# Solar PV String Sizing Calculator

> Calculate the maximum number of solar panels that can be wired in series in one string without exceeding inverter/system voltage limits.

Page: https://craftquantities.com/calculators/solar-energy/pv-string-sizing-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Maximum panels per string: 13 panels for Maximum System/Inverter Voltage 600, Panel Open-Circuit Voltage Voc 40 and Low-Temperature Correction Factor 1.12, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Maximum System/Inverter Voltage (V) | `maxSystemVoltage` | 600 | 600 | range 100–1500 |
| Panel Open-Circuit Voltage Voc (V, at STC) | `panelVoc` | 40 | 40 | range 10–80 |
| Low-Temperature Correction Factor | `tempCorrectionFactor` | 1.12 | 1.12 | range 1–1.25 |

- **Maximum System/Inverter Voltage (V)**: The maximum allowable DC voltage for the inverter or system.
- **Panel Open-Circuit Voltage Voc (V, at STC)**: The panel's rated open-circuit voltage at Standard Test Conditions.
- **Low-Temperature Correction Factor**: Accounts for Voc increasing as ambient temperature drops. NEC Table 690.7(A) gives 1.12 for a record low of -1 to -5 C (31 to 23 F), and 1.16 by -11 to -15 C (13 to 5 F).

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Maximum panels per string** | 13 panels |
| Temperature-corrected Voc per panel | 44.8 V |

### US customary

| Result | Value |
|---|---|
| **Maximum panels per string** | 13 panels |
| Temperature-corrected Voc per panel | 44.8 V |

- Confidence: medium.

## How it is worked out

The correction factor depends on your site's record low ambient temperature and the panel manufacturer's temperature coefficient — use NEC Table 690.7(A) or the manufacturer's datasheet coefficient for your specific location, not an assumed value.

The working the page shows, in order: Temperature-corrected Voc per panel; then maximum panels per string.

The method, derived in full:

- [Photovoltaic Arrays, Inverters and Low-Voltage Runs](https://craftquantities.com/methodology/photovoltaic-and-low-voltage/): Why a solar string is limited by the coldest morning rather than the hottest day, why an array deliberately exceeds its inverter's rating, and why a small shadow can suppress a whole string.

What this calculation does not cover:

- This is the cold-weather upper voltage limit only. Nothing here checks the minimum string length: whether the string's operating voltage at the hottest expected cell temperature still sits above the inverter's MPPT window and start-up voltage. A string that passes this check can still be too short to make power on a hot afternoon.
- The calculation is voltage only. It does not look at short-circuit current, the module's maximum series fuse rating, the inverter's per-MPPT input current limit, conductor ampacity, or combiner fusing, so a string length that passes here has had only half of a string design checked.
- It applies whichever single voltage limit you type. It does not reconcile the inverter's maximum DC input against the module nameplate's own maximum system voltage rating or against the limit your code and occupancy impose - enter the lowest of the three, because the calculator cannot tell you which one governs. The Voc field also stops at 80 V, which covers crystalline silicon modules; thin-film modules run to several times that and will be clamped down to 80 V, returning a string far longer than the module can take.
- The calculator does no temperature arithmetic of its own. It never sees your site's record low ambient temperature or the module's Voc temperature coefficient - it multiplies by whatever factor you type, so a factor taken from the wrong row produces a confident, wrong answer. The factor field also stops at 1.25, the coldest row of NEC Table 690.7(A).
- This is a sizing check, not a design. It assumes every module in the string is identical and does not substitute for the inverter manufacturer's own string-sizing tool or for a design reviewed by the authority having jurisdiction.

A professional must decide:

- This is a sizing check, not a design. It assumes every module in the string is identical and does not substitute for the inverter manufacturer's own string-sizing tool or for a design reviewed by the authority having jurisdiction.
- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- Maximum panels per string = floor(maximum system voltage ÷ (panel open-circuit voltage × low-temperature correction factor)), per NEC 690.7 which requires PV source circuit voltage calculations to account for Voc increasing in cold temperatures using either the manufacturer's temperature coefficient or NEC Table 690.7(A) correction factors

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does cold weather matter for PV string sizing?**

A solar panel's open-circuit voltage (Voc) rises as its temperature drops. On a cold morning, an array's actual string voltage can exceed the value measured at Standard Test Conditions, so NEC 690.7 requires correcting Voc upward using a low-temperature correction factor before sizing the maximum string length.

**Where does the temperature correction factor come from?**

It comes from either the panel manufacturer's published temperature coefficient or NEC Table 690.7(A), applied to your site's record low ambient temperature — not an assumed or default value. Using the wrong factor for your climate can result in a string that exceeds the inverter's maximum voltage in cold conditions.

**Why is the result rounded down rather than to the nearest whole number?**

The maximum panels per string is floored (rounded down) because any fractional result means that many full panels' worth of voltage would still stay within the limit, while rounding up would push the string voltage over the maximum allowed.

## Related calculators

- [Solar Panel PV Wire Sizing Calculator](https://craftquantities.com/calculators/solar-energy/solar-pv-wire-sizing-calculator/)
- [Solar Panel Array Sizing Calculator](https://craftquantities.com/calculators/solar-energy/solar-panel-array-sizing-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/pv-string-sizing-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/pv-string-sizing-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `pv-string-sizing-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/pv-string-sizing-calculator.json

---
Source: https://craftquantities.com/calculators/solar-energy/pv-string-sizing-calculator/