# Controlling Legionella Risk: Turning a Written Assessment into Dated Actions

> The assessment is not a certificate. It is a list of dated actions with owners — a tail cut out, a cistern turned over, a flush timed in seconds.

Page: https://craftquantities.com/guides/how-to-control-legionella-risk/ (trade guide, Water supply). This is the page's Markdown copy; the HTML page is the canonical version.

Published 2026-08-31.

## A capped 22 mm tail behind a bath panel

Three-storey house, converted to four flats in 1989, cistern in the loft and a vented cylinder in each flat. The survey took two hours and the most important thing it found was 1.4 metres of 22 mm copper running behind a bath panel to a blank cap, left when a bidet came out in the nineties. Half a litre, in a bathroom warm most of the year, off a live branch, and no amount of running the taps in that flat moves a drop of it. Nobody had ever seen it, because nobody had taken the panel off.

That is what an assessment is for, and it is why the output of one is not a document. The document is the evidence; the output is a list — cut that tail back to the tee, lag the two cold draw-offs sharing a boxing with the flow to the towel rail, drop the cistern's float valve so the thing turns over, put the four shower hoses on a quarterly descale — with a cost, a trade, a date and a name against every line. A written assessment with no such list is an essay about a building.

What follows is the inspection, the decisions it forces, and the arithmetic behind three of them that people usually guess at: how much water is really standing in a dead leg, how long a flush has to run, and how fast a return loop has to move to hold the temperature the guidance demands. It stops at the plant room door in two directions — designing and balancing a recirculation loop is a job of its own, covered next door, and so is sizing a cylinder for a peak hour, which is the argument this guide is on the other side of.

## The duty is already yours, and the certificate does not exist

Nothing in law is called a legionella certificate, and any company selling one is selling a report with a decorative cover. The duties are ordinary health and safety duties. Section 3 of the Health and Safety at Work etc. Act 1974 makes an employer or self-employed person responsible for people who are not their employees but are affected by their undertaking, which is the hook that catches a landlord; the Control of Substances Hazardous to Health Regulations 2002 then require a suitable and sufficient assessment under regulation 6 and control measures under regulation 7.

The detail sits in the HSE's Approved Code of Practice L8, with the practical schedules in HSG274 Part 2 for hot and cold water systems. An ACOP carries a specific legal weight worth understanding: following it is not compulsory, but where a duty holder is prosecuted and shown not to have followed it, the court will find against them unless they can demonstrate they complied some other equally effective way. That makes HSG274's schedules the default, and any departure something you write down and justify rather than something you simply do.

For a single let house with a combi, a cold main and no storage, the honest assessment is short, the risk is low and the HSE says so — but it still has to be done, recorded and reviewed. Proportionality cuts the other way too: an HMO with a loft cistern, a care home with TMV3 valves under BS 7942, or anything with a loop and a plant room is not a fifteen-minute job, and whoever does it has to be competent in the sense the ACOP uses — able to identify the hazards in this system, not merely holding a training certificate. BS 8580-1 is the code of practice for how the assessment is carried out.

American readers are doing the same work under a different noun. ASHRAE Standard 188 requires a water management program built by a designated team rather than a risk assessment, ASHRAE Guideline 12 carries the supporting practice, and the CDC's toolkit walks a building through the same elements. The vocabulary differs and the temperatures are in Fahrenheit; the substance is identical. Describe the system, find where water sits still or sits warm, decide the control, set the limit, measure it, and record what you did when the limit was missed.

## Walking the system before writing a word of it

The deliverable of the first visit is a schematic and an asset list, and the schematic is worth more than the prose that comes after it. It does not need to be pretty; it needs every source, vessel, branch and outlet on it, with the dead ends drawn in rather than tidied away. A drawing that omits the capped tail is worse than no drawing, because the next assessor will believe it.

Take the temperatures on the same walk, with the same thermometer, and write down where the probe was: a surface reading on a lagged pipe and a reading in the flowing stream at an outlet are different measurements, and a log that mixes them cannot be compared with next year's. Note what you could not reach as well — a cistern with no safe access, valves above a fixed ceiling, a riser boxed in behind tiling. Those become actions too, because a control you cannot verify is not a control.

1. Start at the incoming main: stop tap, meter, and any filter, softener or backflow device before the first draw-off.
2. Follow the cold side to storage. Lift every cistern lid, look for light ingress, insects and debris, and read the temperature near the outlet rather than at the surface.
3. Record what fills that cistern, what it feeds, and roughly how much leaves it in a day.
4. Read the heat source data plate — volume, input rating, set point — then the actual store temperature at the thermostat pocket and, if there is a drain, at the base.
5. Trace the hot distribution to the furthest outlet, noting every branch, every unlagged run and every place a cold pipe shares a void with a hot one.
6. Open every outlet in turn, time how long the hot takes to arrive and the cold takes to fall, and note anything that never gets there.
7. Take the panels off. Baths, shower trays, boxed risers, airing cupboards and the backs of vanity units are where dead legs live.
8. List what is out of use: a spare bathroom, a wing shut for refurbishment, an outside tap capped for winter, a washing machine valve nobody has opened in years.

## Dead legs, dead ends, and the litres actually standing in them

The two words get used interchangeably on site and they lead to opposite actions. A dead leg serves a real outlet used only occasionally — the guest en-suite, the cleaner's sink, the outside tap — so water moves through it when somebody opens the tap and it can be managed by flushing. A dead end goes nowhere: a capped tail, a redundant branch left live at the tee, a riser that once fed a floor since converted. Nothing you do at any outlet moves the water in it, ever. Flushing a system does not touch its dead ends, and a schedule that claims otherwise is describing something that cannot happen.

So the first thing to write against each one is a volume, because the volume decides whether it is a nuisance or a reservoir. The table gives the standing litres per metre for the bores that actually turn up and what a two metre run of each holds; the right-hand column is the other number the assessment needs, the seconds a tap has to run to displace three branch volumes at a modest six litres a minute.

The priorities then sort themselves. That 1.4 metre dead end in 22 mm copper holds 0.45 litres; the same tail in 15 mm plastic holds 0.15. Both should go, but with one plumber and one day they are not the same problem. The flushing column is why a weekly flush is so often done badly: nineteen seconds on a 22 mm branch is a different instruction from the two-second habit of opening a tap and shutting it, and unless the duration is written down the person doing it will do the habit.

There is a trap in adopting flushing as the answer at all. It is a recognised control and the right interim measure while a tail waits for a plumber, but it depends on somebody doing a thing every week for the life of the building and it fails silently the first week nobody does. Removal does not fail. Where the choice is between cutting out four dead ends on one visit and writing a weekly regime into a schedule somebody will inherit, cut them out — and keep flushing for the outlets that genuinely exist and are genuinely little used.

**Standing water in a branch, by bore. Volume per metre is the pipe's own capacity; the flush column is the time at 6 L/min to pass three branch volumes, which is the usual basis for a timed flush of a little-used outlet.**

| Branch pipe | Bore | Litres per metre | Held in a 2 m branch | Flush at 6 L/min |
|---|---|---|---|---|
| 15 mm plastic barrier pipe | 11.5 mm | 0.104 L | 0.21 L | 6 seconds |
| 15 mm copper | 13.6 mm | 0.145 L | 0.29 L | 9 seconds |
| 22 mm copper | 20.2 mm | 0.320 L | 0.64 L | 19 seconds |
| 28 mm copper | 26.2 mm | 0.539 L | 1.08 L | 32 seconds |
| 35 mm copper | 32.6 mm | 0.835 L | 1.67 L | 50 seconds |

Put in the real bore and the measured length of the branch you are standing in front of, and the standing volume comes out — which is the figure that decides whether it goes on the removal list or the flushing schedule, and how long the flush has to run if it is the latter. The page runs [Pipe Volume Calculator](https://craftquantities.com/calculators/plumbing-hvac/pipe-volume-calculator/) here.

## The branch that is one size too generous

Oversized pipework is a legionella finding, and one that almost never gets written down because the instinct on site runs the other way: a bigger pipe is a kinder pipe, it will never be the thing that starves an outlet, and going up a size costs little at first fix. What it buys is residence time. The same daily draw through a bore one size larger sits in the building for longer, wets more surface per litre delivered, and loses whatever temperature it was holding over a longer transit — and on the cold side it is more pipe to keep below twenty degrees.

The way to put a number on it is to size the branch for the load it actually carries and then compare that with what is on the wall. Take the fixture units for the one small outlet at the end of it, hold the velocity at the usual ceiling, and the minimum bore that comes back sits comfortably inside 15 mm copper. Running 22 mm to the same outlet does not change what it delivers; it holds 0.320 litres a metre instead of 0.145, a factor of 2.2, and turns a nine-second flush into a nineteen-second one for the rest of the building's life. Treat the calculator's answer as a floor rather than a specification — it knows nothing about the pressure you need at the outlet or the friction on the way there, and on a long run those govern — but the ratio between the two bores does not depend on any of that.

You will rarely re-pipe a building over this. You note it, and let it change three smaller decisions: that branch gets the longer flush, it is a candidate for shortening whenever the wall is open anyway, and it moves up the list if a point-of-use heater or a re-route is ever on the table. In a refurbishment it is the cheapest control there is, because specifying the smaller bore costs nothing and cannot be retrofitted afterwards without a wall coming down.

Enter the fixture units for what this one branch actually serves and read the minimum bore at a sensible velocity. It sizes on flow alone and knows nothing about your pressure, so treat the answer as a floor — but a floor a whole size below the pipe that got installed is a residence-time finding worth recording. The page runs [Domestic Water Pipe Sizing by Fixture Unit Calculator](https://craftquantities.com/calculators/materials-quantities/domestic-water-pipe-sizing-calculator/) here.

## Twenty degrees, and the cistern that has not emptied since March

The cold side has one number in HSG274 Part 2 and it is easy to test: below 20 °C at the outlet after running for up to two minutes. Almost every failure of it is a heat gain you can point at — a loft cistern reaching thirty degrees in July, a cold draw-off boxed in beside a hot flow, a long horizontal run above a heated ceiling, a cold pipe clipped to a hot one all the way up a riser because that was tidier. None is a plumbing fault in any ordinary sense, and all are findings with cheap actions.

Then the cistern itself, where the control is turnover rather than temperature. A tank holding more than the building draws in a day stores water that gets older every day, and one oversized for a household that has since halved is worse. Take the volume, take the daily cold draw, divide: 230 litres of storage against 300 litres a day is a residence time under a day, which is what the traditional sizing was aiming at. The same cistern serving a single occupant drawing 90 litres holds water for two and a half days — in a loft, in summer.

The remedies are ordinary. Drop the float valve so the working volume matches the draw. Replace an oversized tank with a smaller one, or two in series so both turn over rather than one becoming a sump. Move the outlet away from the inlet so the tank does not short-circuit across one corner while the rest stagnates. Insulate it, and get a lid on it: Schedule 2 of the Water Supply (Water Fittings) Regulations 1999 requires cisterns to be covered against contamination with screened vents and warning pipes, and an open cistern in a loft is a Regulations breach before it is anything else.

One cold-side finding gets missed almost every time. Anything sitting in the flow that holds water belongs on the list — a base-exchange softener's resin bed, a filter housing, a sampling point with a hose left on it, a potable-side expansion vessel with a diaphragm and no flow through it. HSG274 Part 2 covers these, and the answer is usually the same: give it flow, service it on a schedule, or take it out if it is no longer doing anything.

## Sixty in the cylinder, and the argument about how big it should be

On the hot side the schedule is 60 °C stored and 50 °C or above distributed, with 55 °C in healthcare premises following HTM 04-01. Those are HSG274 Part 2's figures, and they are why a hot water system is designed to scald and then protected at the outlet by a mixing valve rather than run comfortable throughout. The store temperature is a control, not a setting, and turning it down to save energy is a change to the risk assessment.

Which is the collision worth naming, because it is now common rather than theoretical. A heat pump cylinder is usually run at 50 to 55 °C, since the coefficient of performance falls away above that, with a scheduled pasteurisation cycle taking the store up periodically. That can be perfectly defensible — but it is a departure from the ACOP's default, so it goes into the assessment with the cycle's temperature, duration and frequency stated, and someone verifies it actually happens. A heat pump retrofit nobody told the responsible person about is the commonest way a compliant building quietly stops being one.

Volume is the other half, and here this guide argues in the opposite direction to everything else on the site. Sizing for the peak hour pushes storage up; residence time pushes it down, because a store taking three days to turn over is three days of water at whatever temperature the base of the cylinder is actually holding. Both are correct, and the resolution is not a compromise number but knowing which constraint binds in this building. A 300 litre cylinder serving two people is not a generous system, it is a slow one.

The calculator below is a household-size bracket in US gallons and nothing more. Use it for one thing: to get a defensible range on the page and hold the installed volume against it. A cylinder well above the bracket for the people actually living there is the finding, and the actions are a smaller vessel at replacement and a note that the base of the cylinder needs measuring rather than assuming — a thermostat reading 60 °C near the top says very little about the coldest fifth of the store, which is where the sediment is.

Take the bracket for the household that lives there now, not the one the cylinder was bought for, and compare it with the litres on the data plate. A store well above the bracket is a residence-time finding, and it is the one nobody writes down because a big cylinder feels like a good cylinder. The page runs [Water Heater Sizing Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-heater-sizing-calculator/) here.

## Fifty at the outlet in a minute, which is a flow rate in disguise

The distribution criterion is that hot water reaches 50 °C at the outlet within one minute of opening it. In a small dwelling that is a question about the length of the run. On anything with a circulating loop it is a question about flow in the return, and what differs from ordinary design work is that the temperature drop is not yours to choose: guidance puts 60 °C at the calorifier flow and not below 50 °C at the return, so the whole loop has 10 K to spend and the flow becomes an output of that ceiling rather than a comfort preference. Design tighter than that if you want margin — but 10 K is the number the assessment is judged against, and a scheme that commits to less has to be able to show it achieves it.

Which makes the calculation a compliance check. Take the loop's total heat loss — from the insulation schedule and the developed length, not from a guess — put the drop in at the figure the assessment commits to, and the required circulation rate falls out. Compare it with what the pump is actually doing. A loop whose measured return sits at 44 °C is either losing more heat than the schedule says or moving less water than the duty point promises, and the two are told apart by measuring the flow, not by turning the pump up.

When the answer comes out absurd it is telling you something real. A required flow far above what the return bore can carry at a sane velocity means the loop cannot be held at temperature at any pump speed, and the fix is insulation, a shorter loop or a second loop — never a bigger circulator, which buys a few degrees and then erodes the return. How the loop is balanced so every riser sees its share, and what control strategy is defensible when the assessment requires the distribution held hot, is a design job covered next door; what belongs here is the figure the assessment commits to and the monthly reading that proves it.

Enter the loop's heat loss and put the allowable drop in at what the guidance leaves you rather than at what would be comfortable. The flow that comes out is the minimum the pump has to deliver for the return temperature in your written scheme to be achievable at all. The page runs [Domestic Hot Water Recirculation Flow Calculator](https://craftquantities.com/calculators/materials-quantities/dhw-recirculation-flow-calculator/) here.

## The schedule the assessment writes, and who signs it

The written scheme is the half of the assessment that lives on after the survey: what gets checked, how often, against what limit, and what happens when the limit is missed. The table sets out its shape for a hot and cold water system following HSG274 Part 2. Take the definitive list and frequencies from the document itself and adjust them to what your own assessment found — a building with a known temperature problem gets checked more often, not less, and healthcare premises work to HTM 04-01 with its own regime.

Two things kill a scheme and neither is technical. The first is the log filled in at a desk: a column of identical round numbers, all taken on the first of the month, is not evidence of control and it is the first thing an investigator notices. Give the person doing it a thermometer that logs, or accept a shorter list of checks genuinely done. The second is the change of contractor. Schemes are inherited, the frequencies survive while the reasons for them do not, and the new firm quietly rationalises the odd-looking items — usually the ones your assessment added for a building-specific reason. Write the reason next to the frequency and it survives.

**The shape of a written scheme for a hot and cold water system, following HSG274 Part 2. Frequencies are the guidance's defaults for a typical system and are adjusted by the building's own assessment.**

| What is checked | How often | What the reading has to show |
|---|---|---|
| Hot sentinel outlets, nearest and furthest from the calorifier | Monthly | 50 °C or above within one minute of running |
| Cold sentinel outlets, nearest to and furthest from the source | Monthly | Below 20 °C within two minutes of running |
| Calorifier flow and return temperatures | Monthly | 60 °C leaving, not below 50 °C returning |
| Other outlets on a rotating sample | Through the year, so all are covered | Same limits as the sentinels |
| Little-used outlets | Weekly | Flushed for the duration recorded against that outlet |
| Showerheads and hoses | Quarterly | Dismantled, cleaned, descaled and disinfected |
| Thermostatic mixing valves | Annually, or as the assessment sets | Blend temperature and fail-safe verified; strainers cleaned |
| Cold water storage cistern | Annually | Lid, screens and insulation intact; water clean; temperature and turnover acceptable |
| Calorifier internals and drain-off | Annually | Inspected where accessible; drained to check for debris and scale |

## Bringing a void property back, and the reheat nobody schedules

A property that has stood empty is the sharpest version of this whole subject, and every landlord and facilities manager now has recent experience of it. Between tenancies, over a refurbishment, or across a wing taken out of use, the system does not merely sit still: the cold side warms to room temperature, the hot side cools through the growth range, and the first person to open a shower makes an aerosol out of it. The assessment has to say what happens before that person arrives.

The order matters. Bring the heat source up first and hold the store at temperature, because flushing while the cylinder is still at thirty degrees distributes the problem rather than removing it. Then run the outlets in sequence, furthest first, hot and cold, long enough to displace the branch volumes — with the head off the shower hose or the hose into a bucket, so the exercise does not aerosolise the water you are trying to get rid of. Where the void has been long, the system complex or the occupants vulnerable, the answer moves from flushing to disinfection.

Thermal disinfection is the procedure most buildings can actually carry out: HSG274 Part 2 sets it out as raising the calorifier to 70 °C or above, holding it, then running each outlet in turn for at least five minutes at not less than 60 °C. The arithmetic is what gets underestimated. A 210 litre cylinder taken from a cold fill at 8 °C to 70 °C needs about 15 kWh into the water — an hour at best on a 15 kW coil, and over five hours on a 3 kW immersion, before a single outlet has been opened and with every outlet then drawing off the store you just heated. Thirty outlets is a day planned around the reheat, not an afternoon.

The chemical route is a contractor's job. BS 8558 sets out the chlorination procedure and HSG274 Part 2 covers the alternatives — chlorine dioxide, silver-copper ionisation and the rest — each of which has to hold an approval position for use in a drinking water system under Regulation 31 of the Water Supply (Water Quality) Regulations 2016. Whichever route is taken, be clear about what it achieved. A disinfection resets the system; it does not control it. If the dead end is still behind the bath panel and the cistern still turns over in three days, the count comes back and the next disinfection is on the calendar rather than in the plan.

Put the cylinder's volume, the winter cold feed, the disinfection target and the real input at the coil or element in, and you get the length of the window you have to book. Its 0.75 recovery efficiency is a flued-gas assumption, so read the answer as an upper bound for an immersion element and plan the day around it. The page runs [Water Heater Recovery Time Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-heater-recovery-time-calculator/) here.

## Sampling, and what a clear result is worth

Sampling is not the default. Where the strategy is temperature control and the temperatures are being achieved and recorded, HSG274 Part 2 does not call for routine legionella sampling in a hot and cold water system — the log is the evidence. Sampling comes in for specific reasons: control by biocide rather than temperature, temperatures not being achieved, premises housing especially susceptible people, or a case associated with the building. When it is done, BS 7592 governs how the sample is taken and ISO 11731 how it is enumerated, by an accredited laboratory.

Then be clear-eyed about the answer. A clear result says that on that day, at that tap, in that volume, nothing was detected. It says nothing about the flat above, the cistern in the loft, or next Tuesday, and it is no defence for a system whose temperatures have not been held. Duty holders have been badly served by an annual sample sold as a substitute for a regime, because the sample is cheap and the regime is not. A detection is equally information rather than a verdict: it triggers the assessment's own actions and a review, and the useful question is which control failed.

What the file holds, in the end, is small and unglamorous. The assessment, dated and signed. The schematic. The written scheme, with the reason beside each frequency. The logs, in the handwriting of whoever took them. Every action closed out with a date — the tail removed, the lagging fitted, the float valve dropped. And a review whenever something changes: a heat pump, a wing closed, a bathroom added, an occupancy gone from four people to one. COSHH requires review when there is reason to believe the assessment is no longer valid, and a building that has changed against an assessment that has not is exactly that.

## What to have on paper before the first action is priced

The survey produces a schematic and a list. These are the items that turn the list into instructions a plumber, a caretaker or a contractor can act on without going back to the building.

- **A schematic with the dead ends drawn in**: Every source, vessel, branch and outlet, including the ones behind panels. Tidying a capped tail off the drawing is how it survives the next twenty years.
- **Standing volume against every dead leg and dead end**: Bore and measured length, converted to litres. It is what separates the removal list from the flushing schedule and ranks the removals against each other.
- **A flush duration in seconds for each little-used outlet**: Written on the schedule beside the outlet, not left as the word 'flush'. Nineteen seconds and two seconds are different instructions and only one of them works.
- **Cistern volume against the actual daily cold draw**: The ratio is the residence time. A tank sized for a household that has since halved is storing water for days in a warm loft.
- **Store temperature at the thermostat and at the base**: Plus the set point, the volume from the data plate, and — where it is a heat pump — the pasteurisation cycle's temperature, duration and frequency.
- **Loop heat loss and the measured return temperature**: The two together say whether the return is failing on insulation or on flow, which are different jobs with different costs.
- **The list of what you could not reach**: Cisterns without safe access, valves above fixed ceilings, boxed risers. Providing access is an action in its own right, because an unverifiable control is not one.

Calculators for these quantities: [Domestic Water Pipe Sizing by Fixture Unit Calculator](https://craftquantities.com/calculators/materials-quantities/domestic-water-pipe-sizing-calculator/), [Pipe Volume Calculator](https://craftquantities.com/calculators/plumbing-hvac/pipe-volume-calculator/), [Water Heater Sizing Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-heater-sizing-calculator/), [Water Heater Recovery Time Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-heater-recovery-time-calculator/), [Domestic Hot Water Recirculation Flow Calculator](https://craftquantities.com/calculators/materials-quantities/dhw-recirculation-flow-calculator/).

## Calculators this guide uses

- [Pipe Volume Calculator](https://craftquantities.com/calculators/plumbing-hvac/pipe-volume-calculator/)
- [Domestic Water Pipe Sizing by Fixture Unit Calculator](https://craftquantities.com/calculators/materials-quantities/domestic-water-pipe-sizing-calculator/)
- [Water Heater Sizing Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-heater-sizing-calculator/)
- [Domestic Hot Water Recirculation Flow Calculator](https://craftquantities.com/calculators/materials-quantities/dhw-recirculation-flow-calculator/)
- [Water Heater Recovery Time Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-heater-recovery-time-calculator/)
- [Pipe Insulation Calculator](https://craftquantities.com/calculators/insulation-efficiency/pipe-insulation-calculator/)
- [Tankless Water Heater Sizing Calculator](https://craftquantities.com/calculators/plumbing-hvac/tankless-water-heater-calculator/)
- [Water Softener Sizing Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-softener-sizing-calculator/)
- [Backflow Preventer Discharge Velocity Calculator](https://craftquantities.com/calculators/materials-quantities/backflow-preventer-velocity-calculator/)
- [Temperature Conversion Calculator](https://craftquantities.com/calculators/measurements-conversions/temperature-conversion-calculator/)

## See also

- [Recirculating Domestic Hot Water](https://craftquantities.com/guides/how-to-recirculate-domestic-hot-water/)
- [Sizing Domestic Hot Water](https://craftquantities.com/guides/how-to-size-a-water-heater/)
- [Matching a Shower to the Water Supply You Have](https://craftquantities.com/guides/how-to-choose-a-shower-for-your-water-supply/)
- [Sizing and Plumbing a Water Softener](https://craftquantities.com/guides/how-to-size-a-water-softener/)
- [Boosting a Weak Incoming Water Supply](https://craftquantities.com/guides/how-to-boost-a-weak-water-supply/)

## Sources

- Health and Safety at Work etc. Act 1974, sections 2 and 3
- The Control of Substances Hazardous to Health Regulations 2002 (SI 2002/2677), regulations 6 and 7
- HSE Approved Code of Practice and guidance L8, Legionnaires' disease: The control of legionella bacteria in water systems
- HSE HSG274 Part 2, Legionnaires' disease: The control of legionella bacteria in hot and cold water systems, and HSG274 Part 3 for other risk systems
- BS 8580-1, Water quality — Risk assessments for Legionella control — Code of practice
- BS 8558, Guide to the design, installation, testing and maintenance of services supplying water for domestic use within buildings and their curtilages
- BS EN 806-5, Specifications for installations inside buildings conveying water for human consumption — Operation and maintenance
- The Water Supply (Water Fittings) Regulations 1999 (SI 1999/1148), Schedule 2, with the equivalent Scottish Byelaws and Northern Ireland Regulations
- The Water Supply (Water Quality) Regulations 2016, Regulation 31, on the approval of substances and products in contact with water intended for human consumption
- Approved Document G, Sanitation, hot water safety and water efficiency (England), requirement G3
- BS 7942, Thermostatic mixing valves for use in care establishments (Types 3 and 3H) — Requirements and test methods
- Health Technical Memorandum 04-01, Safe water in healthcare premises
- BS 7592, Sampling for Legionella bacteria in water systems — Code of practice
- BS EN ISO 11731, Water quality — Enumeration of Legionella
- ASHRAE Standard 188, Legionellosis: Risk Management for Building Water Systems, and ASHRAE Guideline 12, Managing the Risk of Legionellosis Associated with Building Water Systems
- US Centers for Disease Control and Prevention, Toolkit for developing a water management program to reduce Legionella growth and spread in buildings
- World Health Organization, Legionella and the prevention of legionellosis
- The cylinder, mixing valve and circulator manufacturer's own installation and servicing literature for the specific models installed — set points, pasteurisation cycle behaviour and service intervals are model-specific and are taken from that document rather than from a general rule

---