# Attic ventilation for a 12 by 8 m bungalow in Canada, at the National Building Code's 1/300

> A 12 x 8 m Canadian bungalow attic, worked with the attic ventilation calculator at the NBC's 1/300: the area, the split and the vents.

Page: https://craftquantities.com/examples/calculators/attic-ventilation-12-x-8-m-canadian-bungalow/ (worked example). This is the page's Markdown copy; the HTML page is the canonical version.

A bungalow attic of 96 m² (1,033.3 sq ft) over an insulated ceiling needs 0.32 m² (3.44 sq ft (net free area)) of open vent area at the National Building Code's 1/300. Here is how that area divides between the eaves and the ridge, and how it becomes a length of vent to fit.

- 0.32 m² The answer
- 5 Steps shown
- Canada, metric first Written for

On this page

Run it yourself

[Open these inputs in the Attic and Loft Ventilation Calculator (Intake, Exhaust and Vent Count)](https://craftquantities.com/calculators/insulation-efficiency/attic-ventilation-calculator/#atticLength=12&atticWidth=8&hasVaporBarrier=nbc&intakeVent=soffit&exhaustVent=ridge)

## The job

Modelled, not recorded. Every figure here is the answer the Attic and Loft Ventilation Calculator (Intake, Exhaust and Vent Count) gives for these inputs, written down in both unit systems and re-run whenever the site is built. No job was carried out, so there is no measured overrun on this page.

The house is a single-storey bungalow with a gable roof, a plan found street after street in Canadian suburbs and a common candidate for a deeper layer of insulation. Its attic is 12 m along the ridge and 8 m from eaves to eaves, the insulation lies on the ceiling joists, and the space above it is cold in winter. That cold space is what the ventilation serves: it carries away moisture that gets past the ceiling before it condenses on the underside of the roof sheathing.

Canada's rule is a ratio, like the American one, but it is simpler to apply. Article 9.19.1.2 of the National Building Code asks for vent area of at least 1/300 of the insulated ceiling, spread on opposite sides with at least a quarter at the top and a quarter at the bottom. There is no vapour-retarder exception to qualify for, because the NBC already expects a vapour barrier on the warm side; the ratio only doubles where the roof is shallow or built with roof joists, and that case is shown below.

The rule is the one a Canadian reader's page opens on, and it is named here as the reader's reference. Each province and territory adopts the NBC in its own way, sometimes with changes, and the building official where the house stands decides; this page works the arithmetic and certifies nothing. The two vents counted are the calculator's listed soffit and ridge products, used as examples. A Canadian building supply may stock others, and the count changes with the net free area printed on whichever label is bought.

[Open this job in the calculator](https://craftquantities.com/calculators/insulation-efficiency/attic-ventilation-calculator/#atticLength=12&atticWidth=8&hasVaporBarrier=nbc&intakeVent=soffit&exhaustVent=ridge)

[Embed this calculator on your own page](https://craftquantities.com/embeds/#calculator=attic-ventilation-calculator)

Every figure is worked again by the real calculators, in both unit systems; nothing is priced and nothing is saved until you press Use as my project.

## The inputs, exactly as entered

**Every input the calculator takes for this job, and why it is what it is**

| Input | Value | Why |
|---|---|---|
| Attic or Loft Length (along the ridge) | 12 m (39.37 ft) | Left at the calculator's own default. |
| Attic or Loft Width (the span, eaves to eaves) | 8 m (26.25 ft) | The span from the outside of one wall plate to the other, taken on the ceiling below rather than along the slope of the roof, because the NBC takes its ratio on the insulated ceiling. |
| Rule | NBC 9.19.1.2: 1/300 of the insulated ceiling (Canada) | The National Building Code's ordinary ratio, the rule a Canadian reader's page opens on: it applies to a roof of ordinary slope framed with rafters or trusses. |
| Intake Vent (eaves or soffit) | Lomanco 140 soffit vent, 88 sq in per 8 ft length | Left at the calculator's own default. |
| Exhaust Vent (ridge or upper) | GAF Cobra RidgeRunner ridge vent, 12.5 sq in per foot | Left at the calculator's own default. |

## The working, step by step

1. ### 1. Attic floor area

   96 m² (1,033.3 sq ft)

   The length and the span multiply to the insulated ceiling, 96 m² (1,033.3 sq ft). The NBC's ratio is taken on this area and not on the roof's sloping surface, which is larger; measuring the roof by mistake overstates the vents in proportion to the pitch.
2. ### 2. Net free area needed

   320,000 mm² (496 in²)

   One three-hundredth of that ceiling is the open area the vents must add up to: 320,000 mm² (496 in²). Net free area is the gap air actually passes through once the louvres, mesh and baffles of a vent are allowed for, which is always less than the size of the hole, so this figure is compared with the net figure printed on a vent's label and never with its outside dimensions.
3. ### 3. Exhaust, high on the roof (ridge or upper vents)

   160,000 mm² (248 in²)

   The calculator splits the area evenly between top and bottom, which satisfies the code's quarter-at-each-end floor with room to spare: half the total, 160,000 mm² (248 in²), is placed high on the roof at the ridge. Spread along the ridge it is the same as a continuous slot of 13.33 mm, a useful picture when comparing a ridge vent with a row of box vents.
4. ### 4. Intake, low on the roof (eaves or soffit)

   185,206 mm² (287.1 in²)

   The intake at the soffits is kept at least equal to the exhaust actually bought, never only to half the requirement, so that the roof draws air in low rather than pulling it out of the house: 185,206 mm² (287.1 in²). Because the ridge vent comes in whole pieces, it supplies a little more than its half, and the intake grows to match it.
5. ### 5. Intake vent to fit

   8 m (26.25 ft)

   Dividing each area by the rated area of one piece of the chosen product gives what to fit: 8 m (26.25 ft) of soffit vent along the eaves and 7 m (22.97 ft) of ridge vent. Those lengths are shorter than the eaves and the ridge, which is normal; what matters is that the soffit vents are not blocked by insulation, which is what baffles at each rafter bay are for.

Net free vent area needed

0.32 m²

3.44 sq ft (net free area)

The answer to carry to the supplier is the pair of lengths, 8 m of intake and 7 m of exhaust, for these two products; the area behind them, 0.32 m² (3.44 sq ft (net free area)), is the figure to check any other product against. The calculator rates its confidence as medium because the result leans on two assumptions it cannot see: that the roof is of ordinary slope, and that every soffit vent will be left open to the attic once the insulation is blown in.

## What to buy

**The quantities this job comes to, and what each is for**

| Quantity | Figure | What it is for |
|---|---|---|
| Net free vent area needed | 0.32 m² (3.44 sq ft (net free area)) | The total net free area, the figure to hold any vent against: add up the label ratings of what is fitted until they reach it. |
| Intake vent to fit | 8 m (26.25 ft) | Soffit vent for the eaves, as a length of the listed product; with another product, divide the intake area by its own rating. |
| Exhaust vent to fit | 7 m (22.97 ft) | Ridge vent for the top of the roof, as a length of the listed product, cut to fit between the gable ends. |

## The allowance, and what it does here

The calculator adds no allowance to the area, and none is wanted: the code gives a minimum, and the count already rounds up to whole pieces of vent, which is why the vents bought supply a little more than the requirement. Where an allowance is earned is in the fitting. Soffit vents sold in lengths are cut at corners and around downspout brackets, and a ridge vent stops short of each gable, so buy the lengths as counted and keep the offcuts, rather than adding a percentage to an area that is already a minimum.

## The common mistake

### Covering the soffit vents with the new insulation

The most common way a correctly sized system fails is during the insulation job that prompted the question. Blown cellulose or fibreglass is poured to depth across the ceiling, it drifts into the eaves, and it buries the soffit vents from the inside. The ridge vent then has nothing to draw from except the house, which pulls warm, moist air up through every gap in the ceiling, the exact opposite of what the vents are for. Fit a baffle in every rafter bay at the eaves before the insulation goes in, so a clear channel stays open over the top plate, and count the soffit vents as working only if air can reach them.

## Change the job, and see what moves

- ### The same attic under a roof below a one-in-six slope

  Rule: NBC 9.19.1.2: 1/150 below a 1 in 6 slope or with roof joists (Canada) → 0.64 m² (6.89 sq ft (net free area))

  Under a roof shallower than the NBC's one-in-six slope, or one built with roof joists, the ratio doubles to 1/150 and the same ceiling needs 0.64 m². The vents follow: 14 m at the soffits and 13 m at the ridge. A shallow roof has less height for air to rise through, which is why it asks for more opening.
- ### A shorter bungalow of the same span

  Attic or Loft Length (along the ridge): 10 m (32.81 ft) → 0.267 m² (2.87 sq ft (net free area))

  Shorten the bungalow to 10 m along the ridge and the ceiling falls to 80 m², so the requirement falls with it, to 0.267 m². The ratio does not change with size: the area moves in direct proportion to the ceiling, and only the rounding to whole pieces of vent keeps the lengths from following it exactly.

## What to run next

- [Attic Rafter Baffle/Chute Count Calculator](https://craftquantities.com/calculators/materials-quantities/attic-baffle-count-calculator/)

  Every rafter bay with a soffit vent beneath it needs a baffle to keep the insulation off the vent, and the count follows from the eaves length and the rafter spacing.
- [Attic Insulation Upgrade Calculator](https://craftquantities.com/calculators/insulation-efficiency/attic-insulation-upgrade-calculator/)

  The ventilation question usually comes with a top-up of the insulation, which is counted by the depth to reach over the same ceiling.
- [Ridge Vent Linear Footage Calculator](https://craftquantities.com/calculators/materials-quantities/ridge-vent-linear-footage-calculator/)

  A ridge vent is cut to the ridge less a stop at each end; that calculator measures it for a hip or gable roof of any shape.

## Sources

The method and every constant behind these figures belong to the [Attic and Loft Ventilation Calculator (Intake, Exhaust and Vent Count)](https://craftquantities.com/calculators/insulation-efficiency/attic-ventilation-calculator/), version 1.1.0, last verified 2026-10-05. It rests on:

- International Code Council, 2021 International Residential Code, as adopted without amendment in the Colorado Division of Fire Prevention and Control Residential Code 2021: R806.2, net free ventilating area 1/150 of the vented space; exception, 1/300 where both conditions are met: a Class I or II vapor retarder on the warm-in-winter side of the ceiling in climate zones 6, 7 and 8, and 40 to 50 percent of the required area in ventilators in the upper portion of the attic or rafter space
- Residential Code of Ohio, Ohio Adm. Code 4101:8-8-01 (effective 1 July 2019), sections 806.1–806.3 on the 2018 IRC text: upper ventilators not more than 3 ft (914 mm) below the ridge or highest point, measured vertically; the balance in the bottom one-third of the attic space; installation lower where framing conflicts; not less than 1 in (25 mm) between insulation and roof sheathing (Ohio deletes the exception's vapor-retarder condition)
- National Research Council of Canada, National Building Code of Canada 2020, Division B, 9.19.1.1–9.19.1.3: vent area not less than 1/300 of the insulated ceiling area, or 1/150 where the roof slope is less than 1 in 6 or the roof has roof joists; vents distributed uniformly on opposite sides, at least 25% at the top and at least 25% at the bottom of the space; 63 mm between insulation and sheathing
- Marley, 'How do I ventilate a cold roof?' (technical support guidance, citing BS 5250, Management of moisture in buildings): with a high-resistance underlay, 25 mm along the eaves for pitches of 15° or less, 10 mm for pitches above 15°, and 5 mm at high level where the pitch exceeds 35°, the span exceeds 10 m, or the roof is lean-to or mono-pitch; Wienerberger, 'Roof space ventilation' (2013): a continuous 10 mm gap gives 10,000 mm² per metre run, and the 5 mm high-level vent where a building is 10 metres wide or more or the pitch 35 degrees or above (the page takes this, the stricter reading at the boundaries). Approved Document C (2013) 6.10–6.11 refers roof condensation to BS 5250
- Vent ratings and the balance rule: GAF Cobra RidgeRunner data sheet RESCB171 (2020), 12.5 sq in per lineal foot (26,458 mm² per lineal metre), exhaust never to exceed intake, and the chart 1,600 sq ft to 31 ft with 388 sq in of intake; Lomanco 140 soffit vent product specification (2012), 88 sq in per 8 ft unit; Marley Ventilated Dry Ridge System, 5 mm continuous
- Marley, Universal 25mm Eaves Vent System: 25,000 mm² free area of ventilation per linear metre, for roof pitches of 12.5° to 55° (product page; Marley's NBS Source data, ventilation opening 25 000 mm²/m, 6000 mm packs; fixing instructions, December 2018, a continuous 25 mm free ventilation path, pack code 46351)
- Australian Building Codes Board, National Construction Code 2022 (as adopted), Housing Provisions 10.8.3, ventilation of roof spaces: in climate zones 6, 7 and 8, Table 10.8.3, under 10° pitch 25,000 mm²/m at each of two opposing ends; 10° to under 15°, 25,000 mm²/m at the eaves and 5,000 mm²/m at high level; 15° to under 75°, 7,000 mm²/m at the eaves and 5,000 mm²/m at high level, plus 18,000 mm²/m at the eaves for a cathedral ceiling; areas per metre of the roof's longest horizontal dimension; high level within 900 mm below the ridge; not for concrete roofs, structural insulated panels or BAL-FZ. Applied along both eaves as the Australian Steel Institute's 'Ventilation in Steel Roofing' (VSR V27, 2024) works the table for a gable or hipped roof

This job is one of that calculator’s published test vectors, which the test suite re-runs on every build.

## Frequently asked questions

**How much attic ventilation does a 12 by 8 m bungalow need in Canada?**

At the National Building Code's 1/300 of the insulated ceiling, 96 m² needs 0.32 m² (3.44 sq ft (net free area)) of net free vent area, which the calculator splits into 160,000 mm² high up and at least as much low down. The province's adoption of the NBC, and the building official, govern.

**When does the NBC ask for 1/150 instead of 1/300?**

Where the roof slopes less than one in six, or is built with roof joists rather than rafters or trusses. On this ceiling that would double the requirement to 0.64 m².

**Why is the soffit intake larger than the ridge exhaust?**

The calculator keeps the intake at least equal to the exhaust that is actually fitted, and the ridge vent is bought in whole pieces that supply slightly more than half the total. So the intake rises to 185,206 mm², which keeps the attic drawing air in at the eaves.

## More worked calculator examples

- [An L-shaped hip and valley roof, measured Roof Area of an L-Shaped House: Hips, Valleys, Squares](https://craftquantities.com/examples/calculators/roof-area-l-shaped-house-hip-and-valley/)
- [A semi's roof re-covered, in tiles and battens Roof Tiles for a 81 m² Re-roof: Tiles and Battens](https://craftquantities.com/examples/calculators/roof-tiles-81-m2-semi-recover/)
- [A low-pitch garage roof, in squares and bundles Shingles for a 24 x 24 ft Garage Roof](https://craftquantities.com/examples/calculators/shingles-24-x-24-ft-garage-roof/)
- [A gable roof, in squares and bundles Shingles for a 34 x 26 ft Roof: Squares and Bundles](https://craftquantities.com/examples/calculators/shingles-34-x-26-ft-roof/)

### Comparisons that weigh them

- [Compare: Ice Dam Membrane vs Attic Ventilation](https://craftquantities.com/compare/ice-dam-membrane-vs-attic-ventilation/)

- [Material hub: Roofing](https://craftquantities.com/materials/roofing/)
- [Guide: Insulating an Attic](https://craftquantities.com/guides/how-to-insulate-an-attic/)
- [Guide: Boarding a Loft Without Crushing the Insulation](https://craftquantities.com/guides/how-to-board-a-loft-over-insulation/)

---
Source: https://craftquantities.com/examples/calculators/attic-ventilation-12-x-8-m-canadian-bungalow/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.