# Deflection, Creep and Vibration: What Governs a Span

> Why doubling a span multiplies its deflection by sixteen, why a stronger grade of steel does nothing for it, and why a floor that passes every deflection…

Page: https://craftquantities.com/methodology/deflection-and-vibration/ (methodology paper). This is the page's Markdown copy; the HTML page is the canonical version.

Why doubling a span multiplies its deflection by sixteen, why a stronger grade of steel does nothing for it, and why a floor that passes every deflection check can still be unacceptable to walk on.

- 6 Sections
- 1 Equations
- 9 Calculators

## The fourth power, and what it means for long spans

Deflection under a uniformly distributed load grows with the FOURTH power of the span. Doubling a span multiplies its deflection by sixteen while multiplying its bending moment by only four — so the two checks diverge rapidly as members get longer.

The consequence is a crossover. Short members are governed by STRENGTH: they will break before they sag noticeably. Long members are governed by STIFFNESS: they will sag unacceptably long before they are anywhere near breaking. Somewhere in between the governing check changes hands, and which side of it a member sits on determines what to do about it.

This is why a [joist](https://craftquantities.com/glossary/joist/) table has two columns for the same [timber](https://craftquantities.com/glossary/timber/), why a long-span [truss](https://craftquantities.com/glossary/roof-truss/) is deeper than its moment demands, and why the answer to "the beam does not work" depends entirely on WHICH check failed. Strengthening a stiffness-governed member is money spent on the wrong property.

δ=5 384⁢w⁢L 4 E⁢I

_Mid-span deflection of a simply supported beam under a uniform load: proportional to the load and the fourth power of the span, inversely proportional to the modulus and the second moment of area._

**δ**

deflection at mid-span

**w**

uniformly distributed load per unit length

**L**

span — entering to the FOURTH power

**E**

elastic modulus, a material constant that grade does not change

**I**

second moment of area, growing with depth cubed

## Grade does nothing; depth does everything

The modulus of elasticity is a property of the MATERIAL, not of its strength grade. Structural steel has essentially one modulus whatever its yield strength, so specifying a higher grade to cure a deflection problem achieves precisely nothing — the member is stronger and exactly as flexible.

The same is true within a species of [timber](https://craftquantities.com/glossary/timber/) to a lesser degree, and within a concrete strength class to a lesser degree still; concrete's modulus does rise with strength, but only with its square root, so doubling the strength buys about forty per cent more stiffness for a great deal more [cement](https://craftquantities.com/glossary/cement/).

What works is geometry. The second moment of area grows with depth cubed, so fifty per cent more depth is more than three times the stiffness. That is the lever, and it is why deflection problems are solved by deeper sections, closer spacing, or a shorter span — and by nothing else.

## Which deflection, and what the limit protects

A deflection limit is meaningless without saying which deflection it applies to, and codes give several. TOTAL deflection includes the dead load, and matters for clearances, drainage and appearance. LIVE-LOAD deflection excludes it, and matters for the finishes — because a plaster ceiling is applied after the dead load is already on and only ever sees what comes afterwards. INCREMENTAL deflection is what happens after a specified stage, which is the one a brittle partition actually experiences.

So a member is routinely checked two or three times against different limits, and passing one says nothing about the others. The limits themselves are ratios of span, and they differ by what is being protected: a plastered ceiling gets a tighter limit than an open soffit, a roof draining to a low point gets a tighter one than a pitched roof.

On a low-slope roof the limit exists to prevent PONDING, and it is qualitatively different from the others: water collecting in a sagging bay adds load, which deepens the sag, which collects more water. That feedback does not settle at a new equilibrium if the roof is flat enough, which is why deck limits can look tight for a structure carrying nothing brittle at all.

## Creep: the deflection that arrives later

[Timber](https://craftquantities.com/glossary/timber/) and concrete continue to deflect under sustained load long after it is applied. The mechanism is different in each — moisture movement and fibre relaxation in timber, gradual deformation of the [cement](https://craftquantities.com/glossary/cement/) paste in concrete — but the consequence is the same: the deflection measured on the day the props come out is not the one the finishes will live with.

The codes handle it with a long-term multiplier applied to the dead-load portion, and it is not a small correction. For timber the long-term deflection under sustained load can approach twice the immediate one, and for concrete more. Only the SUSTAINED part of the load creeps; a live load that comes and goes does not.

Steel does not creep at ambient temperature, which is one of the reasons steel sections can be sized on immediate deflection alone and timber cannot. It is also why a timber floor that felt fine on handover can feel different two heating seasons later without anything having changed.

## Vibration is not deflection, and a passing floor can still be wrong

A floor that satisfies every deflection limit can still be unpleasant to walk on, and the reason is that vibration is a different question. What matters is the floor's natural FREQUENCY and its response to footfall — not its static sag under a load nobody is applying.

Frequency depends on stiffness and mass together: stiffer raises it, heavier lowers it. Human walking produces harmonics in a band that a lightweight long-span floor can fall squarely into, at which point ordinary footsteps drive the floor at something near its own frequency and the response builds. This is the mechanism behind almost every complaint about a bouncy floor, and it has nothing to do with strength.

Adding MASS is the counter-intuitive fix that often works: it lowers the frequency, which sounds wrong, but it also reduces the amplitude the same footfall produces. Adding stiffness works by moving the frequency above the driving harmonics. Which of the two is right depends on where the floor currently sits, and a frequency estimate on its own does not say — modern assessment methods compute the RESPONSE, in acceleration, against what people actually notice.

The calculators here estimate a fundamental frequency, which is the screening step. A floor comfortably above the walking harmonics needs no more; one near them needs a response calculation rather than a reassurance.

## Camber hides deflection; it does not remove it

CAMBER is a deliberate upward curvature built into a member so that, once the dead load is on, it settles to level. It is a cosmetic and functional device — it protects drainage falls and stops a soffit looking sagged — and it adds no stiffness whatsoever. The member deflects exactly as much as it would have; it simply starts higher.

Because it is set against a PREDICTED dead load, camber is wrong whenever that prediction is. A beam cambered for a slab that turns out thinner finishes humped, and an excessively cambered member is a genuine problem for floor flatness that cannot be fixed by adding load. Common practice is therefore to camber for a proportion of the dead load rather than all of it, and to leave short members uncambered.

[Trusses](https://craftquantities.com/glossary/roof-truss/) carry the same logic with an extra term: their deflection includes the take-up of the connections as well as the elastic deformation of the members, so a fabricated camber has to allow for both. This is one of the reasons a truss's deflection comes from the truss designer's own output rather than from a beam formula — the joints are part of the answer.

## Calculators that use this method

- [Cold-Formed Steel (CFS) C-Stud Deflection Checker Check a cold-formed steel stud's calculated lateral (wind) deflection against a code deflection limit.](https://craftquantities.com/calculators/materials-quantities/cfs-stud-deflection-calculator/)
- [Corrugated Metal Decking Span Deflection Checker Check corrugated steel deck deflection against a code limit, using your deck's own effective moment of inertia.](https://craftquantities.com/calculators/materials-quantities/corrugated-decking-deflection-calculator/)
- [Floor Beam Vibration Natural Frequency Calculator A floor beam's natural frequency and the walking paces that can resonate it, since a beam can meet every deflection ratio and still feel lively underfoot.](https://craftquantities.com/calculators/materials-quantities/floor-vibration-frequency-calculator/)
- [Glulam Beam Deflection Checker Check calculated glulam beam deflection against standard L/180 (roof) or L/360 (floor) code limits.](https://craftquantities.com/calculators/materials-quantities/glulam-beam-deflection-calculator/)
- [I-Joist Minimum Depth Selector Estimate a minimum I-joist depth from a span/depth ratio rule of thumb — a pre-check, not a substitute for manufacturer span tables.](https://craftquantities.com/calculators/materials-quantities/i-joist-minimum-depth-calculator/)
- [Roof/Floor Deflection Limit Calculator Calculate the allowable absolute deflection for a given span and code deflection ratio limit.](https://craftquantities.com/calculators/materials-quantities/roof-deflection-limit-calculator/)
- [Structural Steel Beam Camber Calculator Calculate recommended fabricated camber for a steel beam from its calculated dead-load deflection.](https://craftquantities.com/calculators/materials-quantities/steel-beam-camber-calculator/)
- [Truss Bottom Chord Deflection Calculator Check a truss bottom chord's calculated deflection (acting as a ceiling joist) against the standard L/240 ceiling limit.](https://craftquantities.com/calculators/materials-quantities/truss-bottom-chord-deflection-calculator/)
- [Wood Truss Camber Calculator Estimate the recommended manufactured upward camber for a wood truss from its calculated dead-load deflection.](https://craftquantities.com/calculators/materials-quantities/truss-camber-calculator/)

## Basis

- AISC 360 and the AISC Steel Construction Manual — serviceability provisions, camber practice and tolerances.
- AISC Design Guide 11, Vibrations of Steel-Framed Structural Systems Due to Human Activity. Response-based assessment rather than a frequency threshold alone.
- National Design Specification for Wood Construction (NDS), including the creep factor applied to the sustained portion of the load.
- ACI 318, Chapter 24 — immediate and time-dependent deflection, the long-term multiplier, and the minimum thickness tables that let deflection checks be waived.
- International Building Code Table 1604.3, deflection limits by member and by what it supports, with separate live-load and total-load columns.
- SCI P354 and the Concrete Centre's guidance on floor vibration, for the response-based methods referred to above.
- ASCE 7 and roof ponding provisions, for the stiffness requirement that exists to stop the load-deflection feedback described here.

**Cite this page**

## Other methods

- [Slenderness, Effective Length and the Ratio That Decides Buckling](https://craftquantities.com/methodology/slenderness-and-buckling/)
- [Scaffolds: Ties, Duty and Plank Spans](https://craftquantities.com/methodology/scaffold-ties-duty-and-planks/)
- [Temporary Works: Slings, Wind, Battering and Haul Cycles](https://craftquantities.com/methodology/temporary-works-and-site-safety/)
- [Snow, Uplift and the Roof's Load Path](https://craftquantities.com/methodology/roof-loads-and-the-load-path/)

[All methodology pages](https://craftquantities.com/methodology/)

---
Source: https://craftquantities.com/methodology/deflection-and-vibration/