# Tankless Water Heater Sizing Calculator

> Size an instantaneous water heater from simultaneous flow and the temperature rise your incoming water actually needs.

Page: https://craftquantities.com/calculators/plumbing-hvac/tankless-water-heater-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.0, sources checked 2026-10-31, 4 published test vectors.

Heater output required: 25.4 kW for Incoming water temperature 50 °F and Delivered temperature 107.6 °F, the page's opening figures; on the metric page, 10 °C and 42 °C give 26.8 kW. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Simultaneous flow | `flowRate` | 12 L/min | 3 gal/min | lpm, lps, gpm; range 1–200 L/min |
| Incoming water temperature | `incomingTempC` | 10 °C | 50 °F | c, f, k; range -2–30 °C |
| Delivered temperature | `outletTempC` | 42 °C | 107.6 °F | c, f, k; range 25–80 °C |

- **Simultaneous flow**: Total flow of the fixtures used at once.
- **Incoming water temperature**: Cold mains temperature in winter.
- **Delivered temperature**: Temperature at the outlet.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Heater output required** | 26.8 kW |
| Temperature rise | 32 K |
| BTU/h | 91,412.64 BTU/h |
| Flow in US GPM | 3.17 GPM |
| Flow in gallons per hour | 190.2 GPH |

### US customary

| Result | Value |
|---|---|
| **Heater output required** | 25.4 kW |
| Temperature rise | 32 K |
| BTU/h | 86,508.62 BTU/h |
| Flow in US GPM | 3 GPM |
| Flow in gallons per hour | 180 GPH |

## How it is worked out

Exact thermodynamics for the stated flow and rise. Real units are rated at a specific rise, so compare against the manufacturer's flow-at-rise table rather than a headline kW.

The working the page shows, in order: Temperature rise; BTU/h; Flow in US GPM; Flow in gallons per hour; then heater output required.

The method, derived in full:

- [Sensible Heat and Flow](https://craftquantities.com/methodology/sensible-heat-and-flow/): The single equation behind water heater sizing, duct heating and every temperature-rise problem on the site.

What this calculation does not cover:

- Gas units need adequate supply pipe and flue; an undersized gas run limits output regardless of the appliance rating.
- Electric units of this size often need a dedicated high-current supply that many domestic boards cannot provide.
- Assumes no simultaneous demand beyond what you entered. A tankless unit does not run out of hot water, but it does run out of flow.

A professional must decide:

- Water: supply and drainage design, and work on them, are for a licensed plumber under the local plumbing rules.

## Sources

As the calculator cites them (sources checked 2026-10-31):

- Q = ṁ · c · ΔT. For water: kW = L/min × ΔT × 0.0698 (from 4.186 kJ/kg·K)
- Typical fixture flows: shower 7-11 L/min, basin 4-6, kitchen sink 6-9 — WaterSense and UK Water Regulations fittings data

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does the winter mains temperature matter so much?**

Because it sets the rise, and the rise is directly proportional to the power needed. Going from 15 °C summer mains to 4 °C winter mains raises the required output by about 40% for the same shower. A unit sized in July disappoints in January, and that is the single most common complaint about tankless heaters.

**Will it run out of hot water?**

No — it runs out of flow instead. A tankless unit heats indefinitely, but only as much water per minute as its rating allows at your rise. Open a second shower and either both drop in temperature or the unit limits flow. That is the trade against a cylinder, which has a fixed quantity but no flow limit.

**Can I run one on a normal electrical supply?**

Rarely, at whole-house size. Twenty-three kilowatts is exactly 100 A at 230 V, and a whole-house flow at a winter rise sizes above that whichever units you enter it in — more current than most domestic supplies can provide. Electric tankless units are practical for a single outlet; whole-house instantaneous heating is usually gas for exactly this reason.

## Related calculators

- [Water Heater Sizing Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-heater-sizing-calculator/)
- [Water Heater Recovery Time Calculator](https://craftquantities.com/calculators/plumbing-hvac/water-heater-recovery-time-calculator/)
- [Domestic Water Pipe Sizing by Fixture Unit Calculator](https://craftquantities.com/calculators/materials-quantities/domestic-water-pipe-sizing-calculator/)
- [Domestic Hot Water Recirculation Flow Calculator](https://craftquantities.com/calculators/materials-quantities/dhw-recirculation-flow-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/tankless-water-heater-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/tankless-water-heater-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `tankless-water-heater-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/tankless-water-heater-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/tankless-water-heater-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.