the handrail line, against clear depth between the door swing arc and the top nosing. Both have to be free of the swing, the handrail and anything wall-mounted at any height. The shorter of the two is the answer, and it is the one to record.
Take the clear width and depth the landing genuinely leaves once the door swing arc and the handrail line are deducted, and check the shorter of the two against the turning space the accessibility standard requires.
Limiting available dimension
5 ft1.52 m
- Required minimum diameter (ADA 304.3.1)
- 5 ft1.52 m
What the drawing has to say when it leaves your desk
Every number in this exercise rests on an assumption that a later drawing can break without anyone noticing. The occupant load rests on a factor and on whether the area behind it was gross or net. The travel distance rests on a furniture layout that has not been bought yet. The corridor width rests on nothing ever being mounted on its walls. The exit count rests on a sprinkler system being installed, commissioned and maintained. The refuge rests on a landing dimension surviving the finishes package.
So the deliverable is not the plan. It is the plan plus a short, dated schedule of those assumptions, naming the document and the edition each figure came from. That schedule is what the building control body reads, what the next fit-out designer reads, and what protects the work when a tenant puts a store cupboard across a dead-end limit three years later. Two further packages are then sized directly off the fixed route, and both are far cheaper to coordinate now than to retrofit: escape lighting along the route and at the points the standard calls out irrespective of spacing, and exit signage with sight lines that survive the ceiling and the eventual partition layout. Neither changes a single width. Both fail an inspection just as effectively as a missing exit does.
Fix these before the core drawing is issued
Every line below is a figure some other document owns. Record the number, the document and the edition together — the first thing a checker asks is which edition you read.
- Occupant load, and the factor behind it — The area the factor was applied to, stated as gross or net, with fixed seating and any denser sub-use listed as separate additions rather than averaged into the main rate.
- Exit count and the diagonal check — Two exits on the plan are not two exits until the separation between the nearest edges of their doorways has been measured against the diagonal of the area they serve.
- Required width for each component — Applied at the narrowest point of every door, corridor, ramp and stair, with the loss-of-one-exit distribution rule tested rather than assumed to be satisfied.
- Longest measured walk on the plate — Taken along the natural path around fixed furniture to the enclosure door, with the layout that was assumed written down beside the figure.
- Internal length of each stair shaft — Derived from the storey height and the riser and going the code requires, not from the box the shell-and-core drawing happens to show.
- Refuge space and the landing that holds it — Added to the required escape width rather than taken out of it, and clear of the door swing arc, the handrail line and anything wall-mounted.
Opens the calculators above on one screen with the dimensions from this article already filled in. Quantities only — this site publishes no price list, because local prices vary too much to publish honestly.