# Construction Plant Noise at a Neighbour Calculator (BS 5228-1 / FHWA RCNM)

> Predict the noise up to three items of plant make at a neighbouring property, from each one's reference level, distance and on-time, and any screening.

Page: https://craftquantities.com/calculators/sustainability-compliance/construction-noise-at-receptor-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-09-21, 7 published test vectors.

Predicted level at the receptor, LAeq over the period: 70.7 dB(A) for Plant Item 1 Reference Level (dB(A)) 80, Plant Item 1 On-Time 75 and Plant Item 2 Reference Level (dB(A)) 78, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Reference Levels Are Given As | `basis` | Activity LAeq at 10 m (BS 5228-1 Annex C) | Activity LAeq at 10 m (BS 5228-1 Annex C) | `l10`, `lw`, `l50` |
| Plant Item 1 Reference Level (dB(A)) | `plantLevel1` | 80 | 80 | range 40–140 |
| Plant Item 1 Distance to the Receptor | `plantDistance1` | 30 m | 98 ft | mm, cm, m, in, ft, yd; range 1–2000 m |
| Plant Item 1 On-Time (%) | `plantOnTime1` | 75 | 75 | range 0–100 |
| Plant Item 2 Reference Level (dB(A)) | `plantLevel2` | 78 | 78 | range 40–140 |
| Plant Item 2 Distance to the Receptor | `plantDistance2` | 45 m | 150 ft | mm, cm, m, in, ft, yd; range 1–2000 m |
| Plant Item 2 On-Time (%) | `plantOnTime2` | 50 | 50 | range 0–100 |
| Plant Item 3 Reference Level (dB(A)) | `plantLevel3` | 84 | 84 | range 40–140 |
| Plant Item 3 Distance to the Receptor | `plantDistance3` | 60 m | 195 ft | mm, cm, m, in, ft, yd; range 1–2000 m |
| Plant Item 3 On-Time (%) | `plantOnTime3` | 25 | 25 | range 0–100 |
| Screening Between Plant and Receptor | `screening` | None — clear line of sight | None — clear line of sight | `none`, `partial`, `full` |

- **Reference Levels Are Given As**: Which kind of figure the plant's reference levels are.
- **Plant Item 1 Reference Level (dB(A))**: The item's level in the form the reference basis above asks for.
- **Plant Item 1 Distance to the Receptor**: Straight-line distance from the plant to the receptor.
- **Plant Item 1 On-Time (%)**: The share of the assessment period the plant is actually working — 0 leaves the item out.
- **Plant Item 2 Reference Level (dB(A))**: The item's level in the form the reference basis above asks for.
- **Plant Item 2 Distance to the Receptor**: Straight-line distance from the plant to the receptor.
- **Plant Item 2 On-Time (%)**: The share of the assessment period the plant is actually working — 0 leaves the item out.
- **Plant Item 3 Reference Level (dB(A))**: The item's level in the form the reference basis above asks for.
- **Plant Item 3 Distance to the Receptor**: Straight-line distance from the plant to the receptor.
- **Plant Item 3 On-Time (%)**: The share of the assessment period the plant is actually working — 0 leaves the item out.
- **Screening Between Plant and Receptor**: Whether a hoarding, bund or building stands between the plant and the receptor.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Predicted level at the receptor, LAeq over the period** | 70.7 dB(A) |
| Plant item 1 at the receptor | 69.21 dB(A) |
| Plant item 2 at the receptor | 61.93 dB(A) |
| Plant item 3 at the receptor | 62.42 dB(A) |
| Plant item 1's share of the total | 71.62 % |

### US customary

| Result | Value |
|---|---|
| **Predicted level at the receptor, LAeq over the period** | 70.7 dB(A) |
| Plant item 1 at the receptor | 69.25 dB(A) |
| Plant item 2 at the receptor | 61.79 dB(A) |
| Plant item 3 at the receptor | 62.5 dB(A) |
| Plant item 1's share of the total | 71.89 % |

## How it is worked out

70.7 dB(A) is the predicted LAeq over the period at the receptor from the items entered, over hard ground in neutral weather. Item 1 is most of it: on a logarithmic scale the loudest source decides the total, and moving or screening it changes the result far more than doing the same to the others.

The working the page shows, in order: Plant item 1 at the receptor; Plant item 2 at the receptor; Plant item 3 at the receptor; Plant item 1's share of the total; then predicted level at the receptor, LAeq over the period.

The method, derived in full:

- [Exposure at Work: Doses, Decibels and the Reference Day](https://craftquantities.com/methodology/exposure-at-work/): Why an hour at 94 dB(A) is a whole day at 85, why two countries' rules disagree about the same shift, why twice the vibration is four times the dose, and why a protector rated 30 dB takes off far less.

What this calculation does not cover:

- It is a free-field prediction over hard ground, the conservative case. Soft ground, a long grassed or planted stretch in between, reduces the level at larger distances, and a reading taken 1 m (about 3 ft) in front of a building's facade includes a reflection that usually adds about 3 dB.
- Wind direction and temperature gradients change the level at a neighbour by several decibels from day to day; the prediction is for neutral conditions.
- Plant moving along a haul road is a line source, not a point, and BS 5228-1 treats it with a different method; so is plant whose noise is tonal or impulsive, which assessments often penalise.
- It predicts the level; it does not say what is allowed. The limits at a neighbour come from the planning conditions, the local authority, a prior consent or a local noise ordinance.
- Vibration from piling, breaking and compaction is a separate assessment under BS 5228-2 and is not covered here.

## Sources

As the calculator cites them (sources checked 2026-09-21):

- BS 5228-1:2009+A1:2014, Annex F: from an activity LAeq measured at 10 m, the level at distance R over hard ground is LAeq,10m − 20 log10(R ÷ 10), with an on-time correction of 10 log10 of the fraction of the period the plant operates, and levels from several items combined on energy
- ISO 9613-2: geometric divergence from a point source is 20 log10(d) + 11 dB, so a source on hard ground radiating into a hemisphere gives LWA − 20 log10(R) − 8 at R metres
- BS 5228-1, Annex F: a barrier that just interrupts the line of sight between the plant and the receptor reduces the level by about 5 dB, and one that screens the plant completely by about 10 dB
- FHWA Roadway Construction Noise Model (RCNM), FHWA-HEP-05-054: Leq = Lmax at 50 ft − 20 log10(D ÷ 50) + 10 log10(usage factor ÷ 100) − shielding, with the items combined on energy

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What noise level is allowed at a neighbour's house?**

There is no single figure, but BS 5228-1's 'ABC method' offers daytime thresholds of 65, 70 or 75 dB LAeq at a dwelling, depending on how noisy the area already is. In the UK the limits themselves come from the planning conditions, from the local authority under the Control of Pollution Act, or from a prior consent the contractor applied for; the ABC method is in BS 5228-1's Annex E. In the US the limits are set by city and county noise ordinances and, on federally funded highway work, by the project's own criteria. This page predicts the level; the limit is somebody else's decision.

**Where do the reference levels come from?**

BS 5228-1 Annex C tabulates measured activity LAeq values at 10 metres (about 33 feet) for hundreds of items of construction plant — breakers, excavators, piling rigs, concrete pumps. The FHWA's RCNM carries an equivalent US table as maximum levels at 50 feet (15.24 metres). A manufacturer's declared sound power level is the third route. A measured level from the actual machine on a similar job beats all three.

**Why does doubling the distance only take off 6 dB?**

Sound from a single machine spreads over a growing hemisphere, and the area of a hemisphere grows with the square of its radius, so the energy per square metre falls by four times each time the distance doubles — which is 6 dB. Four times the distance is 12 dB, ten times is 20 dB. That is why moving a noisy item from the near edge of a site to the far edge usually helps more than anything short of a good barrier.

**How much does a site hoarding help?**

BS 5228-1 allows about 5 dB where the barrier just breaks the line of sight between the plant and the window, and about 10 dB where it hides the plant completely. It works best close to the noise or close to the listener, and it has to be solid and continuous — a gap at the gate or under the panels lets a large share of the sound through, for the same reason a crack spoils a sound-insulating wall.

## Related calculators

- [Decibel Addition and Background Correction Calculator](https://craftquantities.com/calculators/sustainability-compliance/decibel-addition-calculator/)
- [Daily Noise Exposure (LEP,d) Calculator](https://craftquantities.com/calculators/sustainability-compliance/daily-noise-exposure-calculator/)
- [Temporary Fence Wind Load Overturning Ballast Calculator](https://craftquantities.com/calculators/materials-quantities/temp-fence-wind-ballast-calculator/)
- [Temporary Construction Fence Panel Count Calculator](https://craftquantities.com/calculators/materials-quantities/temp-fence-panel-count-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/construction-noise-at-receptor-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/construction-noise-at-receptor-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `construction-noise-at-receptor-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/construction-noise-at-receptor-calculator.json

---
Source: https://craftquantities.com/calculators/sustainability-compliance/construction-noise-at-receptor-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.