# Worst-Case Envelope Depressurisation Calculator

> Worst-case depressurisation of a home with all exhausts running, from a blower-door result and net exhaust flow, beside the limit your code sets.

Page: https://craftquantities.com/calculators/plumbing-hvac/worst-case-depressurisation-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-08-30, 2 published test vectors.

Worst-case envelope depressurisation: 17 Pa for Envelope Leakage at the Test Pressure 1059.44 CFM, the page's opening figures; on the metric page, 500 L/s gives 17 Pa. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Envelope Leakage at the Test Pressure | `envelopeLeakage` | 500 L/s | 1059.44 CFM | lps, m3h, lpm, cfm; range 47–4720 L/s |
| Blower-Door Reference Pressure (Pa) | `referencePressure` | 50 | 50 | range 25–75 |
| Envelope Flow Exponent | `flowExponent` | 0.65 | 0.65 | range 0.5–1 |
| Total Simultaneous Exhaust Flow | `totalExhaustFlow` | 250 L/s | 529.72 CFM | lps, m3h, lpm, cfm; range 0–2360 L/s |
| Balanced Mechanical Supply Flow | `mechanicalSupplyFlow` | 0 L/s | 0 CFM | lps, m3h, lpm, cfm; range 0–2360 L/s |
| Interlocked Makeup Air | `makeupAirFlow` | 0 L/s | 0 CFM | lps, m3h, lpm, cfm; range 0–2360 L/s |
| Permitted Depressurisation Limit (Pa) | `permittedLimit` | 5 | 5 | range 1–50 |

- **Envelope Leakage at the Test Pressure**: Airflow the blower door had to move to hold the envelope at its reference pressure.
- **Blower-Door Reference Pressure (Pa)**: Pressure difference the leakage figure above was measured at.
- **Envelope Flow Exponent**: Exponent in the leakage power law, from a multi-point test report where one exists.
- **Total Simultaneous Exhaust Flow**: Everything that can exhaust at once: range hood, dryer, bathroom fans, central vacuum, and the exhaust side of the recovery unit.
- **Balanced Mechanical Supply Flow**: Supply air the ventilation system delivers while the worst case is running.
- **Interlocked Makeup Air**: Dedicated makeup air that is interlocked to open or run whenever the large exhaust appliance does.
- **Permitted Depressurisation Limit (Pa)**: The cap the governing code or standard applies to this building.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Worst-case envelope depressurisation** | 17 Pa |
| Net exhaust flow across the envelope | 250 L/s |
| Permitted depressurisation | 5 Pa |
| Margin to the limit | -12.21 Pa |
| Net exhaust the envelope carries at the limit | 111.94 L/s |

### US customary

| Result | Value |
|---|---|
| **Worst-case envelope depressurisation** | 17 Pa |
| Net exhaust flow across the envelope | 529.72 CFM |
| Permitted depressurisation | 5 Pa |
| Margin to the limit | -12.21 Pa |
| Net exhaust the envelope carries at the limit | 237.18 CFM |

- Confidence: low.

## How it is worked out

This configuration exceeds the limit on the power-law estimate, and the remedies are interlocked makeup air, a sealed-combustion appliance, or a smaller hood — never a note in the handover pack asking the occupants to crack a window. Confirm with a blower door and a manometer before changing the design.

The working the page shows, in order: Net exhaust flow across the envelope; Permitted depressurisation; Margin to the limit; Net exhaust the envelope carries at the limit; then worst-case envelope depressurisation.

The method, derived in full:

- [Containment, Capture and Process Airflow](https://craftquantities.com/methodology/containment-and-process-airflow/): Why a leaky asbestos enclosure needs more air rather than less, why an island cooker hood needs far more than a wall one, and why a powered attic fan can pull conditioned air out of the house it is cooling.

What this calculation does not cover:

- Ignores stack effect and wind, both of which add to or subtract from the mechanical pressure and can dominate on a cold or exposed day.
- Treats the envelope as one zone. A closed interior door between the exhaust and the leakage it draws through creates a worse local pressure than this whole-building figure.

## Sources

As the calculator cites them (sources checked 2026-08-30):

- Envelope leakage follows the power law Q = C x dP^n, so a single-point blower-door result at a stated reference pressure gives dP = P_ref x (Q_net / Q_ref)^(1/n) for any other flow
- CSA F326, Residential Mechanical Ventilation Systems, together with the applicable mechanical and fuel-gas codes, sets the depressurisation limit and the exhaust capacity at which dedicated makeup air becomes mandatory — both are jurisdictional, which is why the limit is entered here rather than published by this page
- A flow exponent of 0.65 is the conventional assumption for a house envelope when the test report gives no measured exponent; it is a rule of thumb, not a property of your building, and a measured exponent from a multi-point test should replace it

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Can this replace a worst-case depressurisation test?**

It cannot, and it is not meant to. The test is one blower door setup and a manometer: close the envelope, run every exhaust appliance at once with interior doors in their worst positions, and read the pressure with reference to outdoors. What this page does is tell you before you get there whether the design has any chance of passing, and what would have to change if it does not.

**Why does the flow exponent matter so much?**

Because the answer is an extrapolation from 50 Pa down to a handful of pascals, which is a long way outside the range the test measured. Over that span the exponent, not the leakage figure, decides how fast the curve falls away — the same house can read several pascals differently at n = 0.55 and n = 0.75. A multi-point test report gives the measured value and is worth asking for.

**Does a passive makeup-air vent count?**

Not in this calculation. Only provision that is interlocked to the appliance — a motorised damper and a fan that run whenever the hood runs — reliably delivers air at the moment the building is most negative. A hole in the wall with no control delivers whatever the pressure difference happens to push through it, which is the very quantity in question.

**Which appliances belong in the simultaneous exhaust total?**

Everything that can be running at the same moment and discharges outdoors: the range hood at boost, the clothes dryer, every bathroom and utility fan, a central vacuum vented outside, and the exhaust side of the recovery ventilator. A solid-fuel appliance drawing on its flue belongs there too, because it is exhausting whether or not it has a fan.

## Related calculators

- [Blower Door CFM50 Target Calculator](https://craftquantities.com/calculators/insulation-efficiency/blower-door-cfm-target-calculator/)
- [Appliance Combustion Air Free Area Calculator (Indoor Air Method)](https://craftquantities.com/calculators/materials-quantities/combustion-air-free-area-calculator/)
- [Commercial Kitchen Ventilation Hood Exhaust CFM Calculator](https://craftquantities.com/calculators/materials-quantities/kitchen-hood-exhaust-cfm-calculator/)
- [ERV/HRV Sizing Calculator](https://craftquantities.com/calculators/insulation-efficiency/erv-hrv-sizing-calculator/)
- [Range Hood and Cooker Hood Airflow Calculator (CFM, L/s and Make-Up Air)](https://craftquantities.com/calculators/plumbing-hvac/range-hood-airflow-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/worst-case-depressurisation-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/worst-case-depressurisation-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `worst-case-depressurisation-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/worst-case-depressurisation-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/worst-case-depressurisation-calculator/