# Solar Panel PV Wire Sizing Calculator

> Calculate the minimum conductor cross-sectional area needed for a PV circuit run at a target maximum voltage drop.

Page: https://craftquantities.com/calculators/solar-energy/solar-pv-wire-sizing-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-05, 2 published test vectors.

Minimum conductor cross-sectional area: 0.00844 in² for Circuit Current 10, System Voltage 48 and Maximum Allowable Voltage Drop 2, the page's opening figures; on the metric page, 10, 48 and 2 give 5.47 mm². Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Circuit Current (A) | `current` | 10 | 10 | range 1–50 |
| System Voltage (V) | `systemVoltage` | 48 | 48 | range 12–600 |
| One-Way Conductor Distance | `oneWayDistance` | 15 m | 49 ft | mm, cm, m, in, ft, yd; range 0.01–150 m |
| Maximum Allowable Voltage Drop (%) | `maxVoltageDropPercent` | 2 | 2 | range 1–3 |
| Copper Resistivity (Ω·mm²/m, ~0.0175 at 20°C, ~0.0213 at 75°C) | `copperResistivity` | 0.0175 | 0.0175 | range 0.015–0.025 |

- **Circuit Current (A)**: The expected current carried by the PV circuit conductor.
- **System Voltage (V)**: The nominal DC system voltage of the PV circuit.
- **One-Way Conductor Distance**: The one-way distance from the source (e.g. array/combiner box) to the load (e.g. inverter/battery).
- **Maximum Allowable Voltage Drop (%)**: The target maximum percentage of system voltage lost to conductor resistance.
- **Copper Resistivity (Ω·mm²/m, ~0.0175 at 20°C, ~0.0213 at 75°C)**: The resistivity of the conductor material at its expected operating temperature.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Minimum conductor cross-sectional area** | 5.47 mm² |

### US customary

| Result | Value |
|---|---|
| **Minimum conductor cross-sectional area** | 0.00844 in² |

- Confidence: medium.

## How it is worked out

Convert the resulting minimum cross-sectional area to the next larger standard wire gauge (AWG) or metric conductor size — do not round down. Also verify the selected conductor's ampacity rating (NEC Table 310.16, with appropriate temperature/conduit fill derating) independently meets or exceeds the circuit current.

The method, derived in full:

- [Voltage Drop and Conductor Sizing](https://craftquantities.com/methodology/voltage-drop-and-conductor-sizing/): Why the run length doubles, why a 12 V circuit suffers a hundred times the percentage loss of a 120 V one, and why ampacity answers a different question entirely.

What this calculation does not cover:

- Voltage drop is not ampacity, and none of the code side of the job is done here. The current is used exactly as typed, with no PV multiplier applied to it, no fuse or breaker sized, and no account taken of the temperature rating of the terminals the conductor lands in. A size that meets this drop target can still be thermally inadequate and non-compliant.
- Copper only. The resistivity field spans copper from cold to a conductor at its rated temperature; aluminium is about 1.6 times as resistive and does not fit inside that range, so an aluminium run has to be sized against the aluminium figure and comes out roughly two AWG sizes larger for the same drop.
- Nothing raises the resistivity for how hot the conductor actually gets. The figure is whatever you enter, so leaving the 20 °C (68 °F) table value in place understates the drop of a loaded circuit sitting in conduit on a sunlit roof by around a fifth against the 75 °C (167 °F) figure.
- Conductor metal only. MC4 connectors, fuse holders, breakers, combiner busbars and every termination in the run add resistance the formula never sees, so an assembled circuit drops more than the copper alone accounts for.
- This models a two-wire DC circuit carrying its full current over the whole run. It does not describe the inverter's AC output circuit, where reactance, power factor and the three-phase multiplier replace the factor of two, and it does not describe a home run that picks up further strings along its length.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-05):

- Conductor area = (2 x resistivity x one-way distance x current) ÷ maximum allowable voltage drop, the standard DC circuit voltage-drop sizing method applied to a solar PV source/output circuit run (the factor of 2 accounts for the round-trip conductor length)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does the formula multiply the distance by 2?**

The factor of 2 accounts for the round-trip conductor length — current flows out to the load through one conductor and back through the other, so both directions' resistance contribute to the voltage drop.

**Should I round the result down to the nearest standard wire size?**

No — always round up to the next larger standard wire gauge (AWG) or metric conductor size. Rounding down would result in a smaller conductor than the minimum needed to stay within your target voltage drop.

**Does meeting the voltage drop target mean the wire is properly sized?**

Not by itself — you also need to independently verify the selected conductor's ampacity rating (per NEC Table 310.16, with appropriate temperature and conduit fill derating) meets or exceeds the circuit current, since voltage-drop sizing and ampacity sizing are separate checks.

## Related calculators

- [Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)](https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/)
- [Solar Panel Array Sizing Calculator](https://craftquantities.com/calculators/solar-energy/solar-panel-array-sizing-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/solar-pv-wire-sizing-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/solar-pv-wire-sizing-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `solar-pv-wire-sizing-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/solar-pv-wire-sizing-calculator.json

---
Source: https://craftquantities.com/calculators/solar-energy/solar-pv-wire-sizing-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.