Materials & Quantities

Concrete Anchor Proof Load Test Calculator

The load a site proof test on concrete anchors is held at, and how many anchors in a lot to pull, from your specification's multiplier and sample rate.

  • Answers as you type
  • Every formula cited
  • Calculated in your browser
SettingsSettings for this calculationUS
Market
Imperial · sales tax
The tension the anchor is designed to carry in service.

Use the same load case the specification's multiplier was written against. A multiplier meant for a service load applied to a factored one, or the reverse, moves the test load by the whole load factor — and the anchor either fails a test it should have passed or passes one that proved nothing.

How many times the design tension the specification asks the test to reach.

Common specified values sit between 1.25 and 2.0, but there is no default worth assuming — the figure belongs to the contract, and inspectors routinely reject a test carried out at the wrong multiplier even when the anchor held.

How many anchors this lot covers — one installer, one product, one condition.

A lot should be homogeneous: the same anchor, the same crew, the same base material and the same day. Sampling across a boundary the specification treats as separate produces a test result that certifies neither group.

The proportion of the lot the specification requires to be tested.

Rates are commonly written as a percentage of the lot with a floor, and are often raised for the first lot or after any failure. Where the specification requires every anchor tested, enter one hundred.

The floor the specification puts under the sample, whatever the percentage gives.

Small lots are why this exists: five per cent of a lot of twelve is one anchor, which is a sample of one and tells you very little. Enter zero if the specification sets no floor.

Proof load to apply and hold

2,700 lbf

Medium confidence

The sample rate governs this lot. A proof test demonstrates that the installation holds the specified load without measurable displacement; it is not a capacity test and must not be taken to the anchor's ultimate. Confirm the specification's cap on the applied load, and confirm what counts as a failure and what happens to the rest of the lot when one occurs.

Anchors to test in this lot
6 anchors
Sample size before the specified floor
6 anchors
Load applied above the design tension
899.24 lbf
Anchors covered by each tested anchor
20 anchors
Then change the inputs to see how far the answer moves.

Show calculation logic

How this was calculated

Formula source(s)

  • ASTM E488/E488M, Standard Test Methods for Strength of Anchors in Concrete Elements — the reference method for applying and measuring a tension load on an installed anchor
  • The proof-load multiplier and the sampling rate are project values, not standard ones: they come from the contract specification and the special inspection programme, which is why both are entered here rather than assumed
  • Arithmetic only: proof load = design tension × the specified multiplier; anchors to test = the specified percentage of the lot, rounded up, subject to the specified minimum and never more than the lot holds

Inputs used

Design Tension per Anchor
1798.47 lbf
Specified Proof-Load Multiplier
1.5
Anchors in the Test Lot
120
Specified Sample Rate
5
Specified Minimum per Lot
2

Intermediate steps

Anchors to test in this lot
6 anchors
Sample size before the specified floor
6 anchors
Load applied above the design tension
899.24 lbf
Anchors covered by each tested anchor
20 anchors
Final result2,697.71 lbf

Confidence note: The sample rate governs this lot. A proof test demonstrates that the installation holds the specified load without measurable displacement; it is not a capacity test and must not be taken to the anchor's ultimate. Confirm the specification's cap on the applied load, and confirm what counts as a failure and what happens to the rest of the lot when one occurs.

What this calculation does not cover

  • Does not set the multiplier or the sample rate. Both are contract values, and a page that supplied them would be inventing the specification.
  • Does not check that the proof load is safe to apply. A multiplier taken against a load close to the anchor's capacity can exceed the steel or the concrete during the test itself.

Add the equipment this sizes

This result is a specification — 2,700 lbf — not a quantity. Put the thing it sizes into your project: how many, what you call it, and your supplier’s price.

Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.

Sources checked 2026-09-02 · in the site-wide review of 2026-09-06 · v1.0.1

Regulatory standards & verification citations3
  1. ASTM E488/E488M, Standard Test Methods for Strength of Anchors in Concrete Elements — the reference method for applying and measuring a tension load on an installed anchor
  2. The proof-load multiplier and the sampling rate are project values, not standard ones: they come from the contract specification and the special inspection programme, which is why both are entered here rather than assumed
  3. Arithmetic only: proof load = design tension × the specified multiplier; anchors to test = the specified percentage of the lot, rounded up, subject to the specified minimum and never more than the lot holds

Which documents these citations point at

Standards referenced: ASTM E488 (ASTM International, United States).

Cite this page

Your workspace

Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.

Now that you have the number

These guides cover the work this quantity is for — the first ones run this calculator inside the section that raises the question.

Called something else where you work? Anchor and fixing — the term in each market, how close the equivalence really is, and the standard that governs it.

Still deciding? Anchor Design vs Proof Testing — the factors that actually differ, with no invented prices.

How to calculate concrete anchor proof load test in 6 steps

  1. Design Tension per AnchorThe tension the anchor is designed to carry in service.
  2. Specified Proof-Load MultiplierHow many times the design tension the specification asks the test to reach.
  3. Anchors in the Test LotHow many anchors this lot covers — one installer, one product, one condition.
  4. Specified Sample RateThe proportion of the lot the specification requires to be tested.
  5. Specified Minimum per LotThe floor the specification puts under the sample, whatever the percentage gives.
  6. Proof load to apply and holdThe tool computes the proof load to apply and hold from those figures and shows the formula, its sources, and a confidence rating alongside it.

Proof load to apply and hold by design tension per anchor

Page defaults, not your figures above.

Design Tension per AnchorProof load to apply and hold (lbf)
1,000 lbf1,500
1,500 lbf2,250
2,000 lbf3,000
2,500 lbf3,750
3,000 lbf4,500
3,500 lbf5,250

Frequently asked questions

What counts as passing a proof test?
Reaching the specified load and holding it for the specified duration without the anchor displacing beyond the allowance the specification sets, and without the concrete showing distress around it. The criterion is displacement, not survival: an anchor that creeps steadily under a held load has failed even though nothing has come out of the hole.
Why not simply test every anchor?
Because proof testing is not free of consequence. Each test loads the anchor and the concrete around it, and testing to a high multiplier can damage the very installation you are certifying. Sampling exists to detect a systematic installation problem — the wrong hole size, an uncleaned hole, a crew skipping a step — which shows up in a sample if it is present at all.
One anchor in my sample failed. What happens to the lot?
That is a specification question and the answers vary widely: some require two further anchors tested for every failure, some require the whole lot tested, some require the lot removed and reinstalled. Agree the rule before testing starts rather than after a failure, because the difference between those outcomes is days of programme.
Does a passed proof test mean the anchor design is right?
No, and confusing the two is a real risk on site. A proof test verifies the installation — that this anchor, in this hole, in this concrete, holds the specified load. Whether the specified load is the right one for the connection is a design calculation that happened long before anyone brought a pull rig to site.
Preliminary estimate, not certified engineering. This tool produces an indicative quantity calculation for planning purposes only — it is not a certified structural analysis, a guaranteed material takeoff, or a substitute for building department approval. Always verify measurements on-site and have a licensed contractor or structural engineer review any load-bearing, code-sensitive, or safety-critical work before purchasing materials or starting construction. Spotted an arithmetic or standards error? Report it to contact@craftquantities.com with your inputs — a confirmed fix gets a permanent check of its own, so the same mistake cannot come back.