# Solar Inverter Sizing Calculator

> Size an inverter to an array, including the deliberate over-sizing of DC to AC that improves real yield.

Page: https://craftquantities.com/calculators/solar-energy/inverter-sizing-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-08-27, 4 published test vectors.

Inverter AC rating: 5,000 W AC for Array DC rating 6000, DC to AC ratio 1.2 and System losses 14, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Array DC rating (W) | `arrayWatts` | 6000 | 6000 | range 100–1000000 |
| DC to AC ratio | `dcAcRatio` | 1.2 | 1.2 | range 1–1.6 |
| System losses (%) | `systemLossPercent` | 14 | 14 | range 5–40 |

- **Array DC rating (W)**: Total nameplate DC watts of the panels.
- **DC to AC ratio**: How much larger the array is than the inverter.
- **System losses (%)**: Soiling, wiring, mismatch, temperature and inverter efficiency.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Inverter AC rating** | 5,000 W AC |
| Inverter rating | 5 kW AC |
| Array DC rating | 6 kW DC |
| Realistic peak AC after losses | 5.16 kW |
| Headroom over realistic peak | -3.1 % |

### US customary

| Result | Value |
|---|---|
| **Inverter AC rating** | 5,000 W AC |
| Inverter rating | 5 kW AC |
| Array DC rating | 6 kW DC |
| Realistic peak AC after losses | 5.16 kW |
| Headroom over realistic peak | -3.1 % |

- Confidence: medium.

## How it is worked out

Capacity sizing only. String voltage limits, MPPT window, temperature coefficients and the local wiring rules all constrain the final selection.

The working the page shows, in order: Inverter rating; Array DC rating; Realistic peak AC after losses; Headroom over realistic peak; then inverter AC rating.

The method, derived in full:

- [Photovoltaic Arrays, Inverters and Low-Voltage Runs](https://craftquantities.com/methodology/photovoltaic-and-low-voltage/): Why a solar string is limited by the coldest morning rather than the hottest day, why an array deliberately exceeds its inverter's rating, and why a small shadow can suppress a whole string.

What this calculation does not cover:

- Does not check string voltage against the inverter's MPPT window or its maximum input voltage — cold-weather open-circuit voltage is what breaks inverters and it depends on the panel's temperature coefficient.
- Does not consider grid export limits, which in several markets cap the inverter rather than the array.
- Shading is not modelled. Partial shading is better addressed with optimisers or microinverters than with sizing.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-08-27):

- DC-to-AC ratio (ILR) of 1.1-1.3 is standard practice; NREL SAM documentation and inverter manufacturers' design guides
- IEC 62109 and local wiring rules govern the electrical design; this sizes capacity only

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is the inverter smaller than the array?**

Because the array almost never produces its nameplate. Standard Test Conditions are 1000 W/m² at 25 °C cell temperature, which in the field happens for a handful of hours a year — panels run hot and lose output as they do. An inverter matched to the nameplate is idle capacity for the whole rest of the year, so the array is deliberately over-sized against it.

**Does over-sizing waste energy?**

A little, at the very top. When DC output exceeds the inverter's rating it clips, and that energy is lost. At a 1.2 ratio the clipping loss is typically well under 1% annually, against a much larger gain in the many partial-output hours. Above about 1.3 the trade starts running the other way.

**What actually limits inverter choice?**

String voltage more often than power. The array's open-circuit voltage rises as temperature falls, and the cold-morning figure must stay inside the inverter's maximum input — exceeding it damages the unit. Power sizing is the easy half of the problem; the voltage window is the half that needs the panel's temperature coefficient and your local record low.

## Related calculators

- [Solar Panel Array Sizing Calculator](https://craftquantities.com/calculators/solar-energy/solar-panel-array-sizing-calculator/)
- [Battery Bank Sizing Calculator](https://craftquantities.com/calculators/solar-energy/battery-bank-sizing-calculator/)
- [Solar Panel PV Wire Sizing Calculator](https://craftquantities.com/calculators/solar-energy/solar-pv-wire-sizing-calculator/)
- [Solar Payback Period Calculator](https://craftquantities.com/calculators/solar-energy/solar-payback-period-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/inverter-sizing-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/inverter-sizing-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `inverter-sizing-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/inverter-sizing-calculator.json

---
Source: https://craftquantities.com/calculators/solar-energy/inverter-sizing-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.