Fire Extinguisher Count and Travel Distance Calculator

How many extinguishers a floor takes by the area rule and by the travel rule — and which of the two governs, because it is usually the one people skip.

  • Answers as you type
  • Every formula cited
  • Calculated in your browser
SettingsSettings for this calculationUS
Market
Imperial · sales tax
The area one storey covers.

Take one storey at a time. Both rules are applied per floor, and a building with the same total area over two storeys needs more extinguishers than one storey of twice the size — because nobody walks between floors to reach one.

What is in the space, not what the building is called.

The class follows the quantity and combustibility of what is stored and handled. An office with a large paper store is not light hazard in that store. Where a building holds more than one class, work each area separately rather than averaging them.

The number before the A on the label — 2-A, 4-A, 10-A.

A higher rating covers more floor area in proportion, up to the cap one extinguisher may cover however it is rated. It does not extend the distance anybody will walk, which is why raising the rating often does not reduce the count.

How far anybody may have to walk to reach one.

75 ft is the NFPA 10 figure for Class A and 30 m the BS 5306-8 one. Measure it as somebody would walk it — around partitions, through doorways, not across the room — which is exactly the part a floor area cannot see.

A floor gets at least this many however small it is.

BS 5306-8 asks for at least two per floor so that one is still reachable when a fire blocks the route to the other. NFPA 10 has no equivalent blanket minimum, so set this to one if you are working strictly to it.

Extinguishers needed

4 extinguishers

Medium confidence

Floor area governs here — 4 by area, 2 by travel, and at least 2 per storey. Where they disagree the larger is the one to take.

By the area rule
4 extinguishers
By the travel rule
2 extinguishers
Area one extinguisher covers, area rule
3,000 sq ft
Area one extinguisher covers, travel rule
5,625 sq ft
Grid spacing the travel rule allows
75 ft
Then change the inputs to see how far the answer moves.

Show calculation logic

How this was calculated

Formula source(s)

  • NFPA 10 gives a maximum floor area per unit of A by hazard class — 3,000 ft² light, 1,500 ft² ordinary, 1,000 ft² extra — with 11,250 ft² the most any single extinguisher may cover whatever its rating
  • Maximum travel distance to a Class A extinguisher is 75 ft (about 23 m). On a square grid walked along its axes the worst case is half the spacing in each direction, so one extinguisher covers at most the travel distance squared
  • BS 5306-8 works to a comparable figure — a 30 m travel distance and a minimum of two extinguishers per floor — which is why the minimum-per-floor field exists

Inputs used

Floor area per storey
10760 sq ft
Hazard class
Ordinary — retail, workshops, parking
Extinguisher A rating
2
Maximum travel distance
75 ft
Minimum per storey
2

Intermediate steps

By the area rule
4 extinguishers
By the travel rule
2 extinguishers
Area one extinguisher covers, area rule
3,000 sq ft
Area one extinguisher covers, travel rule
5,625 sq ft
Grid spacing the travel rule allows
75 ft
Final result4 extinguishers

Confidence note: Floor area governs here — 4 by area, 2 by travel, and at least 2 per storey. Where they disagree the larger is the one to take.

What this calculation does not cover

  • THIS IS A QUANTITY, NOT A COMPLIANCE CHECK. Travel distance is a property of the layout — doors, corridors, partitions, racking — and no floor area can see it. Two extinguishers on the right walls can satisfy a floor that this count says needs three, and three in the wrong places can fail a floor it says needs two.
  • Class A only. Class B liquids, Class C electrical, Class D metals and Class F or K cooking oils each carry their own siting rule, and a kitchen or a plant room is sited on the hazard in it rather than on the floor it sits on.
  • The hazard class follows what is stored and handled, not what the building is called. Where one building holds more than one class, work each area separately — averaging them produces a number that is wrong in both directions at once.
  • Nothing here covers mounting height, signage, the distance from the hazard the extinguisher protects, or the inspection regime that keeps it usable. An uncommissioned extinguisher on the right wall counts for nothing.

Estimated cost — your price

This site holds no price list for this material — local prices vary too much to publish honestly. Enter your supplier's price and the result is costed with it.

Computed in your browser — nothing you enter is uploaded. Presented in US customary units and US trade terminology. Where a formula follows a published standard, that standard and its edition are cited beside it on this page; where none governs, the page says so. Local amendments override model codes — verify against the code in force where you build.

Sources checked 2026-09-23 · v1.0.0

Regulatory standards & verification citations3
  1. NFPA 10 gives a maximum floor area per unit of A by hazard class — 3,000 ft² light, 1,500 ft² ordinary, 1,000 ft² extra — with 11,250 ft² the most any single extinguisher may cover whatever its rating
  2. Maximum travel distance to a Class A extinguisher is 75 ft (about 23 m). On a square grid walked along its axes the worst case is half the spacing in each direction, so one extinguisher covers at most the travel distance squared
  3. BS 5306-8 works to a comparable figure — a 30 m travel distance and a minimum of two extinguishers per floor — which is why the minimum-per-floor field exists

Which documents these citations point at

Standards referenced: NFPA 10 (National Fire Protection Association, United States).

Cite this page

Your workspace

Most jobs need more than one number. Add the calculators you need next and they open right here, underneath this one — your figures stay on screen and nothing is lost to a page change.

How to calculate fire extinguisher count and travel distance in 6 steps

  1. Floor area per storeyThe area one storey covers.
  2. Hazard classWhat is in the space, not what the building is called.
  3. Extinguisher A ratingThe number before the A on the label — 2-A, 4-A, 10-A.
  4. Maximum travel distanceHow far anybody may have to walk to reach one.
  5. Minimum per storeyA floor gets at least this many however small it is.
  6. Extinguishers neededThe tool computes the extinguishers needed from those figures and shows the formula, its sources, and a confidence rating alongside it.

Extinguishers needed by floor area per storey

Page defaults, not your figures above.

Floor area per storeyExtinguishers needed (extinguishers)
5,000 sq ft2
10,000 sq ft4
15,000 sq ft5
20,000 sq ft7

Frequently asked questions

How many fire extinguishers do I need?
The larger of the area rule and the travel rule: the page's 1,000 m² (about 10,800 sq ft) ordinary-hazard floor with 2-A extinguishers needs four by area against two by travel, so four. The area rule gives four because each covers 1,500 sq ft per unit of A, and the travel rule at 75 ft would allow two. On a light-hazard floor of the same size the two swap over.
Which rule usually decides it?
Travel distance, in open-plan space. A 2-A extinguisher covers 6,000 sq ft on a light-hazard floor by area, and only about 5,625 sq ft by a 75 ft travel limit on a square grid. That is why an area-only count comes out short, and why raising the extinguisher's rating frequently does not reduce how many you need — a bigger extinguisher does not shorten the walk.
Does a bigger rating mean fewer extinguishers?
Only up to a point, and often not at all. The area one unit may cover rises with the rating but stops at 11,250 sq ft however it is rated, and the travel limit does not move at all. Once travel is the governing rule — which in open space it usually is — a 10-A extinguisher counts exactly the same as a 2-A one.
Is this enough to satisfy an inspector?
No, and it does not try to be. This is a quantity. Travel distance is a property of the layout — doors, corridors, partitions, racking — and a floor area cannot see any of it, so two extinguishers on the right walls can serve a floor this count says needs three. Class B, C, D and F hazards carry their own siting rules, and mounting, signage and inspection are outside it entirely.
Preliminary estimate, not certified engineering. This tool produces an indicative quantity calculation for planning purposes only — it is not a certified structural analysis, a guaranteed material takeoff, or a substitute for building department approval. Always verify measurements on-site and have a licensed contractor or structural engineer review any load-bearing, code-sensitive, or safety-critical work before purchasing materials or starting construction. Spotted an arithmetic or standards error? Report it to contact@craftquantities.com with your inputs — a confirmed fix gets a permanent check of its own, so the same mistake cannot come back.