Temporary Site Trailer Electrical Load Calculator

Calculate the total connected electrical load and required amperage for a construction site office trailer's temporary power.

  • Answers as you type
  • Every formula cited
  • Calculated in your browser
SettingsSettings for this calculationUS
Market
Imperial · sales tax
The total connected lighting load in the site trailer, in volt-amps.

Sum the volt-amp (or watt) ratings of all lighting fixtures and circuits in the trailer.

The total connected heating/cooling equipment load, in volt-amps.

Use the nameplate volt-amp rating of the trailer's window/split AC unit(s) and any electric heaters.

The total connected load from receptacles, computers, printers, and other plugged-in equipment, in volt-amps.

Sum the expected volt-amp draw of office equipment, chargers, and any other receptacle loads planned for the trailer.

The service voltage supplying the trailer.

Common temporary construction power is single-phase 120/240V — confirm the actual voltage of the temporary service or generator supplying the trailer.

Required service amperage

29.2 A

Medium confidence

This is a simple connected-load sum with no demand factor applied — NEC Article 590 (Temporary Installations) governs the actual code requirements for temporary construction power, including conductor sizing, GFCI protection, and disconnect requirements, which this calculator does not address. Round up to the next standard breaker/service size and consult a licensed electrician for the actual installation.

Total connected load
7,000 VA
Then change the inputs to see how far the answer moves.

Show calculation logic

How this was calculated

Formula source(s)

  • Total connected load (VA) = Lighting + HVAC + Receptacle Loads; Required amperage = Total VA ÷ Voltage — a straightforward connected-load sum with no demand factor applied (unlike a permanent dwelling service calculation), appropriate for a temporary construction trailer under NEC Article 590 (Temporary Installations), which governs the actual code requirements for temporary wiring.

Inputs used

Lighting Load (VA)
1500
HVAC Load (VA)
3500
Receptacle/Equipment Load (VA)
2000
Voltage (V)
240

Intermediate steps

Total connected load
7,000 VA
Final result29.17 A

Confidence note: This is a simple connected-load sum with no demand factor applied — NEC Article 590 (Temporary Installations) governs the actual code requirements for temporary construction power, including conductor sizing, GFCI protection, and disconnect requirements, which this calculator does not address. Round up to the next standard breaker/service size and consult a licensed electrician for the actual installation.

What this calculation does not cover

  • Divides the whole load by the voltage, which only gives the per-leg current if the load splits evenly across both legs of a 120/240 V supply. It never does — the lighting, receptacles and office gear are all 120 V and land wherever the panel schedule puts them. A trailer that computes 29 A total can be pulling 40 A on one leg and 18 A on the other, and the leg is what trips.
  • Connected load is not breaker size. A continuous load is sized at 125 % for the overcurrent device, and the trailer's air conditioner pulls several times its nameplate for the first second of every start. This figure is what the equipment eats while running, not what the breaker has to survive when the compressor kicks in on a hot afternoon.
  • If a generator is feeding the trailer rather than a temporary pole, amperage is the wrong question. A set is rated in kW at a stated power factor, and it is the motor starting kVA of the air conditioner that sizes it — a genset matched to the running load sags and stalls on AC startup, and the office reboots with it.

Add the equipment this sizes

This result is a specification — 29.2 A — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.

Sources checked 2026-09-06 · in the site-wide review of 2026-09-06 · v1.0.1

Regulatory standards & verification citations1
  1. Total connected load (VA) = Lighting + HVAC + Receptacle Loads; Required amperage = Total VA ÷ Voltage — a straightforward connected-load sum with no demand factor applied (unlike a permanent dwelling service calculation), appropriate for a temporary construction trailer under NEC Article 590 (Temporary Installations), which governs the actual code requirements for temporary wiring.

Which documents these citations point at

  • National Electrical Code (NFPA 70) — Article 590 (United States)Electrical installations — conductor sizing and protection, load calculation, wiring methods, grounding and working clearances.

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments. This site holds no adoption data for any authority, so check what is in force with the authority where you build. Any section cited above without an edition should be checked against the edition in force where you build. What it would take to know.

Cite this page

Your workspace

Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.

Now that you have the number

These guides cover the work this quantity is for — the first ones run this calculator inside the section that raises the question.

How to calculate temporary site trailer electrical load in 5 steps

  1. Lighting Load (VA)The total connected lighting load in the site trailer, in volt-amps.
  2. HVAC Load (VA)The total connected heating/cooling equipment load, in volt-amps.
  3. Receptacle/Equipment Load (VA)The total connected load from receptacles, computers, printers, and other plugged-in equipment, in volt-amps.
  4. Voltage (V)The service voltage supplying the trailer.
  5. Required service amperageThe tool computes the required service amperage from those figures and shows the formula, its sources, and a confidence rating alongside it.

Required service amperage by lighting load (VA)

Page defaults, not your figures above.

Lighting Load (VA)Required service amperage (A)
20023.8
50025
1,00027.1
2,00031.3
5,00043.8
10,00064.6

Frequently asked questions

Does this calculation apply a demand factor like a permanent dwelling load calculation?
No — it is a straightforward connected-load sum (lighting + HVAC + receptacle loads) with no demand factor applied, which is the appropriate approach for a temporary construction trailer under NEC Article 590 (Temporary Installations).
What amperage/breaker size should I actually install?
Round the calculated amperage up to the next standard breaker or service size, and always consult a licensed electrician. This calculator gives only the raw connected-load amperage and does not address conductor sizing, GFCI protection, or disconnect requirements, all of which NEC Article 590 governs for temporary installations.
Where do I get the VA values for lighting, HVAC, and receptacle loads?
Use the nameplate volt-amp (or watt) ratings on the trailer's lighting fixtures, air conditioner/heater, and any plugged-in equipment — sum each category separately before entering it here.
Preliminary estimate, not certified engineering. This tool produces an indicative quantity calculation for planning purposes only — it is not a certified structural analysis, a guaranteed material takeoff, or a substitute for building department approval. Always verify measurements on-site and have a licensed contractor or structural engineer review any load-bearing, code-sensitive, or safety-critical work before purchasing materials or starting construction. Spotted an arithmetic or standards error? Report it to contact@craftquantities.com with your inputs — a confirmed fix gets a permanent check of its own, so the same mistake cannot come back.