# Stack Effect Pressure Calculator

> Stack effect pressure across an opening from its height off the neutral plane and the indoor-outdoor temperature difference, and the air speed it drives.

Page: https://craftquantities.com/calculators/plumbing-hvac/stack-effect-pressure-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-09-22, 4 published test vectors.

Stack pressure across the opening: 5.21 Pa for Height of the Opening From the Neutral Pressure Plane 19.5 ft, Inside Temperature 64.4 °F and Outside Temperature 28.4 °F, the page's opening figures; on the metric page, 6 m, 18 °C and -2 °C give 5.26 Pa. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Height of the Opening From the Neutral Pressure Plane | `height` | 6 m | 19.5 ft | mm, cm, m, in, ft, yd; range 0–500 m |
| Where the Opening Is | `position` | Below the neutral plane — a door, a low vent | Below the neutral plane — a door, a low vent | `below`, `above` |
| Inside Temperature | `insideTemp` | 18 °C | 64.4 °F | c, f, k; range -20–50 °C |
| Outside Temperature | `outsideTemp` | -2 °C | 28.4 °F | c, f, k; range -40–50 °C |
| Discharge Coefficient of the Opening | `dischargeCoefficient` | 0.65 | 0.65 | range 0.3–1 |

- **Height of the Opening From the Neutral Pressure Plane**: How far the opening is below (or above) the level where inside and outside pressures are equal.
- **Where the Opening Is**: Sets the direction the air moves; the size of the pressure depends only on the height.
- **Inside Temperature**: The air temperature inside the building.
- **Outside Temperature**: The outdoor air temperature.
- **Discharge Coefficient of the Opening**: How much of the ideal flow a real opening passes — about 0.65 for a large opening.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Stack pressure across the opening** | 5.26 Pa |
| The same pressure in inches of water gauge (in. w.g.) | 0.02 in. w.g. |
| Outdoor air density | 1.3 kg/m³ |
| Air speed through the opening at this discharge coefficient | 1.85 m/s |

### US customary

| Result | Value |
|---|---|
| **Stack pressure across the opening** | 5.21 Pa |
| The same pressure in inches of water gauge (in. w.g.) | 0.02 in. w.g. |
| Outdoor air density | 0.08 pcf |
| Air speed through the opening at this discharge coefficient | 362.08 ft/min |

- Confidence: medium.

## How it is worked out

Outside air is pushed in through this opening: the building is warmer than outside and the opening is below the neutral plane, or cooler and above it. The pressure grows in a straight line with the height from the neutral plane and with the temperature difference.

The working the page shows, in order: The same pressure in inches of water gauge (in. w.g.); Outdoor air density; Air speed through the opening at this discharge coefficient; then stack pressure across the opening.

The method, derived in full:

- [Airtightness, Infiltration and Moisture](https://craftquantities.com/methodology/airtightness-and-infiltration/): Why a blower-door result is not an air change rate, why a leak at the top of a house matters far more than the same leak halfway up, and why sealing without ventilating moves the problem rather than solving it.

What this calculation does not cover:

- The neutral plane's position is an estimate: mid-height for evenly spread openings, lower when the large openings are low. Wind adds its own pressures on top, and on an exposed door it can dominate.
- The air speed is an order-of-magnitude figure. Discharge coefficients vary with the opening's shape, and flow through a large door is two-way — out at the top while it comes in at the bottom.
- Mechanical ventilation that holds the building above or below outside pressure moves the neutral plane and can reverse the flow at a given opening.

## Sources

As the calculator cites them (sources checked 2026-09-22):

- ASHRAE Handbook—Fundamentals, Chapter 16, Ventilation and Infiltration: stack pressure Δp = ρo × g × (H_NPL − H) × (Ti − To) ÷ Ti, temperatures absolute; flow through a large opening with a discharge coefficient of about 0.65
- Outdoor air density from the ideal gas law: ρ = 101,325 Pa ÷ (287.055 J/kg·K × T), dry air at standard pressure

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does an open dock door cost so much heat?**

Because a few pascals across a large opening move a great deal of air. The guide's 12 m (39 ft) shed with 20 K (36 °F) across its walls sees about five pascals at floor level, enough to drive roughly two metres a second (400 ft/min) inward across the bottom of an open door — tens of thousands of cubic metres an hour to be heated through that difference.

**Where is the neutral pressure plane?**

Where the inside and outside pressures are equal. With leakage spread evenly it sits near mid-height; a big opening low down pulls it down, and a building held above outside pressure by its ventilation shifts it too. Above it air leaves the building in winter; below it air comes in.

**Why are the temperatures absolute?**

Because the effect comes from the difference in air density, and density follows the absolute temperature. The formula divides by the indoor temperature in kelvin, which is why the same 20 degrees does slightly more on a cold day than on a mild one.

## Related calculators

- [Air Permeability (q50) and Test Flow Calculator](https://craftquantities.com/calculators/insulation-efficiency/air-permeability-q50-calculator/)
- [Air Changes Per Hour (ACH50) Calculator](https://craftquantities.com/calculators/insulation-efficiency/air-changes-per-hour-calculator/)
- [HVAC Thermal Load (U-Value) Calculator](https://craftquantities.com/calculators/plumbing-hvac/hvac-thermal-load-calculator/)
- [Blower Door CFM50 Target Calculator](https://craftquantities.com/calculators/insulation-efficiency/blower-door-cfm-target-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/stack-effect-pressure-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/stack-effect-pressure-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `stack-effect-pressure-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/stack-effect-pressure-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/stack-effect-pressure-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.